P
rodUct
S
PecificationS
P
rodUct
S
PecificationS
SS-GPC14H
www.goodmanmfg.com
3
S
PecificationS
Models
GPC14
24H41AC
GPC14
30H41AC
GPC14
36H41AC
GPC14
42H41AC
GPC14
48H41AC
GPC14
60H41A*
Cooling Capacity
Cooling Capacity (BTU/h)
24,000
28,400
35,600
40,000
46,000
57,500
Sensible BTU/h
18,200
21,600
27,100
30,400
35,300
40,800
SEER / EER
14.0 / 12.0
14.0 / 12.0
14.0 / 12.0
14.0 / 12.0
14.0 / 12.0
14.2 / 12.0
Decibels
76
76
78
78
80
80
AHRI Numbers
4635463
4635464
4635465
4635466
4635467
4385084
Evaporator Motor
Type
EEM
EEM
EEM
EEM
EEM
EEM
Wheel (D x W)
10 x 8
10 x 8
10 x 8
10 x 8
10 x 8
11 x 8
Cooling CFM
875
1,050
1,200
1,200
1,600
1,600
Fan-Only CFM
800
950
1,100
1,200
1,400
1,600
RLA
1.5
1.86
1.86
2.9
2.9
2.9
No. of Speeds
5
5
5
5
5
5
Horsepower - RPM
½ - 1050
½ - 1050
½ - 1050
½ - 1050
¾ - 1050
¾ - 1050
Evaporator Coil
Face Area (ft²)
5.25
5.25
5.2
6.2
6.2
7.0
Rows Deep/ Fins per Inch
3/ 16
3/ 16
3/ 14
4/ 14
4/ 14
4/ 14
Indoor Orifice Size
0.057
0.062
0.068
0.072
0.078
0.088
Filter Size (")
20 x 20 x 1
20 x 25 x 1
25 x 25 x 1
(2) 20 x 20 x 1 (2) 20 x 20 x 1 (2) 20 x 25 x 1
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
Refrigerant Charge (oz.)
59
53
65
94
90
190
Condenser Fan / Coil
Horsepower - RPM
1/6 - 815
1/6 - 815
¼ - 830
¼ - 1075
¼ - 1075
¼ - 1075
RLA/LRA
1.1 / 1.7
1.1 / 1.7
1.5 / 3.0
1.4 / 2.9
1.4 / 2.9
1.4 / 2.9
Fan Diameter/ # Fan Blades
22 / 2
22 / 2
22 / 3
22 / 4
22 / 4
22 / 4
Face Area (ft²)
12.3
12.3
12.3
16
19.5
19.1
Rows Deep/ Fins per Inch
1 / 26
1 / 26
1 / 26
1 / 28
1 / 28
2 / 16
Compressor
Quantity / Type
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
Stage
Single
Single
Single
Single
Single
Single
Compressor RLA/LRA
13.5 / 58.3
12.8 / 64
16.7 / 79
17.9 / 112
19.9 / 109
26.4 / 134
Electrical Data
Voltage-Phase
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
Indoor Blower FLA
1.5
1.86
1.86
2.9
2.9
2.9
Outdoor Fan RLA
1.1
1.5
1.5
1.4
1.4
1.4
Total Unit Amps
16.1
15.76
20.06
22.2
24.2
30.7
Min. Circuit Ampacity¹
19.5
19
24.2
26.6
29.1
37.3
Max. Overcurrent Protection (amps)²
30
30
40
40
45
60
Ship Weight (lbs)
290
290
370
370
400
400
Operating Weight (lbs)
280
280
360
360
390
390
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.