THERMOSTAT

BLUE

YELLOW

TO CONDENSING UNIT

24 V CONNECTIONS

W

R Y G

Figure 6

2

4

5

6

1

3

C.R.I.

* W

R B

I

W Br G

R

W

2

O

Y
C

CEILING MOUNT UNIT

* W

* Y

* B

I

R

O

Y

E G W

2

C

THERMOSTAT

HEAT PUMP

*WIRES SUPPLIES WITH HPSK KIT

Note: in case of heat pump failure, switch to “E” on Thermostat for 

emergency heat.  See note under Low Voltage Wiring

Figure 7

Connect low voltage wires from the thermostat to the corresponding 

wires in the Ceiling Mount unit and outdoor unit  using No. 18 AWG 

wires as follows:

LEAD

THERMOSTAT

NOTES

RED

R (24V)

-

GREEN

G (FAN)

-

-

Y

TO CONDENSING UNIT 

24V CONNECTIONS

WHITE

W

-

BLUE

-

TO CONDENSING UNIT 

24V CONNECTIONS

BROWN

E

TO BE USED FOR 

EMERGENCY HEAT ONLY

Table 5

CONSTANT TORQUE (EEM) MOTORS

ACNF25 and ACNF31 models utilize constant torque (EEM) motors.  

These motors come with a separate control box which is mounted 

on the side of the unit as shown in Figure 8.  The harness from the 

motor is inserted into the control box which has another harness 

leading into the control panel of the unit.

Control Box

Figure 8

The high voltage wiring is the same as the other ACNF models.

The low voltage wiring connections for the ACNF25 and ACNF31 

models are shown in Figure 9.  The wire from the motor, T2 

(purple,)  T3  (pink)  or  T4  (yellow),  connects  to  “Y”  from  the 

thermostat/condenser depending on the application.  The rest of 

the connections are similar to the other ACNF models.

Thermostat 

Air Handler 

Condensing Unit 

#18 Gauge 

24 VAC 

#18 Gauge 

24 VAC 

Note: Connect T2,T3 or T4 to the Y 

terminal to the outdoor unit.

 

T1

T5

CONFIRM SPEED TAP SELECTED (T2, T3, OR T4)

IS APPROPRIATE FOR THE APPLICATION BASED ON THIS TABLE.

WIRE COLOR

PURPLE

PINK

YELLOW

BTU

18000

24000

h

HIGH CFM OPTION

Figure 9

MAINTENANCE

Room Thermostat

The room thermostat controls the operation of your heating and/

or cooling unit. It senses the indoor temperature and signals the 

equipment to start or stop maintaining the temperature you have 

selected for your comfort. The room thermostat should be in a 

central, draft free inside wall location for best operation. Do not place 

any heat producing apparatus such as lights, radio, etc., near the 

thermostat as this will cause erratic operation of the comfort system. 

Содержание ACNF18 Series

Страница 1: ...JURY OR DEATH WARNING Cancer and Reproductive Harm www P65Warnings ca gov PROP 65 WARNING FOR CALIFORNIA CONSUMERS 0140M00517 A HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UN...

Страница 2: ...f 1 5 2 and 2 5 nominal tons of cooling with a PSC motor ACNF18 ACNF24 and ACNF30 and 2 and 2 5 nominal tons of cooing with a constant torque EEM motor ACNF25 and ACNF31 Electric heat models are avail...

Страница 3: ...ditioned air from escaping It is permissible in this application to use a shallow trap design sometimes referred to as a running trap Unit 3 MIN POSITIVE LIQUID SEAL REQUIRED AT TRAP Drain Connection...

Страница 4: ...N 64 2 5 TON 68 Table 2 2 Mount the unit in a horizontal position above a dropped ceil ing of adequate strength Refer to Figure 3 Refer to Figure 4 for proper mounting methods DROP CEILING PLENUM OUTL...

Страница 5: ...n 1 6 of a turn Do not overtighten CAUTION EXCESSIVE TORQUE CAN CAUSE ORIFICES TO STICK USE THE PROPER TORQUE SETTINGS WHEN TIGHTENING ORIFICES 11 Replace suction line insulation 12 After installation...

Страница 6: ...he unit Control Box Figure 8 The high voltage wiring is the same as the other ACNF models The low voltage wiring connections for the ACNF25 and ACNF31 models are shown in Figure 9 The wire from the mo...

Страница 7: ...o provide many years of dependable trouble free comfort when properly maintained Proper maintenance will consist of annual checkups and cleaning of the internal electrical and heat transfer components...

Страница 8: ...8 778 T4 969 912 854 798 778 T3 802 776 690 641 584 T2 680 610 550 484 431 T1 680 610 550 484 431 T5 999 928 868 824 764 T4 999 928 868 824 764 T3 871 798 750 687 614 T2 763 695 625 548 478 T1 763 695...

Страница 9: ...9 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Страница 10: ...10 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Страница 11: ...11 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Страница 12: ...in all product comments Please fill out the feedback form on one of the following links Daikin Products https daikincomfort com contact us Goodman Brand Products http www goodmanmfg com about contact...

Отзывы: