Optional Remote Controls

Goldline offers a variety of wired and wireless remote control options for the Pro Logic.  Each model gives
you the ability to control your pool’s functions from a remote location, away from the Control Center.

Wired Remote Controls

Up to 3 wired remote controls can be installed.  See page 19 for wiring information.

AQL-WW-P-4

The AQL-WW-P-4 display/keypad must be mounted indoors or in a weather protected area (rain should
never touch the unit).  The display/keypad is designed to mount onto a standard electrical utility box (same
box as a single light switch, ideal for new construction) or can be mounted directly onto any wall surface.
When selecting a location, note that the wire to the Pro Logic main unit must be less than 500’ long. Refer
to the remote’s installation instructions as well as the steps below:

1. Remove display/keypad baseplate from the cover by lifting up on the cover at the lower end of the

keypad. See diagram below.

2. Screw the baseplate in the desired position (screws supplied by installer).

3. See “Electrical Wiring”  (page 19) for instructions on running the cable from the Pro Logic main unit

to the remote display/keypad.

AQL-SS-6B-x  (x=W, G or B for White, Gray or Black)

The AQL-SS-6B is a double insulated, waterproof device which is intended for installation at the water's
edge.  The remote control comes with an attached 150’ cable and is typically installed at the tile-line of the
spa wall, or in the deck, within arm's reach of a pool/spa occupant.  Refer to the AQL-SS-6B installation
manual for specific mounting and wiring information.

Wireless Remote Controls

Note that the Pro Logic is compatible with AQL2 wireless remote controls only.  A single AQL2-BASE-
RF Base Station must be installed on the Pro Logic in order to use any of the Goldline wireless remote
controls.  With the Base Station installed, there is no limit on the number of wireless remotes that can used.
The maximum distance between the wireless remotes and the base station on the Pro Logic main control
unit is 400 feet (120m) line of sight or 200 feet (60m) through walls, etc.  If in doubt about the distance, test
operation before installing the remote. All wireless models require the user to run the “Teach Wireless”
routine in the Settings Menu.  This information can be found in the Pro Logic Operation Manual and the
owner’s manual of each remote.

AQL2-Tx-RF-P-4

The AQL2-Tx-RF-P-4 is a portable battery operated remote control designed to be used in a weather
protected area (rain should never hit the unit). This remote comes with a wall mounted power supply for
recharging the built-in batteries.

7

24

Lowest Speed

This is the lowest speed that the variable speed pump is allowed to run at. It is used as the
lower limit in the Low Speed Settings Menu. Set lowest speed from 10% (default) to 50%.

Highest Speed

This is the highest speed that the variable speed pump is allowed to run at. It is used as the
upper limit in the High Speed Settings Menu.  Also, this is the speed that the pump will run
at during the first 3 minutes of operation anytime the pump has been off for more than 30
seconds. Set highest speed from 20% to 100% (default).

Freeze Protection

Freeze protection is used to protect the pool and plumbed equipment against freeze damage.
If freeze protection is enabled and the AIR temperature sensor falls below the freeze threshold
(see below), the Pro Logic will turn on the filter pump to circulate the water. If “Pool and Spa”
is selected in the Pool/Spa sub-menu (see page 22), the valves will also alternate between the
pool and spa every 30 minutes and the filter pump will turn off while the valves are turning.
The chlorinator will not operate if freeze protection is the only reason the pump is running.

Freeze Protection Speed

This menu only appears if freeze protection is enabled and the pump is configured for 2-
speed or variable speed pump operation. This is the speed that the pump will run at during
freeze protection operation. Select high (default) or low speed operation.

Freeze Protection Temperature

Select the temperature to be used for freeze protection.  Temperature is adjustable from 33ºF
-  42ºF (1ºC - 6ºC).  38ºF (3ºC) is default. This threshold will be used for all outputs that have
freeze protection enabled.

Heater1 Config.

+ to view/change

Heater1 

Disable

Heater1 Cooldown 

Disabled

Heater1 Extend 

Disabled

Push to access heater options

Toggle between Enabled and Disabled (default) Heater 1

Toggle between Enabled and Disabled (default) Heater 1 Cooldown

Toggle between Enabled and Disabled (default) Heater 1 Extend

Move to previous/next configuration menu

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to previous/next configuration menu

if “Heater1” is enabled

if “Heater1” is enabled

Allow Low Speed 

Disabled

Toggle between Enabled and Disabled (default) 

Move to next menu item or previous/next configuration menu

if “Heater1” is enabled and
1-speed filter pump is not selected

Heater1

If the heater is “Enabled”, the heater relay will turn on when the water temperature is less
than the desired temperature setting and the filter pump is running.  The desired temperature
is in the “Settings Menu”.  If applicable, the homeowner will be prompted to enter separate
“pool” and “spa” settings.  Depending on the position of the pool/spa suction valve, the
proper temperature setting will be used.

Heater Cooldown

This feature ensures that the heater cools down before water circulation is stopped.  When
enabled, the Pro Logic will continue to run the filter pump for 5 minutes after the heater turns
off.  During this period the filter pump LED will flash and also a “Heater Cooldown, X:XX
remaining” message will scroll on the display.

Remote Keypad

to remove cover

push up here 

Содержание Pro Logic PL-P-4

Страница 1: ...www goldlinecontrols com Automation and Chlorination Installation Manual for model PL P 4 LD C G LINE ON TROLS...

Страница 2: ...nal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment One bondin...

Страница 3: ...al Remote Controls 7 Optional Base Station 8 Optional ValveActuators 8 3 Plumbing Pool Spa Configuration 9 Turbo Cell 10 Flow Switch 10 4 Electrical Main Service 11 Wiring Grounding and Bonding 11 Cir...

Страница 4: ...roofcover formountingonsideofProLogic Mounting hardware screws etc for mounting Pro Logic and remote display keypad Valves use standard Hayward Pentair Compool or Jandy valves Additionalvalveactuators...

Страница 5: ...raturesensors Remotedisplay keypad optional Valve actuators if applicable 3 Plumbing page 9 GeneralPoolEquipment Turbo Cell Flow Switch 4 ElectricalWiring page 11 Main service Groundingandbonding Circ...

Страница 6: ...ou are using the chlorinator features on the Pro Logic Control If you are NOT using the chlorinator it is recommended that you follow all of the other chemistry recommendations be sides salt Refer to...

Страница 7: ...100 45 110 160 50 73 120 170 55 77 130 180 59 81 140 190 64 86 150 200 68 90 93 42 107 48 120 55 133 61 147 213 67 98 160 227 73 104 173 240 79 110 187 253 85 117 200 267 91 123 2200 3000 2800 2400 32...

Страница 8: ...h x 893 Length x Width x Average Depth x 1000 POUNDS and Kg OF STABILIZER CYANURIC ACID NEEDED FOR 80 PPM Gallons and Liters of Pool Spa water Current Stabilizer Level ppm 0 ppm 20 ppm 60 ppm 30 ppm 4...

Страница 9: ...l O ring makes an adequate seal Do not overtighten 4 For maximum temperature accuracy cover the sensor and 3 6cm of pipe on either side with insulationandwhitepaint Air Sensor Mount the air sensor out...

Страница 10: ...sulated waterproof device which is intended for installation at the water s edge Theremotecontrolcomeswithanattached150 cableandistypicallyinstalledatthetile lineofthe spa wall or in the deck within a...

Страница 11: ...emote control is used To installthebasestation removetheknockoutontheupperleftsideoftheProLogicmaincontrolunit insert the base station and then tighten the nut from the inside Also refer to the Base S...

Страница 12: ...mps operate only when the filterpumpisonandthesystemisinthe poolonly operatingmode 6 The plumbing diagram above is intended to be used as a general guideline and is not a complete plumbingschematicfor...

Страница 13: ...for a watertight seal For systems with 1 plumbinguseadaptors providedbyinstaller Flow Switch supplied withAQL CLchlorination kit TheflowswitchmustbeplumbedinthesamesectionofplumbingastheTurboCell The...

Страница 14: ...ical panel to the Pro Logic ground bus bar Also ground each piece of high voltage 120 or 240VAC equipment that is connected to the Pro Logic control relays or circuit breakers The Pro Logic should als...

Страница 15: ...heProLogicrequires120VAC 2A powertooperatethecontrollogiccircuitsandthechlorinator This power should be connected to one of the circuit breakers WARNING 120VAC only permanent damage if connected to 24...

Страница 16: ...externaltransformer Forlightingsystemsthathavebothalightsource and color wheel connect the light source to the Lights relay and then connect the color wheel to one of theAUXoutputs Hayward Variable Sp...

Страница 17: ...red by a GFCB Low Voltage Wiring ValveActuators The Pro Logic can control up to three automatic valve actuators Two of the valve outputs are dedicated to the pool spa suction Valve2 and return Valve1...

Страница 18: ...raturerating for wires If no guidance is given use 105 C rated wire 3 Set any ON OFF switch on the heater to ON 4 Set the thermostat s on the heater to the maximum hottest setting Laars Heaters 1 Turn...

Страница 19: ...aterwillfirewheneverProLogicrequests whenProLogic Heater LEDisilluminated Pentair Purex MiniMax 1 Turn power off to heater 2 Removefactoryinstalledjumperfromthe ExtSwitch connector 3 Wire the Pro Logi...

Страница 20: ...L or SPA which then disables the remote control by the Pro Logic To prevent this Remove the heater touch pad connector P5 which will disable the touchpad STA RITE Heater 1 Turn power off to heater 2 R...

Страница 21: ...d VSC power connections if possible VSCPumpAddressSetting For proper communications a pump address must be set for each VSC used in the system For single pumpsystems theVSCaddressshouldbesetto001 When...

Страница 22: ...isplay keypads are installed Never connect more than 2 wires to any terminal block Two remotes can be wired back to the Pro Logic main unit or the second display keypad and third ifapplicable canbe da...

Страница 23: ...lineAqua Rite Chlorinator TheProLogiccancontroloneormoreGoldlineAquaRitechlorinatorswhenadditionalsanitizingcapacity is required A4 wire connection is used to communicate to theAqua Rite and can be wi...

Страница 24: ...gle between T CELL 5 and T CELL 15 Move to next menu item Move to next menu item Chlorinator Enabled Display Salt Chlor Config to view change Toggle between Display Salt default and Minerals Toggle be...

Страница 25: ...d Disabled default if Pool Only or Spa Only is selected Move to previous next configuration menu Filter Off Valve Change Enabled Toggle between Enabled and Disabled default if Pool and Spa is selected...

Страница 26: ...ter Cooldown mode Filter Config to view change Filter Pump 1 Speed Freeze Protect Enabled Lowest Speed 10 Highest Speed 100 Push to access pump options Rotates between 1 speed default 2 speed and vari...

Страница 27: ...erature to be used for freeze protection Temperature is adjustable from 33 F 42 F 1 C 6 C 38 F 3 C is default This threshold will be used for all outputs that have freeze protection enabled Heater1 Co...

Страница 28: ...enu item if Solar is enabled if Solar is enabled Allow Low Speed Disabled Toggle between Enabled and Disabled default Move to next menu item or previous next configuration menu if Solar is enabled and...

Страница 29: ...hts Function Although designated as the Lights output the function of the lights relay is similar to the aux1 and aux2 relays If pool lights are wired to the lights relay some options including Solar...

Страница 30: ...c will energize the lights relay IMPORTANT this only enables operation of the lights relay during freeze see the Filter Pump Config menu to enable freeze protection for the main circulation system NOT...

Страница 31: ...ntdown Timer Timeclock selected above and turn the aux1 off when filter pump is off first 3 minutes of filter pump operation allows the pump to prime and get water flowing when the pool spa suction re...

Страница 32: ...re threshold the Pro Logic will turn on the valve to allow circulation of the water IMPORTANT this only enables operation of the valve3 output during freeze see the Filter Pump Config menu to enable f...

Страница 33: ...ion parameters Move to previous next configuration menu config not reset Move to previous next menu config not reset Move to previous next configuration menu Use this function to erase all previous sy...

Страница 34: ...ng is set as high as possible usually 104 F 40 C Also note that some heat pumps actually have be set to the lowest possible temperature 3 Once the heater is running you can verify the heater cooldown...

Страница 35: ...itecap Drive North Kingstown RI 02852 for warranty service The costs incurred in removal and or reinstallation of the product are NOT covered under this warranty Some states do not allow limitations o...

Страница 36: ...pool high low speed day and time backlit display light beeper teach wireless remote wireless channel maintenance menu pH calibration wizard clean probe wizard timers menu pool filter pump1 or hi spee...

Отзывы: