GMI D5263S Скачать руководство пользователя страница 4

 

D5263 

- SIL 2 Load Cell/Strain Gauge Bridge Isolating Repeater 

G.M. International ISM0227-8 

Parameters Table 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5263 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
Check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

 

Must 

 be 

Hazardous Area/Hazardous 

Locations Device Parameters 

D5263 Associated 

Apparatus Parameters 

D5263 Terminals 

Function Diagram 

HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC 

SAFE AREA, ZONE 2 GROUP IIC T4 

Uo / Voc = 7.2 V 

Ui / Vmax 

 

13 - 14 - 15 - 16 - 17 - 18 

Io / Isc = 177 mA

 

Ii / Imax 

 

Po / Po = 471 mW 

Pi / Pi 

 

Must 

 be 

Hazardous Area/Hazardous 

Locations Device Parameters 

D5263 Associated 

Apparatus Parameters Cenelec (US) 

D5263 Terminals 

IIC (A,B) 

Co / Ca = 0.3 

µ

Ci / Ci  C cable 

 

13 - 14 - 15 - 16 - 17 - 18 

IIB (C) 

Co / Ca = 1.5 

µ

IIA (D) 

Co / Ca = 2.2 

µ

Co / Ca = 2.8 

µ

IIIC (E, F, G) 

Co / Ca = 1.5 

µ

IIC (A,B) 

13 - 14 - 15 - 16 - 17 - 18 

IIB (C) 
IIA (D) 

IIIC (E, F, G) 

Lo / La = 0.5 mH 
Lo / La = 6.5 mH 
Lo / La = 9.5 mH 

Lo / La = 13 mH 

Lo / La = 6.5 mH 

Characteristic: trapezoidal. 
 
If the cable parameters are unknown, the following values may be used: capacitance 200 pF per meter (60 pF per foot), inductance 1 µH per meter (0.20 µH per foot). 

13 - 14 - 15 - 16 - 17 - 18 

13 - 14 - 15 - 16 - 17 - 18 

Li / Li L cable 

 

Up to 10 load cells 1000 

 in parallel 

Up to 4 load cells 350 

 in parallel 

Up to 5 load cells 450 

 in parallel 

13

14

9 +

10 -

1

Supply 24 Vdc

15

16

17

18

=

=

2

3

4

5

Weighting Indicator

=

=

=

6

+EXC

+Sense

-Sense

-EXC

+IN

-IN

Out 1

+Sense

+EXC

-Sense

-EXC

+IN

-IN

Load cell

In 1

MODEL D5263S

+

-

Power Bus 

SIL 2

Содержание D5263S

Страница 1: ...263 SIL 2 Load Cell Strain Gauge Bridge Isolating Repeater G M International ISM0227 8 SIL 2 Load Cell Strain Gauge Bridge Isolating Repeater DIN Rail and Power Bus Model D5263S D5263S INSTRUCTION MANUAL ...

Страница 2: ...esistance compensation 10 Ω Output Same as Input signal Output impedance 500 Ω typical Excitation voltage 4 0 V typical 15 V maximum Externally applied Transfer characteristic linear based on mV input Response time 100 ms 10 to 90 step change Performance Ref Conditions 24 V supply 23 1 C ambient temperature Calibration accuracy after system calibration 0 003 of full scale of input range Linearity ...

Страница 3: ... to the instruments associated with the barrier 20 16 15 19 18 14 17 13 1 2 3 4 D5263 5 6 7 8 9 10 11 12 PWR SIL 2 13 14 15 16 4 3 2 1 8 7 6 5 12 11 10 9 17 18 19 20 Front Panel and Features Terminal block connections Ordering Information Model D5263S Power Bus and DIN Rail accessories Connector JDFT050 Cover and fix MCHP196 Terminal block male MOR017 Terminal block female MOR022 HAZARDOUS AREA SA...

Страница 4: ...rs D5263 Associated Apparatus Parameters D5263 Terminals Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 Uo Voc 7 2 V Ui Vmax 13 14 15 16 17 18 Io Isc 177 mA Ii Imax Po Po 471 mW Pi Pi Must be Hazardous Area Hazardous Locations Device Parameters D5263 Associated Apparatus Parameters Cenelec US D5263 Terminals IIC A B Co Ca 0 3 µF Ci Ci device C cable 13 14 15...

Страница 5: ...t shall be installed in an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC 60079 0 The enclosure must have a door or cover accessible only by the use of a tool The end user is responsible to ensure that the operating temperature of the module is not exceeded in the end use application Units must be protected against dirt dust extreme mechanical e g vibration imp...

Отзывы: