BLOWER PERFORMANCE SPECIFICATIONS

19

1. Units are shipped without filter(s). CFM in chart is without filter(s).

2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed

as needed. The first task is to determine the proper aiflow for the cooling system.

3. For most cooling applications, about 400 CFM per ton is desirable.

4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on

rating plate.

5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling

purposes only.

6. * Motor CFM minimum.

GMVC95/AMVC95 Low Stage Cooling Speed Charts

GMVC95/AMVC95

 

High (Single) Stage Cooling Speed Charts

Cooling

Speed

Tap

Adjus t

Tap

CFM at
.1" - .8"

w.c. ESP

Cooling

Speed

Tap

Adjus t

Tap

CFM at
.1" - .8"

w.c. ESP

Cooling

Speed

Tap

Adjus t

Tap

CFM at
.1" - .8"

w.c. ESP

Cooling

Speed

Tap

Adjus t

Tap

CFM at
.1" - .8"

w.c. ESP

Minus (-)

540

Minus (-)

540

Minus (-)

720

Minus (-)

720

Norm al  

600

Norm al  

600

Norm al  

800

Norm al  

800

Plus  (+)

660

Plus  (+)

660

Plus  (+)

880

Plus  (+)

880

Minus (-)

720

Minus (-)

720

Minus (-)

990

Minus (-)

990

Norm al  

800

Norm al  

800

Norm al  

1100

Norm al  

1100

Plus  (+)

880

Plus  (+)

880

Plus  (+)

1210

Plus  (+)

1210

Minus (-)

900

Minus (-)

990

Minus (-)

1260

Minus (-)

1260

Norm al 

 1000

Norm al 

 1100

Norm al 

 1400

Norm al 

 1400

Plus  (+)

1100

Plus  (+)

1210

Plus  (+)

1540

Plus  (+)

1540

Minus (-)

1080

Minus (-)

1286

Minus (-)

1620

Minus (-)

1620

Norm al 

 1200

Norm al 

 1429

Norm al 

 1800

Norm al 

 1800

Plus  (+)

1320

Plus  (+)

1572

Plus  (+)

1980

Plus  (+)

1980

D

GMVC950704CX*

AMVC950704CX*

A

B

C

C

D

GMVC950453BX*

AMVC950453BX*

A

B

D

D

C

C

GMVC951155DX*

AMVC951155DX*

GMVC950905DX*

AMVC950905DX*

B

B

A

A

C ooling

Speed

Tap

Adjus t

Tap

C FM  at
.1" - .8"

w .c.  ESP

Cooling

Speed

Tap

Adjus t

Tap

CFM at
.1" - .8"

w .c. ESP

C ooling

Speed

Tap

Adjus t

Tap

C FM  at
.1" - .8"

w .c.  ESP

C ooling

Speed

Tap

Adjus t

Tap

C FM  at
.1" - .8"

w.c. ESP

Minus (-)

351

Minus (-)

351

Minus (-)

468

Minus (-)

468

Norm al  

390

N orm al  

390

N orm al  

520

Norm al  

520

Plus  (+)

429

Plus  (+)

429

Plus  (+)

572

Plus  (+)

572

Minus (-)

468

Minus (-)

468

Minus (-)

644

Minus (-)

644

Norm al  

520

N orm al  

520

N orm al  

715

Norm al  

715

Plus  (+)

572

Plus  (+)

572

Plus  (+)

787

Plus  (+)

787

Minus (-)

585

Minus (-)

644

Minus (-)

819

Minus (-)

819

Norm al  

650

N orm al  

715

N orm al  

910

Norm al  

910

Plus  (+)

715

Plus  (+)

787

Plus  (+)

1001

Plus  (+)

1001

Minus (-)

702

Minus (-)

836

Minus (-)

1053

Minus (-)

1053

Norm al  

780

N orm al  

929

N orm al  

1170

Norm al  

1170

Plus  (+)

858

Plus  (+)

