6
D5072-087
- SIL 2 Resistance Isolating Repeater
G.M. International ISM0178-5
D5072-087 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN/IEC60715 TH 35 DIN
-
Rail located in Safe Area or Zone 2, Group IIC, Temperature T4
Hazardous Area (according to EN/IEC60079
-
15) within the specified operating temperature limits Tamb
-
40 to +70 °C, and connected to equipment with a maximum limit for AC power
supply Um of 250 Vrms or Vdc.
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D5072-087 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/
IEC60079
-
14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules,
particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De
-
energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Warning
Operation
Each input channel of Resistance Isolating Repeater D5072-087 accepts a 2-3-4 wire RTD (D5072S-087) or 2-3 wire RTD (D5072D-087) temperature or transmitting potentiometer
sensor, located in Hazardous Area, and repeats, with isolation, the signal to drive a Safe Area load. Presence of supply power is displayed by a “POWER ON” green signaling LED.
Burnout condition is signaled by red front panel LED for each channel. D5072D-087 module has double input and output channel, and can also be programmed to interface a single input
and obtain dual output channel (duplicator) or configurable output channel (outputs can repeat the corresponding inputs).
Installation
D5072-087 series are Resistance Isolating Repeater housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus.
D5072-087 unit can be mounted with any orientation over the entire ambient temperature range.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without
suffering or causing any damage
(for Zone 2 installations check the area to be nonhazardous before servicing)
. Connect only one individual conductor per each clamping point, use
conductors up to 2.5 mm
2
and a torque value of 0.5-0.6 Nm. Use only cables that are suitable for a temperature of at least 85°C.
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections.
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other
and do not produce any unintentional connection.
The enclosure provides, according to EN60529, an IP20 minimum degree of protection (or similar to NEMA Standard 250 type 1). The unit shall be installed in an area of not more than
pollution degree 2 according to EN/IEC60664-1. For hazardous location, the unit shall be installed in a certified Ex enclosure with a minimum ingress protection of at least IP54 in
accordance with EN/IEC60079-15, that must have a door or cover accessible only by the use of a tool.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a
cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5072-087 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized modification must be avoided.
According to EN61010, D5072-087 series must be connected to SELV or SELV-E supplies.
All circuits connected to D5072-0 unit must comply with the overvoltage category II (or better) according to EN/IEC60664-1.
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
=
=
=
MODEL D5072D-087 (Duplicator)
Ohm
+
-
Fault and Power Bus
Out 1
F
2-3 wires
RTD / Resistance
2 wires
poten.
In 1
2-3 wires
9
7
8
Ohm
Ohm
Ohm
=
=
=
1 +
2 -
5 -
3 +
4 -
6 -
Out 2
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed
wires that could touch each other causing dangerous unwanted shorts.
Check that the module has been correctly configured through SWC5090 software. For details please see SWC5090 manual ISM0154.
Turn on power, the “power on” green led must be lit, output must be in accordance with the corresponding input signal value. If possible change the sensor condition and check the
corresponding Safe Area output.