35
F2
Tin temperature sensor failure (Inlet water temperature)
F3
Tliq temperature sensor failure
F4
Tout temperature sensor failure (Outlet water temperature)
F5
Water flow switch off protection
E6
Communication failure between indoor unit and outdoor unit
F9
Cooling mode antifreeze switch off protection
EE
Indoor unit EEPROM failure(only for split type)
FA
Insufficient water flow protection
“8888”Flashing
Communication failure between PCB and controller display
A1
Tao temperature sensor failure (Ambient temperature)
A2
Tdef temperature sensor failure (Defrosting temperature)
A4
Td temperature sensor failure (Compressor exhaust temperature)
A7
Ts temperature sensor failure (Compressor suction temperature)
A8
Tcm temperature sensor failure (Coil temperature)
Ab
Pd pressure switch failure (High pressure switch )
H3
Outdoor unit EEPROM failure
P6
High pressure switch disconnect protection
P9
Low pressure switch disconnect protection
P1
Cooling mode over pressure protection
L2
Indoor unit and outdoor unit communication failure
LC
Control board and drive board communication failure
C4
Td temperature sensor over temperature protection (Compressor exhaust
temperature)
C7
Exhaust overheating value too low protection
Y3
Fan motor 1 failure
J3
Fan motor 2 failure
H5
Four-way valve failure
b9
Drive board IPM over temperature protection
b5
Drive board power input over-current protection
b6
Drive board DC bus under-voltage protection
b7
Drive board heat sink temperature sensor failure
b1
Drive module protection (F0)
b2
Drive module hardware protection
b3
Drive module software protection
b4
Compressor disconnected with drive board
bA
Compressor failed to activate or out of steps failure