Page
7
SmartFOAM
Figure 4
: SmartFOAM Buttons and Indicators
4. Set the foam injection rate to 1.0% by pressing
the INCR or DECR arrow buttons.
5. Press the ON/OFF button to energize the Hale
SmartFOAM system.
a. The Pump Speed bar graph will
increase to indicate the motor is
running.
b. Observe the discharge at the bypass
hose to make sure the foam pump is
operating.
6. After one minute press the ON/OFF button again
to stop the foam pump. Approximately one
gallon (3.8 liters) of water should discharges into
the container. The TOTAL FOAM display reads
approximately 1.00.
7. Exit simulated water flow. Use the steps
described in step 3 and Figure 46
8. Drain water from the foam tank and concentrate
lines and return the bypass valve’s handle to the
INJECT
position.
9. Verify operation of the flow sensor. Also
calibrate the flow sensor using the calibration
procedures. See “User Calibration”.
This completes the Hale SmartFOAM system operation
checks accomplished at the system installer facility.
Foam pump feedback calibration along with setting of
user specified default simulated flow and concentrate
injection rates should be accomplished upon delivery to
the end user using actual end user specified foam
concentrates and default values.