D6036 

- SIL 2 Switch/Proximity Detector Repeater, Relay Output 

G.M. International ISM0407-0 

Ordering Information 

 

Front Panel and Features 

 



SIL 2 according to IEC 61508:2010 Ed. 2 
for Tproof = 4 / 20 years (

10% / >10 % of total SIF) for D6036S and D6036D. 



PFDavg (1 year) 2.25 E-04, SFF 70.87 % for D6036S. 



PFDavg (1 year) 2.25 E-04, SFF 71.76 % for D6036D. 



Systematic capability SIL 3. 



NO/NC switch/proximity Detector Input, NE/ND relay actuation mode. 



Field open and short circuit detection. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



In-field programmability by DIP Switch. 



TÜV Certification. 



TÜV Functional Safety Certification. 



High Density, two channels per unit. 



Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus. 

+ Input Ch 1 for Proximity or Voltage free Contact 

Terminal block connections 

 

- Input Ch 1 for Proximity or Voltage free Contact 

+ Input Ch 2 for Proximity or Voltage free Contact 

- Input Ch 2 for Proximity or Voltage free Contact 

7

 

8

 

9

 

10

 

Output Ch 1 

1

 

Output Ch 1 

2

 

Output Ch 2 

3

 

Output Ch 2 

4

 

+ Power Supply 24 Vdc 

5

 

- Power Supply 24 Vdc 

6

 

Model:     D6036 

1 channel 

2 channels 

Power Bus and DIN-Rail accessories: 
Connector JDFT049    Cover and fix MCHP196 
Terminal block male MOR017  Terminal block female MOR022 

4 3 

6 5 

7 8 

9 10 

Содержание D6036S

Страница 1: ...6036 SIL 2 Switch Proximity Detector Repeater Relay Output G M International ISM0407 0 SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D6036S D6036D D6036S D6036D INSTRUCTION MANUAL ...

Страница 2: ... W for 1 channel D6036S with 24 V supply voltage short circuit input and relay energized typical Isolation Test Voltage In Out 1 5 KV In Supply 1 5 KV In In 500 V Out Supply 1 5 KV Out Out 1 5 KV Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range OFF 1 2 mA 0 4 to 1 3 mA range switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA Input equival...

Страница 3: ... for safety system In field programmability by DIP Switch TÜV Certification TÜV Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus Input Ch 1 for Proximity or Voltage free Contact Terminal block connections Input Ch 1 for Proximity or Voltage free Contact Input Ch 2 for Proximity o...

Страница 4: ...mity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 2 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5036S 5 6 1 2 Out NO Contact SIL 2 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out NC Contact In Proximity voltage free Contact voltage free Contact R1 R2 Relay contact shown in de energized position Terminals 1 2 and 3...

Страница 5: ...red unit without suffering or causing any damage The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections Identify the number of channels of the specific card e g D6036S is a single channel model and D6036D is a dual channel model the function and location of each conn...

Страница 6: ...ne resistors de energizes relay in fault condition 7 2 OFF NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NE 1 2 1 ND 2 Output 1 ND 2 Output NE 1 2 Position in fault condition 1 2 Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energize...

Страница 7: ...hannel 1 2 SW4 ON OFF D6036D Configuration Summary Table D6036S A configuration DIP switch is located on component side of pcb This switch allows the configuration of input output relationship fault detection functions and operating mode Configuration Dip switch configuration CH1 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE 2 ON 2 OFF Disabled switch proximity sensor...

Отзывы: