7.4 Problems with Current 2

Current Reading:

Less than expected

Time of Day:

Day, clear sunny skies

Possible Cause:

(1) Current is being limited below 1 Amp as per normal operation.

(2) Incorrect series/parallel configuration and/or wiring connections and/or wire gauge.

(3) Dirty or shaded module or lack of sun.

(4) Blown diode in solar module when two or more modules are connected in parallel.

How to tell:

(1) Battery State of Charge screen is close to 100% and the Sun and Battery icon are present

with an arrow in between.

(2) Check that the modules and batteries are configured correctly and check wiring connections.

(3) Modules look dirty, overhead object is shading modules or it is an overcast day in which a

shadow cannot be cast.

Note:

Avoid any shading no matter how small. An object as small as a

broomstick held across the solar module may cause the power output to be cut to almost nil.

Overcast days may also cut the power output of the module to almost nil.

(4) Disconnect one or both array wires from the controller. Take a voltage reading between the

positive and negative array wire. A single 12-volt module should have an open circuit voltage

between 17 and 22 volts. If you have more than one solar module, you will need to conduct this

test between the positive and negative terminals of each module junction box with either the

positive or negative wires disconnected from the terminal.

Remedy:

(2) Reconnect in correct configuration. Tighten all connections. Check wire gauge and length of

wire run. Refer to Suggested Minimum Wire Gauge in Section 4.

(3) Clean modules, clear obstruction or wait for conditions to clear.

(4) If the open circuit voltage of a non-connected 12-volt module is lower than the

manufacturer’s specifications, the module may be faulty. Check for blown diodes in the solar

module junction box, which may be shorting the power output of module.

8.0 General Warranty

GP warrants the GP-PWM-30-SQ for a period of one (1) year from the date of purchase. This

warranty is valid against defects in materials and workmanship for the one (1) year warranty

period.

Proof of purchase is required

for any warranty replacements. Visit

gpelectric.com

for

warranty details.

8.1 Return Information

Visit

gpelectric.com

to read the “frequently asked questions” section of our website to

troubleshoot the problem. If trouble persists:

1. Call your Go Power!

®

Technical Support team (1-866-247-6527).

2. Return defective product to place of purchase

Содержание GP-PWM-30-SQ

Страница 1: ...verview 2 2 0 Warnings 3 3 0 Choosing a Location 4 4 0 Installation Instructions 4 5 0 Operating Instructions 5 6 0 Frequently Asked Questions FAQs 7 7 0 Troubleshooting 7 8 0 General Warranty 8 9 0 W...

Страница 2: ...anel to battery 2 CHARGING CHARACTERISTICS Minimum battery start charging voltage VDC Soft start charging voltage Soft start charging current 50 PWM duty Bulk charge voltage Absorption charging voltag...

Страница 3: ...um Power Current Imp of the solar PV strings in parallel The resulting system Imp current is not to exceed 30A The voltage of the array is the rated open circuit voltage Voc of the PV array and is not...

Страница 4: ...uge For other applications please refer to standard wire guide 100 Watt 10 Wire Gauge 170 Watt 10 Wire Gauge Identify the polarity pos and neg on the cable used for the battery and solar module Use co...

Страница 5: ...for details on each profile Self test starts digital meter segments test Software version test Rated voltage Current test After going into charging process the LCD displays the charging states as bel...

Страница 6: ...matically run this stage to bring the internal cells as an equal state and fully complement the loss of capacity LTO Gel Life P04 and AGM battery do not run Equalization charge Float Charge Battery is...

Страница 7: ...wire gauge or both How to tell 1 Check the voltage at the controller battery terminals with a voltmeter and compare with the voltage reading at the battery terminals If there is a voltage discrepancy...

Страница 8: ...uld have an open circuit voltage between 17 and 22 volts If you have more than one solar module you will need to conduct this test between the positive and negative terminals of each module junction b...

Страница 9: ...rcuits 30A fuse for the GP PWM 30 SQ as close to the battery panel as possible The Solar Controller has 4 terminals which are clearly marked Solar and Battery There is a 12V and earth GND terminal for...

Страница 10: ...2013 GO POWER GP_MAN_GP PWM 30 SQ_RevH gpelectric com...

Страница 11: ...11 TOP BOTTOM...

Отзывы: