D5291 

- 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition 

G.M. International ISM0112-10 

 

 

 

Technical Data 

Characteristics 

Input: 

24 Vdc nom (21.6 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

The following monitoring circuits are mutually exclusive:

 

1) 

Line input monitoring (DIP-Switch selectable):

 to allow DCS/PLC line monitoring function (pulse test). 

2) 

Voltage monitoring (DIP-Switch selectable):

 

 21.6 Vdc for normal operation,  

 17 Vdc reflects a high impedance (

 10 mA consumption) to the control device. 

Current consumption @ 24 V:

 60 mA with relay energized, typical. 

Power dissipation:

 1.5 W with 24 V input voltage and relay energized, typical. 

Isolation (Test Voltage): 

Input/Output 2.5 KV. 

Output: 

voltage free SPDT relay contact. 

Terminals 13-14, open when relay de-energized, close in energized condition. Terminals 13-15, close when relay de-energized, open in energized condition. 

Contact material: 

Ag Alloy (Cd free) or AgSnO

2

Contact rating: 

10 A 250 Vac 2500 VA, 10 A 250 Vdc 300 W (resistive load). 

Contact inrush current: 

16 A at 24 Vdc, 250 Vac. 

                                                                                                                

DC Load breaking capacity: 

 
 
 
  Mechanical / Electrical life: 

10 * 10

6

 / 5 * 10

4

 operation, typical. 

Operate / Release time: 

8 / 4 ms typical. 

Bounce time NO / NC contact: 

4 / 6 ms, typical. 

Frequency response: 

10 Hz maximum. 

Compatibility: 

CE mark compliant, conforms to Directive: 
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits - 40 to + 60 °C, relative humidity 95 %, up to 55 °C. 

Storage:

 temperature limits - 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3G Ex nA nC IIC T4 Gc 

IECEx / INMETRO / NEPSI:

 Ex nA nC IIC T4 Gc 

FM: 

NI / I / 2 / ABCD /T4, I / 2 / AEx nA nC / IIC /T4 

FMC: 

NI / I / 2 / ABCD /T4, I / 2 / Ex nA nC / IIC /T4 

EAC-EX: 

2ExnAnCIICT4 X. 

UKR TR n. 898:

 2ExnAnCIICT4 X. 

non-sparking electrical equipment. 
-40 °C 

 Ta 

 70 °C. 

Approvals: 

BVS 10 ATEX E 114 conforms to EN60079-0, EN60079-15. 
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-15. 

INMETRO DNV 13.0109 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-15. 
UL & C-UL E477485 conforms to ANSI/UL508 
FM 3046304 and FMC 3046304C conforms to Class 3600, 3611, 3810, ANSI/ISA-60079-0, ANSI/ISA-60079-15, C22.2 No.142, C22.2 No.213, C22.2 No. 60079-0, C22.2 No. 60079-15. 
C-IT.ME92.B.00206 conforms to GOST 30852.0, 30852.14. 
C

Ц

 16.0036 X conforms to 

ДСТУ

 7113, 

ДСТУ

 I

ЕС

 60079-15. 

GYJ14.1406X conforms to GB3836.1, GB3836.8. 
TÜV Certificate No. C-IS-236198-04, SIL 2 / SIL 3 conforms to IEC61508:2010 Ed.2. 
TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 
DNV Type Approval Certificate No.A-13625 and KR No.MIL20769-EL002 Certificates for maritime applications. 

Mounting:

 T35 DIN-Rail according to EN50022 or on customized Termination Board. 

Weight:

 about 165 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4. 

Protection class:

 IP 20. 

Dimensions: 

Width 22.5 mm, Depth 123 mm, Height 120 mm. 

General Description:

 The single channel Relay Output, D5291S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 

for high risk industries. It provides isolation between input and output contacts. 
Two mutually exclusive (by DIP-Switch programming) monitoring circuits are provided: 
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, 
  executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering. 
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold. 
D5291S provides 1 SPDT contact for two different safety functions: 
1) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state) is available at Terminal Blocks 13-14. The driving signal is normally low (0 Vdc), 
  the relay is normally de-energized, contact is open and load is de-energized. The safety function is met when the driving signal is high (24 Vdc), the relay is energized, 
  contact is closed and load is energized. At Terminal Blocks 13-15 is also available a service contact (for service load) with opposite (not SIL) function. 
2) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state) is available at Terminal Blocks 13-15. The driving signal is normally high (24 Vdc), 
  the relay is normally energized, contact is open and load is de-energized. The safety function is met when the driving signal is low (0 Vdc), the relay is de-energized, 
  contact is closed and load is energized. At Terminal Blocks 13-14 is also available a service contact (for service load) with opposite (not SIL) function. 
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2. 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

3

Resistive 

Load

4 5

10

250

FSM

SIL 3

Содержание D5291S

Страница 1: ...Module for ND Load with ND or NE Relay condition G M International ISM0112 10 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition DIN Rail and Termination Board Model D5291S D529...

Страница 2: ...te No A 13625 and KR No MIL20769 EL002 Certificates for maritime applications Mounting T35 DIN Rail according to EN50022 or on customized Termination Board Weight about 165 g Connection by polarized p...

Страница 3: ...state 2 SIL 3 for ND load energized in fail safe state with NE relay condition de energized in fail safe state 16 A inrush current at 24 Vdc 250 Vac Line input monitoring in field DIP Switch selectabl...

Страница 4: ...nergized in fail safe state is available at terminal blocks 13 15 In this case the Safety Function is met when the relay is de energized closed contact SIL3 Safety Function for ND load energized in fa...

Страница 5: ...defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor...

Страница 6: ...e defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure no...

Страница 7: ...t 99 of all possible Dangerous Undetected failures in the relay module Warning Operation D5291S relay module is suitable for the switching of safety related circuits providing isolation between the in...

Страница 8: ...proof relays dip1 relay1 dip3 relay2 dip5 relay3 1 2 3 4 5 6 7 8 ON ON OFF ON OFF ON OFF ON ON Please see next page for testing procedure at T proof WARNING after T proof test dip switch 1 3 5 must be...

Отзывы: