CONDENSING UNIT SPECIFICATIONS
9
VSC130181A* - VSC130301B*
VSC130[18-60]1*
VSC130361A* - VSC130601A*
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
(3)
Installer will need to supply 3/4" to 7/8" adapters for suction line connectors
(4)
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit
breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
VSC130181A*
VSC130181B*
VSC130241A*
VSC130301A*
VSC130301B*
Nominal Cooling Capacity, BTUH
18,000
18,000
24,000
30,000
30,000
Compressor
R.L. Amps
6.78
6.78
7.7
9.7
9.7
L.R. Amps
40
40
40
49
49
Condenser Fan Motor
Horsepower
1/6
1/6
1/6
1/6
1/6
F.L. Amps
1.5
1.1
1.5
1.5
1.1
Refrigerant Line Size
Liquid Line, Inches O.D.
3/8"
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.
3/4"
3/4"
3/4"
3/4"
3/4"
Refrigerant Connection Size
Liquid Line, Inches O.D.
3/8"
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.
3/4"
3/4"
3/4"
3/4"
3/4"
Refrigerant Charge
82
67
83
106
87
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Am pacity
(1)
9.98
9.6
11.2
13.6
13.2
Maximum Overcurrent Device
(2)
15
15
15
20
20
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
141
128
150
195
156
VSC130361A*
VSC130361B*
VSC130421A*
VSC130481A*
VSC130601A*
Nominal Cooling Capacity, BTUH
36,000
36,000
42,000
48,000
60,000
Compressor
R.L. Amps
12.2
12.2
14.7
16.9
25.0
L.R. Amps
73
73
77
86
148
Condenser Fan Motor
Horsepower
1/6
1/6
1/4
1/4
1/6
F.L. Amps
1.5
1.1
1.8
1.5
1.1
Refrigerant Line Size
Liquid Line, Inches O.D.
3/8"
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.
7/8"
7/8"
1-1/8"
1-1/8"
1-1/8"
Refrigerant Connection Size
Liquid Line, Inches O.D.
3/8"
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.
3/4"
3
3/4"
3
7/8"
4
7/8"
4
7/8"
4
Refrigerant Charge
119
83
135
145
167
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Am pacity
(1)
16.8
16.4
20.2
22.7
32.3
Maximum Overcurrent Device
(2)
25
25
30
40
50
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
199
189
199
198
242