![Goodman ACES80 Series Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/goodman/aces80-series/aces80-series_service-and-troubleshooting_2243409044.webp)
SERVICING
44
Set Point on
Pressure Fall (PF)
W.C.
Max Make
Pressure On
Rise W.C.
Pressure Switch
Part#
*MES800403A*
-0.70 ±0.06
-0.85
0130F00505
*MES800603A*
-0.75 ±0.07
-0.90
0130F00506
*MES800603B*
-0.75 ±0.07
-0.90
0130F00506
*MES800604B*
-0.75 ±0.07
-0.90
0130F00506
*MES800803B*
-0.70 ±0.06
-0.85
0130F00505
*MES800804B*
-0.70 ±0.06
-0.85
0130F00505
*MES800804C*
-0.75 ±0.07
-0.90
0130F00506
*MES800805C*
-0.75 ±0.07
-0.90
0130F00506
*MES801005C*
-0.70 ±0.06
-0.85
0130F00505
*MES801205D*
-0.80 ±0.05
-0.95
0130F00507
*CES800403A*
-0.60 ±0.06
-0.75
0130F00504
*CES800603A*
-0.60 ±0.06
-0.75
0130F00504
*CES800804B*
-0.60 ±0.06
-0.75
0130F00504
*CES800805C*
-0.60 ±0.06
-0.75
0130F00504
*CES801005C*
-0.80 ±0.05
-0.95
0130F00507
*MES80 / *CES80 Pressure Switch Trip Points And Usage Chart
MODEL
ID BLOWER