2
www.goodmanmfg.com
SS-GSZ14
SS-GSZ14
www.goodmanmfg.com
3
Product Specifications
GSZ14
0181K*
GSZ14
0191A*
GSZ14
0241K*
GSZ14
0251A*
GSZ14
0301K*
GSZ14
0311A*
Nominal Capacities
Cooling (BTU/h)
18,000
17,400
24,000
23,200
30,000
28,000
Heating (BTU/h)
18,000
18,000
24,000
23,200
30,000
31,000
Decibels
72
72
72
72
74
75
Compressor
RLA
9.0
9.0
10.9
10.9
13.5
13.5
LRA
47.5
47.5
62.9
62.9
72.5
72.5
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Condenser Fan Motor
Horsepower
1/6
1/6
1/6
1/6
1/6
1/6
FLA
0.95
1.1
0.95
1.1
0.95
1.10
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
¾"
¾"
¾"
¾"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.)
¾"
¾"
¾"
¾"
¾"
¾”
Standard Line Set Length (max. feet)
80
80
80
80
80
80
Long Line Set Length (max. feet) ²
Equivalent Length
250
250
250
250
250
250
Linear Length
200
200
200
200
200
200
Vertical Length (outdoor below indoor)
80
80
80
80
80
80
Vertical Length (outdoor above indoor)
80
200
80
200
80
200
Valve Connection Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge (oz.)
108
108
108
108
108
160
Electrical Data
Volts/Phase (60 Hz)
208-230/1
208-230/1
208-230/1
208-230/1
208-230/1
208-230/1
Minimum Circuit Ampacity ³
12.2
12.4
14.6
14.7
17.8
17.9
Max. Overcurrent Protection ⁴
20
20
25
25
30
30
Min / Max Volts
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197/253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
1/2" or 3/4"
Unit Weights
Equipment Weight (lbs.)
143
143
143
143
171
186
Ship Weight (lbs)
154
154
154
154
182
206
ENERGY STAR® Certified ^
NO
NO
NO
^ Energy Star Notes
Proper sizing and installation of equipment is critical to achieving optimal performance. Split system air conditioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinations certified to meet ENERGY STAR requirements. See Page 24 for all ENERGY STAR certified combinations
as of this document’s revision date.
¹ Tested and rated in accordance with ARI Standard 210/240
² Reference TP-107* for additional application requirements
³ Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
⁴ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
•
Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
•
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
•
Installation of these units may require the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT
NOT THE INDOOR COIL.