4
OPERATION MODES
V2Plus system with 1 access door panel (1 riser).
Installations with 1 access door panel and up to 2 repeaters in daisy chain where it is wanted to increase the
distance with the repeater in 200 m. more (see example A & C) or increase up to 32 monitors/telephones in a
max. distance of 150 m. between the repeater and the last monitor/telephone and between monitors/telephones
of different apartments connected to repeater (see example B, C & D).
Important:
Read the footnotes.
A: 32 elements (350 meters):
EL500/V2Plus
FA-V2Plus
RD-V2Plus
FA-V2Plus
150m
25m.
0,75 mm
2
200m
3m.
1,5 mm
2
2
2
B: 64 elements (300 meters):
EL500/V2Plus
FA-V2Plus
RD-V2Plus
150m
25m.
0,75 mm
2
150m
2
BUS
FA-V2Plus
3m.
1,5 mm
2
2
C: Repeater
(64 elements / 500 meters):
in daisy chain
EL500/V2Plus
FA-V2Plus
RD-V2Plus
150m
25m.
0,75 mm
2
200m
2
FA-V2Plus
3m.
1,5 mm
2
2
RD-V2Plus
FA-V2Plus
3m.
1,5 mm
2
2
BUS
BUS
BUS
BUS
150m
Bus: Golmar RAP-2150 cable.
BUS
BUS
BUS
BUS
*
*
*
Important:
Do not exceed the max. monitors/telephones connected to a door panel/multiplexer/repeater, or the distances
indicated for door panel/multiplexer/repeater and last monitor and monitors between different apartments connected to door
panel/multiplexer/repeater. For characteristics, sections and distances see the corresponding product manual.
D1L or D4L-V2Plus
Up to 32 monitors
Apartments
D1L or D4L-V2Plus
Up to 32 monitors
Apartments
D1L or D4L-V2Plus
Up to 32 monitors
Apartments
D1L or D4L-V2Plus
Up to 32 monitors
Apartments
D1L or D4L-V2Plus
Up to 32 monitors
Apartments
( )
1
( )
1
( )
1
( )
1
( )
1
Note:
If the repeater/multiplexer is at a distance less than 50 meters from the door panel, place in the door panel the dip
gain SW1-6 to OFF.
( )
1