PRODUCT DESIGN

4

GSZ14 models are available in 1 1/2 through 5 ton sizes and
use R-410A refrigerant. They are designed for 208/230 volt
single phase applications.

The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then dis-
charged out of the top of the cabinet.

These units are designed for free air discharge, so no addi-
tional resistance like duct work shall be attached.

The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type cop-
per. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal in-
stallation is factory installed in the condensing unit. GSZ units
are charged for the matching evaporator coil and a 15 foot
refrigerant line set.

Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent.  It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.

GSZ models use high-efficiency Copeland

®

 scroll  "Ultratech"

compressors which are specifically desgined for R-410A re-
frigerant. There are a number of design characteristics which
are different from the scroll compared to the traditional recip-
rocating compressor.

"Ultratech" Series scroll compressors with Copeland

®

ComfortAlert diagnositics will not have a discharge thermo-
stat. Some of the early model scroll compressors required
discharge thermostats.

Due to their design Scroll compressors are inherently more
tolerant of small quantities of liquid refrigerant.

NOTE:  Even though the compressor section of a Scroll com-
pressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.

"Ultratech" Series scroll compressors use "POE" or
polyolester oil  which is 

NOT

 compatible with mineral oil based

lubricants like 3GS.  "POE"  oil must be used if additional oil
is required.

WARNING

To avoid possible injury, explosion or death, practice
safe handling of refrigerants.

Operating pressures and amp draws may differ from stan-
dard reciprocating and/or scroll compressors.  This informa-
tion may be found in the "Cooling Performance Data" sec-
tion.

This unit is for outdoor installation only. Refer to minimum
figure for clearances from the sides of the unit to full walls
and other objects.

NOTE:

 This unit cannot be completely enclosed. At least

one side must be unrestricted.

These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for ex-
ample, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.

DO 

NOT

 locate the unit:

* Directly under a vent termination for a gas appliance.

* Within 3 feet of a clothes drier vent

* Where the refreezing of defrost water would create

a hazard

* Where water may rise into the unit.

OK!

OK!

AA

AA

A

A

C

C

C

C

OK!

OK!

OK!

OK!

NOT

RECOMMENDED

AA

AA

AA

AA

AA

B

B

B

B

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12"

12"

18"

24"

Minimum Airflow Clearance

Model

Dimensions - W x D x H

GSZ140181A*

29 x 29 x 34¼

GSZ140241A*

29 x 29 x 38¼

GSZ140301A*

29 x 29 x 38¼

GSZ140361A*

29 x 29 x 38¼

GSZ140421A*

35½ x 35½ x 38¼

GSZ140481A*

35½ x 35½ x 38¼

GSZ140601A*

35½ x 35½ x 38¼

Содержание GSZ 14 SEER

Страница 1: ...number information Models listed on page 3 RT6213007 February2011 Copyright 2011 Goodman Manufacturing Company L P TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL AL...

Страница 2: ...any jurisdictions require a license to install or service heating and air conditioning equipment WARNING WARNING WARNING WARNING ONLY individuals meeting at a mininum the requirements of an Entry Leve...

Страница 3: ...e with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING WARNING To prevent the risk o...

Страница 4: ...re tolerant of small quantities of liquid refrigerant NOTE Even though the compressor section of a Scroll com pressor is more tolerant of liquid refrigerant continued floodback or flooded start condit...

Страница 5: ...d TXV Kit to be installed on the indoor coil THE SPECIFIED TXV IS DETERMINED BY THE OUTDOORUNIT NOTTHEINDOORCOIL GSZ140181A GSZ140601A GSZ140181A GSZ140241A GSZ140301A GSZ140361A GSZ140421A GSZ140481A...

Страница 6: ...16 3 17 7 19 0 14 7 15 1 16 4 17 6 S T 0 84 0 75 0 57 0 36 0 87 0 78 0 59 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 65 0 42 0 96 0 86 0 65 0 42 Delta T 20 19 15 11 21 19 16 11 21 19 16...

Страница 7: ...4 252 266 277 266 286 302 315 303 326 344 359 341 367 387 404 376 405 428 446 LO PR 104 111 121 129 110 117 128 136 115 122 133 142 120 128 140 149 126 134 147 156 131 139 152 161 MBh 18 6 18 9 19 8 2...

Страница 8: ...25 3 19 6 20 2 21 8 23 4 S T 0 86 0 77 0 58 0 37 0 89 0 79 0 60 0 39 0 91 0 81 0 62 0 40 0 94 0 84 0 64 0 41 0 98 0 87 0 66 0 42 0 98 0 88 0 67 0 43 Delta T 20 18 15 10 20 18 15 10 20 18 15 10 20 19...

Страница 9: ...277 289 278 299 315 329 316 340 359 375 356 383 404 422 393 423 447 466 LO PR 108 115 125 133 114 121 132 141 118 126 138 146 124 132 144 154 130 139 151 161 135 143 157 167 MBh 24 8 25 2 26 4 28 2 24...

Страница 10: ...26 1 28 3 30 3 23 5 24 2 26 2 28 1 S T 0 89 0 80 0 61 0 39 0 93 0 83 0 63 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 66 0 43 1 00 0 91 0 69 0 44 1 00 0 92 0 69 0 45 Delta T 20 18 15 10 20 19 15 11 20 19 15...

Страница 11: ...43 261 276 287 276 297 313 327 314 338 357 372 353 380 402 419 390 420 444 463 LO PR 110 117 127 136 116 123 135 143 120 128 140 149 126 135 147 156 133 141 154 164 137 146 159 170 MBh 29 7 30 3 31 7...

Страница 12: ...0 25 6 26 3 28 5 30 6 S T 0 82 0 74 0 56 0 36 0 85 0 76 0 58 0 37 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 94 0 84 0 63 0 41 0 95 0 85 0 64 0 41 Delta T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 1...

Страница 13: ...03 316 303 326 344 359 345 371 392 409 388 417 441 460 429 461 487 508 LO PR 115 122 133 142 121 129 141 150 126 134 146 156 132 141 154 164 139 148 161 172 144 153 167 178 MBh 32 4 33 0 34 6 36 9 31...

Страница 14: ...6 33 6 36 4 39 0 S T 0 88 0 79 0 60 0 38 0 91 0 82 0 62 0 40 0 94 0 84 0 63 0 41 0 97 0 86 0 65 0 42 1 00 0 90 0 68 0 44 1 00 0 90 0 68 0 44 Delta T 20 19 15 11 21 19 16 11 21 19 16 11 21 19 16 11 21...

Страница 15: ...39 257 272 284 272 293 309 322 310 333 352 367 349 375 396 413 385 414 438 456 LO PR 105 112 122 130 111 118 129 138 116 123 134 143 121 129 141 150 127 135 148 157 132 140 153 163 MBh 41 3 42 1 44 1...

Страница 16: ...7 45 1 48 5 37 5 38 6 41 8 44 9 S T 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 99 0 88 0 67 0 43 1 00 0 89 0 67 0 43 Delta T 21 19 16 11 21 20 16 11 21 20 16 11...

Страница 17: ...9 257 271 283 271 292 308 322 309 333 351 366 348 374 395 412 384 413 436 455 LO PR 104 110 121 128 110 117 127 136 114 121 132 141 120 127 139 148 125 133 146 155 130 138 151 160 MBh 47 5 48 4 50 7 5...

Страница 18: ...5 59 5 46 1 47 5 51 4 55 1 S T 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 40 0 96 0 86 0 65 0 42 0 97 0 87 0 66 0 42 Delta T 21 19 16 11 21 20 16 11 21 20 16 11 21 2...

Страница 19: ...1 259 274 285 274 295 311 325 312 336 354 370 351 378 399 416 388 417 441 460 LO PR 101 107 117 125 107 113 124 132 111 118 129 137 116 124 135 144 122 130 142 151 126 134 147 156 MBh 58 3 59 4 62 2 6...

Страница 20: ...294 85 57 913 41 472 16 440 4 428 90 57 206 41 626 15 580 4 547 95 56 500 41 764 14 736 4 666 100 55 088 41 492 13 596 4 767 105 53 675 41 180 12 495 4 868 110 51 698 39 829 11 869 4 955 115 49 720 3...

Страница 21: ...3 35 3 16 2 81 2 65 2 50 2 39 2 33 2 14 1 94 1 73 1 52 1 28 EER 14 5 14 0 13 4 12 8 12 4 12 1 11 4 10 8 9 6 9 1 8 5 8 2 7 9 7 3 6 6 5 9 5 2 4 4 HI PR 373 358 344 329 321 315 303 290 278 266 255 249 24...

Страница 22: ...30 25 20 17 15 10 5 0 5 10 MBh 57 8 54 7 51 5 48 2 46 0 44 6 41 4 38 2 36 6 33 8 31 1 29 4 28 3 25 4 22 5 19 6 16 8 13 7 Delta T 34 5 32 7 30 8 28 8 27 5 26 6 24 7 22 8 21 9 20 2 18 6 17 6 16 9 15 2...

Страница 23: ...01 Basic Unit without Auxiliary Heat Capacity of Unit With KW of Auxiliary heat Outdoor Ambient F Model SZ140301A CA F3642 6A TXV MBR1600 1 Conditions 1050 CFM Indoor Air 70 F DB capacity btuh c o p...

Страница 24: ...0 55 106 93 35 38 18 3 17 54 56 70 94 87 33 103 71 30 36 62 2 94 53 00 69 38 85 76 102 15 25 33 80 2 77 50 18 66 56 82 94 99 32 20 31 12 2 61 47 50 63 89 80 27 96 65 15 28 30 2 43 44 68 61 06 77 45 93...

Страница 25: ...ht increase will occur in indoor temperature drop Delta T A slight decrease will occur in low and high side pressures and power A properly operating unit should be within plus or minus 2 degrees of th...

Страница 26: ...S LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF RUN CAPACITOR FOR COMPRESSOR FAN RVC REVERSING VALVE COIL SA START ASSIST SC START CAPACITOR FOR COMPRESSOR OPTI...

Отзывы: