PRODUCT DESIGN
Dual $aver Configuration & Operation
Dual$aver
This furnace is capable of the following heating modes:
Single Stage (Factory Setting)
Modifi ed Two-Stage
Fixed 5-Min Low Stage
Auto Time (1-12 Min) Low Stage
To change from the factory single-stage operation, adjust the
dipswitches on the ignition control as follows:
Off On
Mode
5 Min Fixed
Auto
Mode Dipswitch
2
nd
Stage Delay Dipswitch
Note: This furnace is designed to be used with a single-stage room
thermostat.
Start
Start
Call for Heat
Call for Heat
Safety Circuit Check
Safety Circuit Check
Start Furnace
in Low Stage
Start Furnace
in Low Stage
Low-Heat Blower
Low-Heat Blower
Delay Time (5 Min)
Delay Time (1-12 Min)
Gas Valve Switch
Gas Valve Switch
to 2nd Stage
to 2nd Stage
Blower Switch to
Blower Switch to
Hi Heat Operation
Hi Heat Operation
T-Stat Satisfi ed
T-Stat Satisfi ed
•
•
»
»