SmartBox
®
1 / SmartBox
®
2 / SmartBox
®
3
part no. 28 100 57 f
13 / 20
Example 2: Well, 7.50m maximum water level from ground of the well, Display m
(fill level 4.20m)
relay switching function is desired.
SmartBox
®
2
Probe 0 - 1000mbar, indication in m water column
Relay 1 has to protect the pump against running dry (switch off)
Relay 1- on at 99%-10% - off at < 10%
Step
Entries / selection
1.Measure probe
1000mbar
(set with [+] / [-] keys)
2.Liquid
Water (
set with [+] / [-] keys)
3.Tank shape
Linear
4.Tank volume
7500L
(set with [+] / [-] keys)
5.Tank height
750cm
(set with [+] / [-] keys)
5b.Filling limit
99%=743cm
(set with [+] / [-] keys)
6.View
View details
FiPercnt
display 2. line - (set with [+] / [-] keys)
7.Relay 1
Active
Switch-on: 99%
Switch-off: 10%
(set with [+] / [-] keys)
7.Relay 2
Deactive
8.Exit
press [+] key to go to
12.Unit
m
(
set with [+] / [-] keys)
13.Rounding
Automatically
14.Exit
press [Enter] to see the indication
Water
4.20m
-3.23m
56%
Example 3: Buried tank, cylindrical, horizontal, for 100600 litres diesel oil
Inner height 288.6cm, (fill level 54cm)
SmartBox
®
3
Standard probe 0 - 250mbar
Limit value message on the device at minimum level <25%
Acoustic alarm - on at <25% - off at >27%
Step
Entries / selection
1.Measure probe
250mbar
(set with [+] / [-] keys)
2.Liquid
Diesel
(set with [+] / [-] keys)
3.Tank shape
Cyl. > 50.000L
(set with [+] / [-] keys)
4.Tank volume
100.600L
(exact value from volume table
set with [+] / [-] keys)
5.Tank height
288.6cm
(exact value from volume table
set with [+] / [-] keys)
5b.Filling limi
t
99%=743cm
(set with [+] / [-] keys)
6.View
View details
Level
display 2. line - (set with [+] / [-] keys)
6.Beepe
r
Active
Switch-on: 25%
Switch-off 27%
(set with [+] / [-] keys)
7.Relay
Deactive
8.Exit
press [Enter] to see the indication
Diesel
12.800L
13%
54cm