28
©Godiva Ltd. Our policy is one of continuous development. We therefore reserve the
right to amend specifications without notice or obligation.
OPERATION
CAUTION:
WT_C OR WS_C PUMPS SHOULD ONLY BE USED WHEN WORKING
FROM OPEN WATER OR A TANK FEED. PROBLEMS WILL OCCUR WITH THE
WATER / AIR PRESSURE RATIO, SHOULD PRESSURISED (HYDRANT) WATER
SUPPLY BE APPLIED DIRECTLY TO THE SUCTION TUBE. HYDRANT SUPPLY
MAY ONLY BE USED ONLY TO MAINTAIN THE WATER LEVEL IN THE VEHICLE
TANK.
FoamLogix Control Panel Functions
Commissioning / Start-Up Procedure
1.
Check that all the necessary connections have been correctly made.
2.
Ensure that the compressor, pump gearbox and bearing housing are filled with
the correct oil type and quantity.
3.
Run the pump at 2-3 bar with compressor engaged.
4.
Run the compressor for 30 seconds to allow oil to circulate.
5.
Stop unit and check compressor oil level – top up if necessary.
6.
Turn the bypass valve on the FoamLogix to bypass and provide a suitable
receptacle to collect the foam, agent.
7.
Ensure that there is sufficient foam agent in the tank(s). For
FoamLogix 3.3
,
select tank
A