GMI D6072D Скачать руководство пользователя страница 3

 

D6072 

- SIL 2 Multifunction Temperature Converter 

G.M. International ISM0216-5 

Ordering Information 

 

Front Panel and Features 

 



SIL 2 according to IEC 61508:2010 (Route 2H) with Tproof = 10 / 20 years (

10% / >10 % of total SIF), for analog current source/sink output. 



SIL 2 according to IEC 61508:2010 (Route 2H) with Tproof = 9 / 20 years (

10% / >10 % of total SIF), for alarm output. 



SC 3: Systematic Capability SIL 3. 



Installation in Zone 2 / Division 2. 



mV, thermocouple, 2 or 3 or 4 wire resistance/RTD or transmitting potentiometer Input Signal. 



2-wire RTD line resistance compensation. 



Internal Reference Junction Compensation. 



Fastest integration time: 50 ms. 



Fully customizable Output range from 0 to 24 mA Output Signal linear or reverse (typical 0/4-20 mA). 



Output duplication possible for D6072D. 



Modbus RTU RS-485 Output. 



Independent multiple Fault detection. 



Programmable alarm available on solid state contact output or Termination Board connector. 



High Accuracy, µP controlled A/D converter. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



Fully programmable operating parameters. 



ATEX, IECEx Certifications (pending). 



UL & C-UL, TÜV Certifications. 



High Density, two channels per unit. 



Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards. 



Data logging and monitoring via software. 

D6072S: +Input for thermocouple TC or for 3, 4 wire RTD or potentiometer 
D6072D: +Input Ch1 for thermocouple TC or for 3 wire RTD or potentiometer 

Terminal block connections 

 

D6072S: -Input for thermocouple TC or for 2, 3, 4 wire RTD or potentiometer 
D6072D: -Input Ch1 for thermocouple TC or for 2, 3 wire RTD or potentiometer 

D6072S: Input for 2, 3, 4 wire RTD or potentiometer 
D6072D: Input Ch1 for 2, 3 wire RTD or potentiometer 

D6072S: Input for 4 wire RTD 
D6072D: Input Ch2 for 2, 3 wire RTD or potentiometer 

D6072D: +Input Ch2 for thermocouple TC or for 3 wire RTD or potentiometer 

D6072D: -Input Ch2 for thermocouple TC or for 2, 3 wire RTD or potentiometer 

7

 

8

 

9

 

10

 

11

 

12

 

D6072S, D6072D (Ch1): +Output Ch1 (source current mode) or 
 

-Output Ch1 (sink current mode) 

1

 

D6072S, D6072D (Ch1): -Output Ch1 (source current mode) or 
 

+Output Ch1 (sink current mode) 

2

 

Model:  

D6072 

1 channel 

2 channels 

Power Bus and DIN-Rail accessories: 
Connector JDFT049 

 

Cover and fix MCHP196 

Terminal block male MOR017 

Terminal block female MOR022 

D6072S (Alarm), D6072D (Current/Alarm): +Output Ch2 (source current) or 
 

-Output Ch2 (sink current) or +Output (Alarm/Fault) 

3

 

D6072S (Alarm), D6072D (Current/Alarm): -Output Ch2 (source current) or 
 

+Output Ch2 (sink current) or -Output (Alarm/Fault) 

4

 

 +Power Supply 24 Vdc 

5

 

 -Power Supply 24 Vdc 

6

 

7 8 

9 10 

11    12 

4 3 

6 5 

Содержание D6072D

Страница 1: ...6072 SIL 2 Multifunction Temperature Converter G M International ISM0216 5 SIL 2 Multifunction Temperature Converter DIN Rail and Termination Board Models D6072S D6072D D6072S D6072D INSTRUCTION MANUA...

Страница 2: ...rnout Sensor out of range Output saturation Internal fault Cable resistance fault Output Fully customizable 0 4 to 20 mA on max 300 load source mode current limited at 24 mA In sink mode external volt...

Страница 3: ...using standard DIN Rail and plug in terminal blocks with or without Power Bus or customized Termination Boards Data logging and monitoring via software D6072S Input for thermocouple TC or for 3 4 wir...

Страница 4: ...24 Vdc Modbus RS485 A B Modbus RS485 mA Sink I RL Out 2 SIL 2 mA Sink I RL In 1 In 2 TC mV 2 3 wires RTD Resistance Pot 2 3 wires RTD Resistance Pot TC ext comp TC mV TC ext comp 5 6 1 2 3 4 9 7 MODEL...

Страница 5: ...tion board connector F Power and Fault Bus Supply 24 Vdc Modbus RS485 A B Modbus RS485 mA Sink I RL Out 2 SIL 2 mA Sink I RL In 1 RTD for Cold Junction Compensation TC Copper wire Copper wire In 2 MOD...

Страница 6: ...n EN IEC60715 TH 35 DIN Rail with or without Power Bus or on customized Termination Board D6072 series can be mounted with any orientation over the entire ambient temperature range Electrical connecti...

Страница 7: ...2 0 to 1800 32 to 3272 0 050 0 090 B IEC 60584 GOST 8 585 ASTM E230 200 360 1 1 2 0 450 to 1820 842 to 3308 0 to 1820 32 to 3308 0 060 0 108 C ASTM E230 ASTM E988 100 180 0 6 1 1 0 to 2315 32 to 4199...

Страница 8: ...h2 cold junction fixed value 0 1 C RW SINT32 1202 Ch2 2 wire rtd correction mOhm RW SINT32 1204 Ch2 rtd multiplier RW FLOAT 1500 Ch1 sensor value volt res ratio uV mOhm ppm RO SINT32 MEASURE 1502 Ch1...

Страница 9: ...ce 4 potentiometer 8 Sensor Connection Bit pos Value Description 0 2 0 volt tc 2 wires 1 tc external compensation 2 res rtd 2 wires 3 res rtd 3 wires 4 res rtd 4 wires 5 potentiometer 3 wires 9 Sensor...

Отзывы: