Goodman GPG16 Скачать руководство пользователя страница 6

6

C

OMPRESSOR

 P

ROTECTION

 D

EVICES

This gas/electric package unit includes components which are
designed to protect the compressor against abnormal operat-
ing conditions.

NOTE: 

The operation of the indoor blower will not be affected by

any compressor protection devices.
If, during a call for cooling, the indoor fan runs and circulates
room temperature air while the compressor and outdoor fan do
not operate:

1. Wait five minutes, as a protection device may be holding the

compressor off.

2. Check the room thermostat to see if it is correctly set.

3. If the room thermostat is correctly set, call a qualified servicer

to determine if one of the compressor protection devices
has opened.

S

HORT

-C

YCLE

 P

ROTECTOR

A short-cycle protector is built into the ignition control.  Each time
the compressor is off for less than 3 minutes,  the short-cycle
protector will delay compressor startup for up to 3 minutes. This
protects the compressor from improper operation.

On Dual Fuel units (GPD/APD), the short-cycle protector will
delay the compressor 5 minutes.

NOTE: 

 These units are not designed to provide mechanical

cooling at outdoor temperatures below 50°F. If low ambient
cooling is needed, consult a qualified servicer.

I

GNITER

The unit has an electronic ignition device which lights the
burners automatically.  Never try to light the burners by hand.  It
also has an induced draft blower to exhaust combustion prod-
ucts.

I

NDOOR

 A

IR

 C

IRCULATOR

 B

LOWER

Keep the blower access door panel in place except for inspec-
tion and maintenance.

R

OUTINE

 M

AINTENANCE

If you perform maintenance on the unit yourself, remember that
certain mechanical and electrical knowledge, skills and tools
are required to perform unit maintenance. Personal injury or
death may result If you are not properly trained.  You should call
your installing dealer or place of purchase if you are uncertain
about your ability to perform maintenance.

A

NNUAL

 I

NSPECTION

Your package unit should be inspected by a qualified installer,
or service agency at least twice every year.  This check should be
performed before the heating and cooling seasons begin.  This
will ensure that adequate combustion air is being drawn and the
vent system is working properly.  Particular attention should be
paid to the following items.  Repair as necessary.

• Check physical support of the unit.  Ensure it is sound with-

out any sagging, cracks, or gaps, around the base.

• Check for obvious signs of deterioration of the unit.

• Flue Hood and Combustion Air Inlet.  Check for blockage

(wasp nest, etc.) and corrosion.

Flue Hood

Combustion

Air Inlet

Flue Hood

• Return Air Connection.  Check for physical soundness and

ensure that the connection is firmly sealed to the package
unit casing.

• Heat exchanger.  Check for corrosion and/or obstructions

within the heat exchanger passageways.

• Burners.  Check for proper ignition, burner flame, and flame

sense.

• Wiring.  Check electrical connections for tightness and/or

corrosion.  Check wires for damage.

• Filters.  Check that filters are clean and in the proper place-

ment in the unit or duct system.

• Louvers. Inspect air inlet louvers inside the heat exchanger

compartments. Ensure the area is clean and free of dirt and
debris.

Содержание GPG16

Страница 1: ...staller Affix this manual Installation Guide and Warranty adjacent to the appliance Owner Read and keep all product literature in a safe place for future reference WARNING SHOULD OVERHEATING OCCUR OR...

Страница 2: ...nces must be kept clear and free of combustible materials gaso line and other flammable vapors and liquids Also do not store or use flammable items such as paint varnish or lac quer in the area 3 The...

Страница 3: ...SSIVE HUMIDITY HEAVILY FROSTED WINDOWS OR A MOIST CLAMMY FEELING IN THE HOME 3 SMOKE FROM A FIREPLACE WILL NOT DRAW UP THE CHIMNEY 4 FLUE GASES THAT WILL NOT DRAW UP THE APPLIANCE VENT PIPE WARNING TO...

Страница 4: ...K TESTED BEFORE PLACING IN OPERATION HEATING START UP To put your unit into operation follow the steps listed below 1 Close the external manual gas shutoff valve 2 Turn off the electrical power to the...

Страница 5: ...sor This limit guards against overheating as a result of insufficient conditioned air passing over the heat exchanger It deenergizes the gas valve if the blower fails NOTE If the power to the unit is...

Страница 6: ...pt for inspec tion and maintenance ROUTINE MAINTENANCE If you perform maintenance on the unit yourself remember that certain mechanical and electrical knowledge skills and tools are required to perfor...

Страница 7: ...s on the filter point in the proper direction CLEAN OUTSIDE COIL QUALIFIED SERVICER ONLY WARNING TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DISCONNECT THE ELECTRICAL SWITCH BEFORE CLEAN...

Страница 8: ...rveau et meme la mort Cette ventilation est n cessaire pour viter le danger d intoxication au CO pouvant survenir si un appareil produisant du monoxyde de carbone continue de fonctionner au sein de la...

Страница 9: ...ther reproductive harm are known to the This product contains fiberglass insulation S tate of California to product could expose California to cause known by the S tate of contains a chemical Fibergla...

Страница 10: ...se cancer birth defects or other reproductive harm are known to the This product contains fiberglass insulation State of California to product could expose California to cause known by the State of co...

Страница 11: ...11 SAFETY LABELS because some gas is heavier than air and will...

Страница 12: ...12 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com...

Отзывы: