background image

SYSTEM OPERATION

11

For furnaces being converted to LP gas, it is strongly 

recommended that a LPLP03 kit also be installed.  The use 

of this kit will prevent the furnace from firing when the LP gas 

supply pressure is too low to support proper combustion.  
High altitude installations may require both a pressure switch 

and an orifice/spring change.  These changes are necessary 

to compensate for the natural reduction in the density of both 

the gas fuel and the combustion air at higher altitude.
For installations above 7000 feet, please refer to the furnace 

Specification Sheets for required kit(s).

Contact the distributor for a tabular listing of appropriate 

manufacturer’s kits for propane gas and/or high altitude 

installations.  The indicated kits must be used to insure 

safe and proper furnace operation.  All conversions must be 

performed by a qualified installer, or service agency.

Vent/Flue Pipe & Combustion Air Pipe

This manual will refer to the pipe that discharges products of 

combustion to the outdoors as the “vent” pipe or “flue” pipe. 

The pipe that supplies air for combustion to the furnace will 

be referred to as the “intake” pipe  or “combustion air” pipe. 

A condensing gas furnace achieves its high level of efficiency by 

extracting almost all of the heat from the products of combustion 

and cooling them to the point where condensation takes place. 

Because of the relatively low flue gas temperature and water 

condensation requirements, PVC or ABS are typically used 

venting and intake pipe materials. In Canada ABS is not an 

approved vent pipe material but it is permissible to use as 

combustion air pipe material. 

In addition to PVC and ABS pipe and fittings, Innoflue

®

 by 

Centrotherm Eco Systems and PolyPro

®

 by M&G Duravent 

are also approved vent and combustion air materials for 

installations in the U.S.A. and Canada. Manufacturers 

Installation instructions for these products must be followed. 

These products have specific instructions for installing, joining 

and terminating. Do not mix materials or components of 

one manufacturer with materials or components of another 

manufacturer.
All furnaces are manufactured with 2” vent / intake pipe and 

connectors. For furnaces requiring installation of 3” pipe, the 

transition from 2” to 3” should be done as close to the furnace 

as practically possible.
This furnace must not be connected to Type B, BW, or L vent 

or vent connector, and must not be vented into any portion 

of a factory built or masonry chimney except when used as 

a pathway for PVC as described later in this section.  Never 

common vent this appliance with another appliance or use 

a vent which is used by a solid fuel appliance.  Do not use 

commercially available “no hub connectors” other than those 

shipped with this product.

It is the responsibility of the installer to follow the manufacturers’ 

recommendations and to verify that all vent/flue piping and 

connectors are compatible with furnace flue products.  

Additionally, it is the responsibility of the installer to ensure 

that all piping and connections possess adequate structural 

integrity and support to prevent flue pipe separation, shifting, 

or sagging during furnace operation.

U

PON

 

COMPLETION

 

OF

 

THE

 

FURNACE

 

INSTALLATION

CAREFULLY

 

INSPECT

 

THE

 

ENTIRE

 

FLUE

 

SYSTEM

 

BOTH

 

INSIDE

 

AND

 

OUTSIDE

 

OF

 

THE

 

FURNACE

 

TO

 

ASSURE

 

IT

 

IS

 

PROPERLY

 

SEALED

. L

EAKS

 

IN

 

THE

 

FLUE

 

SYSTEM

 

CAN

 

RESULT

 

IN

 

SERIOUS

 

PERSONAL

 

INJURY

 

OR

 

DEATH

 

DUE

 

TO

 

EXPOSURE

 

TO

 

FLUE

 

PRODUCTS

INCLUDING

 

CARBON

 

MONOXIDE

.

WARNING

F

AILURE

 

TO

 

FOLLOW

 

THESE

 

INSTRUCTIONS

 

CAN

 

RESULT

 

IN

 

BODILY

 

INJURY

 

OR

 

DEATH

. C

AREFULLY

 

READ

 

AND

 

FOLLOW

 

ALL

 

INSTRUCTIONS

 

GIVEN

 

IN

 

THIS

 

SECTION

.

WARNING

Dual Certification: Non-Direct/Direct Vent

This furnace is dual certified and may be installed as a non-direct 

vent (single pipe) or direct vent (dual pipe) appliance.  A 

non-

direct vent

 installation requires only a vent/flue pipe, while a 

direct vent

 installation requires both a vent/flue pipe and a 

combustion air intake pipe.  Refer to the appropriate section 

for details concerning piping size, length, number of elbows, 

furnace connections, and terminations.

Materials and Joining Methods

Two-three-inch nominal diameter PVC Schedule 40 pipe 

meeting ASTM D1785, PVC primer meeting ASTM F656, and 

PVC  solvent  cement  meeting ASTM  D2564  specifications 

must be used.  Fittings must be DWV type fittings meeting 

ASTM D2665 and ASTM D3311.  Carefully follow the 

manufacturer’s instructions for cutting, cleaning, and solvent 

cementing of PVC.
The use of Schedule 40 PVC cellular core DWV meeting 

ASTM F891-1 or ABS cellular core (Foam Core) plastic pipe 

is also acceptable as a flue/vent and intake pipe material. 

PVC primer meeting ASTM F656 and PVC solvent cement 

meeting ASTM D2564 specifications must be used. Fittings 

must be DWV type fittings meeting ASTM D2665 and ASTM 

D3311. Carefully follow the manufactures instructions for 

cutting, cleaning and solvent cementing of PVC.
For Canadian installations; field supplied PVC venting 

materials must be UL S636 listed.
NOTE: Requirement does not apply to the combustion air 

pipe.

Содержание ACVC96 BA Series

Страница 1: ...its lifetime a product may require service Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped wit...

Страница 2: ...arts testing in struments and the appropriate service manual REVIEWALL SERVICEINFORMATIONINTHEAPPROPRIATESERVICE MANUAL BEFORE BEGINNING REPAIRS OUTSIDE THE U S call 1 713 861 2500 Not a technical ass...

Страница 3: ...El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cualquier mo...

Страница 4: ...tion M Upflow Horizontal MajorRevision C Downflow Horizontal A Initial Release K Dedicated Upflow B Comfortbridge Technology D Dedicated Downflow Nox Motor N Natural Gas V Variable Speed X Low NOx E H...

Страница 5: ...ol from its container Follow steps 1 through 3 if installing the control on a furnace Return any old or new controls to their containers before touching any ungrounded object TO PREVENT PROPERTY DAMAG...

Страница 6: ...requires that the following additional requirements must also be met Gas furnaces must be installed by a licensed plumber or gas fitter A T handle gas cock must be used If the unit is to be installed...

Страница 7: ...m outdoors Refer to the Combustion and Ventilation Air Requirements for details If the furnace is used in connection with a cooling coil unit install the furnace upstream or in parallel with the cooli...

Страница 8: ...openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223 1 or the Natural Gas and Propane Installation Code...

Страница 9: ...never be attached to the back of the furnace Contact your distributor for proper airflow requirements and number of required ductwork connections Refer to Recommended Installation Positions figure fo...

Страница 10: ...ocation Figure 3A AIR DISCHARGE Bottom Return Duct Connection UPFLOW HORIZONTAL LEFT AIR DISCHARGE Figure 3B AIR DISCHARGE Bottom Return Duct Connection UPFLOW HORIZONTAL RIGHT AIR DISCHARGE Figure 3C...

Страница 11: ...into any portion of a factory built or masonry chimney except when used as a pathway for PVC as described later in this section Never common vent this appliance with another appliance or use a vent w...

Страница 12: ...sures 3 1 16 minimum from the plane of one opening to the center line of the other opening for 2 diameter pipe and 4 9 16 minimum for 3 pipe Proper Vent Flue and Combustion Air Piping Practices Adhere...

Страница 13: ...ot above any door window or gravity air inlet into any building The vent termination of a direct vent application must terminate at least 12 inches from any opening through which flue gases may enter...

Страница 14: ...quivalent of one 90 deg elbow when considering elbow count See Figure 7 45 DEGREE LONG SWEEP ELBOWS V E N T Increased Clearance Configuration Figure 8 VENT DRAIN CAP TO BE INSTALLED ON UN USED DRAIN P...

Страница 15: ...either in a horizontal left side down installation or a vertical installation using down venting an alternate com bustion air opening can be used A locating dimple is located on the right side of the...

Страница 16: ...nd Combustion Air Pipe Termination Locations for details concerning location restrictions The penetration of the vent through the roof must be sealed tight with proper flashing such as is used with a...

Страница 17: ...Vent Termination Above Anticipated Snow Level Dual Pipe 12 MIN BETWEEN INTAKE AND VENT VENT 90 ELBOWS 12 MIN ABOVE HIGHEST ANTICIPATED SNOW LEVEL 3 24 BETWEEN PIPES Figure 15 If the combustion air in...

Страница 18: ...x Floor Basement Crawlspace DOWN VENTING UPFLOW MODEL FURNACES ONLY All piping and fittings must be joined per material manufacturers specifications to prevent separation and flue gas leaks Figure 12...

Страница 19: ...t the same elevation Concentric Vent Termination Refer to the directions provided with the Concentric Vent Kit DCVK for installation specifications Side Wall Vent Kit This kit is to be used with 2 or...

Страница 20: ...a cabinet seal when installed See instructions below for your model and installation position NOTE Both sides of the drain trap must be primed prior to initial furnace start up Field Supplied Drain D...

Страница 21: ...lding the drain trap to the blower deck 3 Remove the trap and two hoses from the blower deck 4 Remove the two plugs from the right side of the cabinet and install them in the blower deck 5 Draining th...

Страница 22: ...faces the front of the furnace Secure the trap to the cabinet using two screws removed in step 2 by inserting the two screws through the large set of holes in the top mounting tabs of the trap into th...

Страница 23: ...ith a silver clamp 5 Mate the drain trap inlets to the hoses and secure with silver clamps 6 Line up the trap mounting holes with the pre drilled holes in the furnace and secure with 2 screws removed...

Страница 24: ...alled into hose 4 and secure with a gold clamp 11 Insert the non grommet end of hose 5 factory installed from outside the cabinet in the back drain hole 12 Insert 100 elbow in hose 5 and secure with a...

Страница 25: ...oundscrewlocatedinsidethefurnacejunction box all the way back to the electrical panel NOTE Do not use gas piping as an electrical ground To confirm proper unit grounding turn off the electrical power...

Страница 26: ...emporary heat pump lockout and run the heat pump again There are four adjustable items associated with Dual Fuel control In the same way as the System Target Time each of these items have defaulted va...

Страница 27: ...Down Percent SdP 0 100 20 Over Target Threshold Ott 1 strike 254 strikes 20 strikes Under Target Threshold Utt 1 strike 254 strikes 20 strikes Circulator Blower Speed TheAirflow quantity is displayed...

Страница 28: ...0 4 7 1880 6 2400 2 2 880 3 5 1400 4 8 1920 Cooling Airflow Ramping Profiles The multi circulator blower also offers several custom ON OFF ramping profiles These profiles may be used to enhance coolin...

Страница 29: ...For gas heat only operations no outdoor unit installed the thermostat must be setup to provide a single stage W call when heating is required See Gas Heat Only wiring diagram for wiring instructions...

Страница 30: ...ehum 24 VAC Thermostat 1 2 R C Heat Pump Optional R C W Y This is the only case where setting the thermostat to heat pump mode is acceptable Figure 39 Non Communicating Single Stage Heat Pump R C G W...

Страница 31: ...ket Use Y W G signals Thermostat has a Dehum or Configurable terminal with Dehum option Yes No Does your thermostat have a whole house Dehumidifier setting Install Dehumidistat in living space or retu...

Страница 32: ...RING WARNING The accessory load specifications are as follows EAC 1 0 Amp maximum at 120 VAC The furnace integrated control module is equipped with a line voltage accessory terminal for controlling po...

Страница 33: ...y attempts will result in a new code being dis played on the control If all 3 digits are not visible from the sight glass the user has two options to connect Option 1 Perform thermostat task as instru...

Страница 34: ...meout occurs the displayed option will not be stored in control memory as a selected option The Status Menu includes the following items The operation mode Blower CFM if blower is running Humidificati...

Страница 35: ...display the firmware release revision numbers for each micro controller Constant Fan Speed Menu This menu allows for adjustment of the multiplier for con stant fan operation in 10 increments Each fur...

Страница 36: ...l algorithm Furnace runs integrated control module monitors safety circuits continuously If the internal algorithm changes the call from low heat to high heat the integrated control module will immedi...

Страница 37: ...ame electrostatic potential these steps will help avoid exposing the integrated control module to electrostatic discharge This pro cedure is applicable to both installed and uninstalled ungrounded fur...

Страница 38: ...er furnace operation Remember that dirty filters are the most common cause of inadequate heating or cooling performance Maintenance Improper filter maintenance is the most common cause of inadequate h...

Страница 39: ...a visual check of the burner flames Turn the furnace on at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be stable quiet soft and blu...

Страница 40: ...2 164 327 655 1636 37 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 176 439 16 56 113...

Страница 41: ...e gas valve turn downward clockwise to increase pressure and input and upward counterclockwise to decrease pressure and input A properly operating unit must have the BTU per hour input and CFM of air...

Страница 42: ...RKED TRANSFORMERS TRANSFORMER SECONDARY PRIMARY GND C R LINE VOLTAGE L1 HOT LINE VOLTAGE NEUTRAL METER READS 24 VOLTS METER READS 120 VOLTS GND C R N L1 GND C R N L1 READS 96 VOLTS IN PHASE READS 144...

Страница 43: ...t door to gain access to the thermostat low voltage wires located at the furnace integrated control module terminals 2 Remove the thermostat low voltage wires at the furnace control panel terminal boa...

Страница 44: ...ads the current AC waveform In other words the inductor reduces line current which extends the life of the 3 4 and 1 horsepower motors IMPORTANT If the inductor fails there will be no motor operation...

Страница 45: ...ating Confirm 24VAC to UltraCheck EZTM tool If 24VAC is confirmed diagnostic tool is inoperable ON Blinking Rotating Motor and control end bell are functioning properly ON OFF Rotating Replace motor c...

Страница 46: ...d bell Using an ohmmeter check the resistance between each terminal in the connector If the resistance is 100k or greater the control end bell is functioning properly Replace the control end bell if t...

Страница 47: ...n or overheating of the heat exchanger An airflow and temperature rise table is provided in the blower performance specification section Determine and adjust temperature rise as follows 1 Operate furn...

Страница 48: ...IFYING TAB Testing Primary Limit Control 90 Furnaces 4 After completing check and or replacement of primary limit control reinstall burner compartment door 5 Turn on electrical power and verify proper...

Страница 49: ...may also cause the control to open If the rollout control opens the air circulation blower will run continuously LINE VOLTAGE NOW PRESENT WARNING 1 Remove the burner compartment door to gain access to...

Страница 50: ...Valve WARNING DISCONNECT ALL POWER BEFORE SERVICING CHECKING MAIN BURNERS The main burners are used to provide complete combustion of various fuels in a limited space and transfer this heat of the bu...

Страница 51: ...ing figures NOTE At either location a hose fitting must be installed prior to making the hose connection NOTE Use adapter kit 0151K00000S to measure gas pressure on White Rodgers 36J54 gas valves Meas...

Страница 52: ...to control a non communicating heat pump disconnect the RJ12 jack from the furnace 3 Provide power to the furnace 4 Provide a thermostat W call The system will continuously run at 100 firing rate 5 Wh...

Страница 53: ...switches A GMVC96 and A GCVC model furnaces have a front cover pressure switch wired in series with the gas valve This pressure switch keeps the gas valve from opening in the event of condensate backi...

Страница 54: ...hin a given time frame due to the operation of the ignition control The trial for ignition period is 4 seconds The ignition control is capable of diagnosing many furnace failures to help in troublesho...

Страница 55: ...BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Disconnect the flame sensor wire from the sensor 2...

Страница 56: ...or Auxiliary Limit Switch Open Condensate Switch Open Grounding Fault Rollout Switch Open Redundant Relay Open Redundant Relay Stuck Closed E Module Network Communication Alarm Bluetooth Module Networ...

Страница 57: ...rost High Stage Gas Heat Name 7 Segment Display Cloud Phone App Idle Idle Constant Fan Constant Fan Compressor Cooling Low Stage Compressor Cooling Low Stage Compressor Cooling High Stage Compressor C...

Страница 58: ...15 Provides the 16 humidifier enabling options in different operation modes Ventilation On Time Adjustable between 0 60 minutes The default is 0 minute Off Adjusts the ventilation on time and turn it...

Страница 59: ...e 15 12 9 6 3 0 3 6 9 12 15 Trims the cooling airflow by the selected amount Cool Trim Factor Low 15 12 9 6 3 0 3 6 9 12 15 Trims the cooling airflow by the selected amount Cool Airflow Profile A B C...

Страница 60: ...cted w iring in high limit circuit Symptoms of Abnormal Operation Diagnostic Status LED Codes Possible Causes Corrective Actions Notes Cautions Manual disconnect sw itch turned OFF door sw itch open o...

Страница 61: ...ils to operate Integrated control module LED display provides error code Gas valve is not energized w hen it should be External Gas Valve Error Misw ired gas valve circuit Open gas valve circuit Gas v...

Страница 62: ...er data is loaded and pow er is turned off Error code w ill be cleared once data is turned off Operation different than expected or no operation Integrated control module LED display provides error co...

Страница 63: ...oms of Abnormal Operation Diagnostic Status LED Codes Fault Description Possible Causes Corrective Actions Notes Cautions Tighten or correct w iring connection Check circulator blow er motor Replace i...

Страница 64: ...SENSOR FLAME GN GREEN GR PRESSURE SWITCH FRONT COVER C VAC TO UNIT MUST BE 1 BL RD AND GROUNDED 1 115 WH SWITCH PRESS FIELD SPLICE FIELD GND LOW VOLTAGE FIELD GN BL BR WH NO LIMIT CONTROL AUTO RESET P...

Страница 65: ...ntact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAN...

Отзывы: