D6002 

- Dummy Pass-Through Module 

G.M. International ISM0396-2 

 

Warning 

Installation 

 

 

Start-up 

 

D6002 series are electrical apparatus installed into customized Termination Boards located in Safe Area or Zone 2, Group IIC, Temperature T4 Hazardous Area within the specified 
operating temperature limits Tamb 

-

40 to +70 °C. 

D6002 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC60079

-

14 

Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules. 
De

-

energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous. 

Warning: substitution of components may impair suitability for Zone 2/Division 2. Avertissement: la substitution des composants peut nuire à l’aptitude à la Zone 2/Div. 2. 
Explosion Hazard: to prevent ignition of flammable atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. Danger d'Explosion: pour 
éviter l’inflammation d’atmosphères inflammables, débrancher l’alimentation avant l’entretien ou à moins que région est connue pour être non dangereux. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

D6002 series are Dummy pass-through housed in a plastic enclosure suitable for installation on customized Termination Board. 
D6002 series can be mounted with any orientation over the entire ambient temperature range. 
Electrical connections are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage 

(for Zone 2 installations check the area to be nonhazardous before servicing)

. Connect only one individual conductor per each clamping point, use conductors up to 2.5 mm² 

(13 AWG) and a torque value of 0.5

-

0.6 Nm. Use only cables that are suitable for a temperature of at least 85°C.The wiring cables have to be proportionate in base to the current and the 

length of the cable. On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079

-

14 Electrical apparatus for explosive gas atmospheres 

-

 Part 

14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
The enclosure provides, according to EN60529, an IP20 minimum degree of protection (or similar to NEMA Standard 250 type 1). The unit shall be installed in an area of no more than 
pollution degree 2 according to EN/IEC60664

-

1. When installed in EU Zone 2, the unit shall be mounted in a certified Ex enclosure that provides a degree of protection not less than IP54 

in accordance with EN/IEC60079-15. When installed in a Class I, Division 2 Hazardous Location, the unit shall be mounted in a supplemental enclosure that provides a degree of 
protection not less than IP54. The enclosure must have a door or cover accessible only by the use of a tool. The end user is responsible to ensure that the operating temperature of the 
module is not exceeded in the end use application. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a 
cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D6002 series must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. 
Any unauthorized modification must be avoided. 
All circuits connected to D6002 series must comply with the overvoltage category II (or better) according to EN/IEC60664

-

1. 

Before powering the unit check that all wires are properly connected, particularly input and output wires. Check conductors for exposed wires that could touch each other causing 
dangerous unwanted shorts. 

 

Содержание D6002S

Страница 1: ...D6002 Dummy Pass Through Module G M International ISM0396 2 Dummy Pass Through Module Termination Board Model D6002S D6002S INSTRUCTION MANUAL ...

Страница 2: ...079 0 EN60079 7 IECEx BVS 18 0066X conforms to IEC60079 0 IEC60079 7 UL C UL E222308 conforms to UL 61010 1 and UL 121201 for UL and CAN CSA C22 2 No 61010 1 12 and CSA C22 2 No 213 for C UL Mounting on customized Termination Board Weight about 110 g Connection by polarized plug in disconnect screw terminal blocks to accommodate terminations up to 2 5 mm2 Location installation in Safe Area Non Haz...

Страница 3: ...2 Division 2 EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety systems ATEX IECEx UL UL C Certifications Simplified installation using standard customized Termination Boards Terminal block connections 1st pole of channel 1 SAFE AREA 2nd pole of channel 1 11 12 S 1 channel Model D6002 11 12 D6002 11 12 ...

Страница 4: ...my Pass Through Module G M International ISM0396 2 Function Diagram SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 MODEL D6002S 11 12 Termination board connector ...

Страница 5: ...ctor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm Use only cables that are suitable for a temperature of at least 85 C The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections Installation and wiring must be in accordance ...

Отзывы: