8
PACKAGE GAS SPECIFICATIONS
(1)
Units installed in Canada are certifed only to 4500 feet.
(2)
Calculated external filter size based on air velocity of 300 ft/min. and applies to disposable filters
only.
(3)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit
breakers in accordance with the National Electrical Code and/or all local codes.
*PG15[24-37]***41AA
*PG152407041AA
*PG153009041AA
*PG153609041AA
*PG153709041AA
COOLING
COOLING CAPACITY, BTUH
CAPACITY
HIGH STAGE
23,200
29,000
35,400
35,000
LOW STAGE
N/A
N/A
24,400
N/A
SEER / EER
15.0 / 12.0
14.5 / 12.0
15.0 / 11.0
14.5 / 12.0
HEATING
BTUH INPUT (US) HIGH FIRE
69,000
92,000
92,000
92,000
CAPACITY
OUTPUT (US) HIGH FIRE (Natural Gas)
55,000
73,500
73,500
73,500
OUTPUT (US) HIGH FIRE (LP)
50,000
69,000
69,000
69,000
BTUH INPUT (US) LOW FIRE
52,000
69,000
69,000
69,000
OUPUT (US) LOW FIRE (Natural)
41,500
55,000
55,000
55,000
OUTPUT (US) LOW FIRE (LP)
37,000
50,000
50,000
50,000
A.F.U.E.
80
80
80
80
RATED EXTERNAL STATIC (" w.c.)
0.50
0.50
0.50
0.50
TEMPERATURE RISE (°F)
35-65
45-75
45-75
45-75
PRESSURE SWITCH TRIP POINT (" w.c.)
-.33"
-.33"
-.33"
-.33"
UNIT
VOLTAGE (NAMEPLATE)
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
ELECTRICAL
UNIT AMPS (TOTAL)
18.7
17.5
22.2
20.1
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
22.1
21
26.5
24.2
MAXIMUM OVERCURRENT PROTECTION
(3)
30
35
40
40
HEATING
NUMBER OF BURNERS
3
4
4
4
SECTION
ORIFICE SIZE NATURAL
43
43
43
43
ORIFICE SIZE LP
55
55
55
55
COMPRESSOR
TYPE
Scroll
Scroll
Scroll
Scroll
RATED LOAD AMPS
13.5
14.1
16.7
16.7
LOCKED ROTOR AMPS
58.3
73
82
79
CONDENSER
HORSEPOWER
1/6
1/4
1/4
1/4
FAN MOTOR
RPM
815
830
1075
830
FULL LOAD AMPS
1.10
1.5
1.4
1.5
LOCKED ROTOR AMPS
1.7
3.0
2.9
3.0
CONDENSER
BLADE DIAMETER (INCHES)
22
22
22
22
FAN
NUMBER OF BLADES
3
3
3
3
CFM
2400
2700
2700
2700
CONDENSER
FACE AREA - SQ. FT.
12.3
12.3
12.3
12.3
COIL
NUMBER OF ROWS
1
2
1
2
FINS PER INCH
22
16
22
16
EVAPORATOR
HORSEPOWER - NO. OF SPEEDS
1/2 - X-13
1/2 - X-13
1/2 - X-13
1/2 - X-13
BLOWER
FULL LOAD AMPS
4.1
1.86
4.1
1.86
MOTOR
LOCKED ROTOR AMPS
N/A
N/A
N/A
N/A
MOTOR SPEED TAP - COOLING
T4
T3, T4
T3, T4
T3, T4
RPM / AMPS
724 / 1.21
960 / 3.06
640 / 0.98
960 / 3.06
960 / 3.06
EVAPORATOR
DIAMETER X WIDTH (INCHES)
10 x 8
10 x 9
10 x 9
10 x 9
BLOWER
RATED SCFM COOLING
845
1050
800 / 1225
1050
MAX EXTERNAL STATIC PRESS ("w.c.)
0.5
0.5
0.5
0.5
EVAPORATOR
FACE AREA - SQ. FT.
4.33
4.33
4.33
4.33
COIL
NUMBER OF ROWS
2
3
4
4
FINS PER INCH
14
14
14
14
FILTER SIZE - SQ. FT.
(2)
2.7
4.2
4.2
4.2
DRAIN SIZE (INCHES)
3/4
3/4
3/4
3/4
HEATING
PRIMARY LIMIT SETTING (°F)
160
160
160
160
LIMITS
AUXILIARY LIMIT SETTING (°F)
150
150
150
150
ROLLOUT LIMIT SETTING (°F)
300
300
300
300
GENERAL
EXPANSION DEVICE
TXV
0.065
TXV
TXV
INFORMATION
REFRIGERANT CHARGE R-410A (Oz.)
81
102
99
112
POWER SUPPLY ENTRANCE SIZE (INCHES)
1 1/8
1 1/8
1 1/8
1 1/8
LOW VOLTAGE ENTRANCE SIZE (INCHES)
7/8
7/8
7/8
7/8
SHIPPING WEIGHT LBS.
439
475
480
480
OPERATING WEIGHT LBS.
417
453
458
458