1022

Plus  (+)

1287

Plus  (+)

1287

D

GMVC 950704C X*

AMVC 950704C X*

A

B

C

C

D

GMVC 950453BX*

AMVC950453BX*

A

B

D

D

C

C

GMVC 951155D X*

AMVC 951155D X*

GMVC 950905DX*

AMVC 950905D X*

B

B

A

A

Содержание ComfortNet ACVC90704CXAA

Страница 1: ...r service procedures performed by an unqualified person ACVC9 AMVC95 GCVC9 GMVC95 90 95 Gas Furnace Units Refer to Service Manual RS6200004 for installation operation and troubleshooting information A...

Страница 2: ...ge personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you ass...

Страница 3: ...and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local EPA office WARNING WARNING Do not connect or use any device tha...

Страница 4: ...these models can support 4 wire communication pro tocol and provide more troubleshooting information These models are also backward compatible with the legacy ther mostat wiring The GCVC9 GMVC95 AMVC...

Страница 5: ...fice HAPS28 HANG14 45 Orifice HALP11 56 Orifice HAPS28 GMVC950905DX GMVC951155DX AMVC950905DX AMVC951155DX No Change LPM 05 55 Orifice No Change HANG13 44 Orifice HALP11 56 Orifice HAPS29 HANG14 45 Or...

Страница 6: ...r Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations 21 Drain Trap 22 Blower Door Interlock Switch 23 Inductor Not All Models 24 Two Stage Integrated Control Module with fuse and d...

Страница 7: ...L HOLE RIGHT SIDE DRAIN LINE HOLES STANDARD GAS SUPPLY HOLE DRAIN TRAP 20 3 16 AIR INTAKE PIPE 2 PVC LEFT SIDE DRAIN LINE HOLES 1 3 4 DRAIN TRAP 1 1 2 1 5 8 30 1 4 11 3 4 19 3 16 BOTTOM KNOCK OUT 23 9...

Страница 8: ...CTRICAL HOLE 20 5 32 2 UNFOLDED FLANGES DISCHARGE AIR E CONDENSATE DRAIN TRAP w 3 4 PVC DISCHARGE RIGHT OR LEFT SIDE FOLDED FLANGES RETURN AIR A HIGH VOLTAGE ELECTRICAL HOLE LOW VOLTAGE ELECTRICAL HOL...

Страница 9: ...2 MODEL 1 Data given is least negative pressure required for pressure sw itch to close LOW FIRE HIGH FIRE LOW FIRE HIGH FIRE LOW FIRE HIGH FIRE LOW FIRE HIGH FIRE GMVC950453BX GMVC950704CX AMVC950453B...

Страница 10: ...1 0 1 2 3 5 1 7 1 0 1 2 3 5 1 8 1 0 1 2 3 5 3 3 1 0 1 2 3 5 3 4 1 0 1 2 3 5 3 7 O pe n S e tting F 3 2 5 2 1 0 1 7 0 2 0 0 2 2 0 1 9 0 GM V C9 5 0 4 5 3 BX AM V C9 5 0 4 5 3 BX 1 GM V C9 5 0 7 0 4 CX...

Страница 11: ...naces All CAPF coils have a CAUF equivalent All CHPF coils in B C D heights have an insulated Z bracket for use with one size smaller furnace All proper coil combinations are subject to being ARI rate...

Страница 12: ...be installed elsewhere in the duct system such as a central return Disposable Minimum Filter Area in2 Based on a 300 ft min filter face velocity Minimum filter area dictated by heating airflow require...

Страница 13: ...ngcounterflowtopreturnfiltersizes depending on cabinet size Refer to Minimum Filter Area tables to determine filter area requirement NOTE Filters can also be installed elsewhere in the duct system suc...

Страница 14: ...gh Stage Pressure Switch Trip Point w c 0 75 0 75 1 10 1 10 Low Stage Pressure Switch Trip Point w c 0 30 0 30 0 50 0 50 Front Cover Pressure Switch Trip Point w c 0 10 0 10 0 10 0 10 Blower W heel D...

