CONDENSING UNIT SPECIFICATIONS
9
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
GSX130[18-36]1D*
GSX130181E*
(1)
Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
* Line sizes denoted for less than 25' line sets, tested and rated in accordance with AHRI Standard 210/240. For other line-set lengths or sizes, refer to
the Installation and Operating Instructions and/or the long line-set guidelines.
GSX130181E*
Nominal Cooling Capacity, BTUH
17,800
SEER/EER
13 / 11
Compressor
R.L. Amps
6.70
L.R. Amps
41.0
High Pressure Switch
Open
N/A
Close
YES
Condenser Fan Motor
Horsepower
1/8
F.L. Amps
0.70
Liquid Line, Inches O.D.*
3/8"
Suction Line, Inches O.D.*
3/4"
Refrigerant Charge
73.0
Power Supply
208/230-60-1
Minimum Circuit Ampacity
(1)
9.1
Maximum Overcurrent Device
(2)
15
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
Approximate Shipping Weight
120
GSX130181D*
GSX130241D*
GSX130301D*
GSX130361D*
Nominal Cooling Capacity, BTUH
18,000
24,000
30,000
36,000
SEER/EER
13 / 11
13 / 11
13 / 11
13 / 11
Compressor
R.L. Amps
6.70
13.5
12.80
14.1
L.R. Amps
40.0
58.3
64.0
77.0
High Pressure Switch
Open
N/A
N/A
N/A
N/A
Close
N/A
N/A
N/A
N/A
Condenser Fan Motor
Horsepower
1/8
1/8
1/8
1/4
F.L. Amps
0.70
0.70
0.70
1.50
Liquid Line, Inches O.D.*
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.*
3/4"
3/4"
3/4"
7/8"
Refrigerant Charge
70.0
76.0
76.0
77.0
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity
(1)
9.1
17.6
16.7
19.1
Maximum Overcurr ent Device
(2)
15
30
25
30
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
120
130
130
140