4
PSD1004
- Intrinsically Safe 5 V Supply Module
G.M. International ISM0074-5
PSD1004 is an isolated Intrinsically Safe Power Supply Module installed into standard EN50022 T35 DIN Rail located in Safe Area / Non Hazardous Locations or
Zone 0, Zone 1, Zone 2 Hazardous Area, Gas Group IIB or IIA, Temperature Classification T4 (according to IEC/EN60079-11, EN50020) within the specified operating temperature limits
Tamb -20 to +60 °C, and connected to Associated Apparatus equipment with a maximum limit for Uo<Ui, Io<Ii and Po<Pi as specified in the data sheet.
PSD1004 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
Warning: substitution of components may impair Intrinsic Safety.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative, any unauthorized modification must be avoided.
Warning
Operation
PSD1004 provides fully floating 5 VDC supply to drive Intrinsically Safe loads, typically transmitter or display unit located in Hazardous Area. PSD1004 has remote sensing capability to
compensate line resistance voltage drop-out, connect the sense terminals near the load at the output terminals for better performance and stabilization. If the line resistance is low,
connecting the sense terminals is not mandatory (the voltage stabilization is done internally to the module). Presence of supply power is displayed by a green signaling LED.
Installation
PSD1004 is an I.S. power supply housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022.
PSD1004 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet"
Instruction Manual D1000 series for detailed instructions.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit
without suffering or causing any damage.
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the data sheet and enclosure side a block diagram identifies all connections.
Identify the function and location of each connection terminal using the wiring diagram on the corresponding data sheet, as an example:
Connect input power positive at terminal “1” or “3” and negative at terminal “2” or “4” (two terminals are provided for daisy chain connection if required to supply two PSD1004
with a single Associated Apparatus).
Connect positive output at terminal “13” and negative output at terminal “16”.
Connect sense terminal, if required, at terminal “14” positive and terminal “15” negative.
Note that junction point must be near as possible to the load.
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired, in accordance to the relevant national or international installation standards
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1014 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
Start-up
Before powering the unit check that all wires are properly connected, particularly their polarity, also check that Intrinsically Safe conductors and cable trays are segregated (no direct
contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed wires that could touch each other causing
dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, check the supply voltage generated by PSD1004 is 5 Vdc.
Function Diagram
MODEL PSD1001C
+ 13
- 14
3 +
4 - Supply
Out
=
=
+ 15
- 16
MODEL PSD1004
O + 13
S + 14
1 +
2 -
=
=
S - 15
O - 16
3 +
4 -
PSU1003
HAZARDOUS AREA ZONE 0, GROUP IIB T4
SAFE AREA, ZONE 2, GROUP IIC T4