- SIL 3 Loop Powered 24 to 220 Vac /Vdc Switch Repeater Transistor Out 

G.M. International ISM0175-7 

General Description:

 

The single and dual channel 24 to 220 Vac/Vdc Loop powered Switch Repeater D5093S and D5093D modules are units suitable for applications requiring SIL 3 level (according to  
IEC 61508:2010 Ed.2) in safety related systems for high risk industries. Each channel is able to reflect the presence of a 24 to 220 Vac/Vdc input signal to the output by closing an 
optically coupled NO open-drain transistor (solid-state relay, MOSFET output). The presence of the  24 to 220 Vac/Vdc input signal is also indicated by a yellow LED on the front panel. 
The input switching voltage levels are selected, according to the applied input signal, by means of an internal dip-switch. 
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2. 

 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010 part 1  

clauses 5-6 for safety related systems up to and included SIL3. 

 

  

Technical Data 

Characteristics 

Loop Input: 

loop powered control signal. 

Loop Supply:

 

24 to 220 Vac/Vdc nominal (18 to 250 Vac/Vdc), 50 mA fuse internally protected.  

Current consumption:

 3 mA/channel @ 250 Vac/Vdc nominal input. 

Power consumption:

 0.75 W per channel with 250 Vac/Vdc input signal.  

Isolation (Test Voltage):

 

In/Out 1.5 KV; In/In 500 V; Out /Out 500 V. 

Input switching voltage levels:

 

ON 

 22 Vac/Vdc, OFF 

 17 Vac/Vdc for 24 Vac/Vdc typical input 

ON 

 40 Vac/Vdc, OFF 

 30 Vac/Vdc for 48 Vac/Vdc typical input 

ON 

 50 Vac/Vdc, OFF 

 40 Vac/Vdc for 60 Vac/Vdc typical input 

ON 

 100 Vac/Vdc, OFF 

 80 Vac/Vdc for 120 Vac/Vdc typical input 

ON 

 200 Vac/Vdc, OFF 

 165 Vac/Vdc for 220 Vac/Vdc typical input 

threshold level selection by means of internal dip-switch. 

Output:

 

voltage free SPST optocoupled open-drain transistor (solid-state relay,  

MOSFET output). 

Open-collector rating: 

50 mA at 35 Vdc (

 1 Vdc voltage drop). 

Leakage current: 

 10 µA at 35 Vdc. 

Response time: 

 75 ms. 

Frequency response: 

10 Hz maximum. 

Compatibility:

 

 
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Max altitude:

 2000 m a.s.l. 

Storage:

 

temperature limits – 45 to + 80 °C. 

Safety Description:

 

ATEX:

 II 3G Ex nA IIC T4 Gc 

IECEx:

 Ex nA IIC T4 Gc 

UKR TR n. 898:

 2ExnAIICT4 X. 

Approvals: 

BVS 10 ATEX E 114 X conforms to EN60079-15, EN60079-0. 
IECEx BVS 10.0072X conforms to IEC60079-15, IEC60079-0. 
UL & C-UL E222308 conforms to UL 61010-1, UL 121201 for UL 
and CAN/CSA C22.2 No. 61010-1-12, CSA C22.2 No. 213-17 for C-UL. 
C

Ц

 16.0036 X conforms to 

ДСТУ

 7113, 

ДСТУ

 I

ЕС

 60079-15. 

TÜV Certificate No. C-IS-224248-01 SIL 3 conforms to IEC61508:2010 Ed. 2. 
TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 
DNV No.A-13625 and KR No.MIL20769-EL002 for maritime applications. 

Mounting:

 

T35 DIN-Rail according to EN50022, or on customized Termination Board. 

Weight:

 about 135 g D5093D, 110 g D5093S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4. 

Protection class:

 IP 20. 

Dimensions: 

Width 12.5 mm, Depth 123 mm, Height 120 mm. 

FSM

SIL 3

Содержание D5093S

Страница 1: ...to 220 Vac Vdc Switch Repeater Transistor Out G M International ISM0175 7 SIL 3 Loop Powered 24 to 220 Vac Vdc Switch Repeater Transistor Out DIN Rail and Termination Board Models D5093S D5093D D5093...

Страница 2: ...40 Vac Vdc for 60 Vac Vdc typical input ON 100 Vac Vdc OFF 80 Vac Vdc for 120 Vac Vdc typical input ON 200 Vac Vdc OFF 165 Vac Vdc for 220 Vac Vdc typical input threshold level selection by means of...

Страница 3: ...000 6 4 EN61326 1 EN61326 3 1 for safety system ATEX IECEx UL C UL UKR TR n 898 T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications Hi...

Страница 4: ...SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 MODEL D5093D 1 2 Out 1 SIL 3 10 7 8 Termination board connector 3 4 Out 2 SIL 3 9 In 1 24 220 Vac In 2...

Страница 5: ...part failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness When calculating the SFF this failure mode is not taken into ac...

Страница 6: ...off Once the lower threshold voltage is reached the following two possible fault situations can happen 1 if the status LED has been turned off but a low value voltage is still measured between the out...

Страница 7: ...the module is not exceeded in the end use application Units must be protected against dirt dust extreme mechanical e g vibration impact and shock and thermal stress and casual contacts If enclosure ne...

Отзывы: