INSTALLATION
Wall Mount Installation
Wall mounting hangers with a pogo are available for
installation. The figure illustrates the various parts for a
typical wall mount charger installation:
Step 1. Bolt the Wall Mount Hanger to the Wall
Secure the wall mount hanger to the concrete wall through
the pre-drilled holes in the hanger. Ensure the two fins are
facing up. Mount to a solid concrete wall through holes using
bolts into wall anchors – check with professional installation
personnel to determine proper mounting techniques for all
wall types.
Step 2. Hang the Charger on the Wall Mount
Hang the charger on the wall mount hanger so that the two
slits on the back of the charger line up with the two fins of
the hanger.
Step 3. Mount the Bottom Brace to the Charger and Wall
Step 4. Mount the Pogo Wall Bracket to the Wall
and Attach the Pogo
Top
Bottom
Installation must only be carried out by suitably qualified personnel and in accordance with current local and national wiring regulations.
Battery leads should not be altered without prior consultation with service personnel.
The charger should be sited in a cool, dry, well-ventilated location away from corrosive fumes and humid atmospheres. Ambient temperature range
must be maintained between 32°F-104°F.
Ensure ventilation is not obstructed at the left air intake and right exhaust vents.
The charger is for indoor use only.
Before installation, check that the charger has not sustained any damages during transit. Make sure the electrical ratings are suitable for both the
intended AC input supply and the DC output current and voltage for the batteries to be charged. Also ensure that the connector polarity is correct
and matches the polarity of the battery connector.
CAUTION – To reduce the risk of fire, use only on circuits provided with branch circuit protection consistent with the current indicated on theFactory
Charger Configuration label and in accordance with the National Electrical Code, ANSI/NFPA 70 or equivalent.
The circuit breakers rating should be based on the charger's maximum input current, as stated on the Factory Charger Configuration label. (See the
Technical Specifications page for more details)