2 www.goodmanmfg.com
SS-CKF50
P
RODUCT
S
PECIFICATIONS
D
IMENSIONS
P
ERFORMANCE
R
ATINGS
Outdoor Unit
Indoor Unit
Cooling Capacity (BTU/h)
dBs
Total
Sensible
EER¹
kWI²
CKF24-2*
A24-00-2RA
24,000
16,800
9.0
2.66
76
CA*F1824*6*
24,600
17,400
9.0
2.73
76
CKF36-2*
A36-00-2RA
33,000
23,400
9.0
3.67
76
CA*F3030*6*
34,000
24,200
9.0
3.78
76
CKF36-5*
A36-00-2RA
33,000
23,400
9.0
3.67
76
CA*F3030*6*
34,000
24,200
9.0
3.78
76
CKF48-5*
A48-00-2A
44,000
32,400
9.0
4.89
78
CA*F3636*6*
44,000
32,400
9.0
4.89
78
CKF60-5*
A60-00-2R
55,000
37,800
9.0
6.11
78
CA*F3642*6*
55,000
37,800
9.0
6.11
78
CKF70-5*
A60-00-2R
61,000
41,500
9.0
6.78
80
CA*F4860*6*
62,000
42,000
9.0
6.89
80
A90-00-2R
64,000
43,500
9.0
7.11
80
¹ Energy
Ef
fi
ciency Ratio @ 80°F / 67°F / 95°F
² kWI = Comp Indoor Outdoor Fan Watts
Note:
When mix-matching outdoor and indoor units, the indoor unit check-
fl
owrator must match the out-
door unit size.
•
Model
Width
Depth
Height
CKF24-2*
26
26
29¾
CKF36-2*
26
26
29¾
CKF36-5*
26
26
29¾
CKF48-5*
29
29
29¾
CKF60-5*
29
29
32¼
CKF70-5*
29
29
38¼