Страница 15: ...gh Stage Pressure Switch Trip Point w c 0 75 0 75 1 10 1 10 Low Stage Pressure Switch Trip Point w c 0 30 0 30 0 50 0 50 Front Cover Pressure Switch Trip Point w c 0 10 0 10 0 10 0 10 Blower W heel D...

Страница 16: ...Temperature Rise F 30 60 30 60 40 70 High Stage Pressure Switch Trip Point w c 0 55 0 55 0 55 Low Stage Pressure Switch Trip Point w c 0 20 0 20 0 20 Front Cover Pressure Switch Trip Point w c 0 37 0...

Страница 17: ...gh S tage P res s ure S witc h Trip P oint w c 0 55 0 55 Low S tage P res s ure S witc h Trip P oint w c 0 20 0 20 F ront Cover P res s ure S witc h Trip P oint w c 0 37 0 37 B lower W heel D x W 10 x...

Страница 18: ...51 Normal 600 864 47 Normal 920 1 325 46 Plus 660 950 43 Plus 1 012 1 457 42 Minus 585 842 48 Minus 900 1 296 47 Normal 650 936 43 Normal 1 000 1 440 42 Plus 715 1 030 39 Plus 1 100 1 584 38 Minus 63...

Страница 19: ...Norm al 800 Norm al 1100 Norm al 1100 Plus 880 Plus 880 Plus 1210 Plus 1210 Minus 900 Minus 990 Minus 1260 Minus 1260 Norm al 1000 Norm al 1100 Norm al 1400 Norm al 1400 Plus 1100 Plus 1210 Plus 1540...

Страница 20: ...d 0 8 w c is tabulated for cooling purposes only 6 Motor CFM minimum GMVC95 AMVC95 Continuous Fan Speed Chart Model Furnace Maximum CFM Continuous Fan Speed1 2 GMVC950453BX AMVC950453BX 1400 420 GMVC9...

Страница 21: ...5 w c ESP High Stage CFM at 1 5 w c ESP Rise F Minus 747 1 076 56 Minus 999 1 439 56 Normal 830 1 195 50 Normal 1 110 1 598 50 Plus 913 1 315 46 Plus 1 221 1 758 46 Minus 824 1 186 51 Minus 1 067 1 5...

Страница 22: ...ximum CFM capaibility is 1760 CFM the continuous fan speed will be 0 30 X 1760 CFM 530 CFM Example If the furnace maximum CFM capaibility is 1760 CFM the continuous fan speed will be 0 30 X 1760 CFM 5...

Страница 23: ...esponding taps Refer to the bullet points below for a description of each ramping profile Verify CFM by noting the number displayed on the dual 7 segment LED display 5 6 A OFF OFF B ON OFF C OFF ON D...

Страница 24: ...al 800 Plus 660 Plus 880 Minus 720 Minus 990 Normal 800 Normal 1100 Plus 880 Plus 1210 Minus 990 Minus 1260 Normal 1100 Normal 1400 Plus 1210 Plus 1540 Minus 1286 Minus 1620 Normal 1429 Normal 1800 Pl...

Страница 25: ...30 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPU...

Страница 26: ...WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATER IAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C USE COPPER CONDUCTORS ONLY PU DISCONNECT EAC PLUG CONNECTION...

Страница 27: ...r to the appropriate wiring diagram for the unit being serviced BK WH BK BK INTEGRATED CONTROL MODULE GROUND TO SCROLL HOUSING BK BK ECM BLOWER MOTOR INDUCTOR COIL PI N 4 WH WH TO ECM TRANSFORMER BLWR...

Страница 28: ...reference only Not all wiring is as shown above Refer to the appropriate wiring diagram for the unit being serviced Wiring is subject to change Always refer to the wiring diagram on the unit for the...

Отзывы: