GMI D1180D Скачать руководство пользователя страница 2

 

D1180 

- Flammable Liquid Presence Detector Interface Relay Output 

G.M. International ISM0057-9 

General Description:

 The Flammable Liquid Presence Detector Interface type D1180D is a DIN Rail unit configurable with two isolated independent channels. 

The unit can be configured for NPN or PNP transistor type input, NO or NC and for NE or ND SPDT relay output. 
Each channel enables a Safe Area load to be controlled by 3 wires opto-electronic sensors or 3 wires proximity sensors located in Hazardous Area. 

Function:

 2 channels I.S. flammable liquid presence detector interface or 3 wires proximity sensor. Provides 3 port isolation (input/output/supply). 

Signalling LEDs:

 Power supply indication (green), output status (yellow). 

Field Configurability:

 NO/NC input for sensor transistor input, NE/ND relay operation, switching current levels. 

EMC: 

Fully compliant with CE marking applicable requirements. 

Supply:

 

115-230 Vac, 50-60 Hz nom (85 to 264 Vac, 48 to 400 Hz) or 100 to 350 Vdc, ripple within voltage limits 

 10 Vpp. Limit supply voltage to 250 Vrms for Instrinsic Safety applications. 

Current consumption @ 115 Vac: 

30 mA with short input and relays energized. 

Current consumption @ 230 Vac: 

20 mA with short input and relays energized. 

Max. power consumption: 

at 264 Vac supply voltage, short circuit input and relays energized, 2.2 W. 

Isolation (Test Voltage):

 I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; I.S. In/I.S. In 500 V; Out/Supply 2.5 KV; Out/Out 2.5 KV. 

Input switching current levels:

 DIP switch settable at 

 8.0, 11.0, 14.0, 17.0 mA trip point. Sensor supply current range is 0 to 5, 3 to 8, 6 to 11, 

9 to 14 mA, switching current 

 8.0 mA ± 0.5 mA hysteresis. 

Input equivalent source: 

13.0 V 150 

 typical (13 V no load, 25 mA short circuit limited current). 

Output: 

voltage free SPDT relay contact. 

Contact material: 

AgCdO. 

Contact rating: 

2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). 

DC Load breaking capacity: 

Mechanical / Electrical life: 

30 * 10

6

 / 1 * 10

5

 operation, typical. 

Operate / Release time: 

7 / 3 ms typical. 

Bounce time NO / NC contact: 

3 / 5 ms. 

Response time: 

20 ms. 

Frequency response: 

10 Hz maximum. 

Compatibility: 

 

CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive. 

Environmental conditions: 

Operating: 

temperature limits -20 to + 60 °C, relative humidity max 95 %. 

Storage: 

temperature limits – 45 to + 80 °C. 

Safety Description: 

II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus. 
Uo/Voc = 15.8 V, Io/Isc = 109 mA, Po/Po = 428 mW at terminals 13-16, 9-12. 
Uo/Voc = 15.8 V, Io/Isc = 13 mA, Po/Po = 51 mW at terminals 14-16, 13-15, 10-12, 9-11. 
Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11, 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, 
Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X, 
KR Type Approval Certificate for marine applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight:

 

about 160 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 Safe Area installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

Characteristics 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

5

Resistive 

Load

Содержание D1180D

Страница 1: ...D1180 Flammable Liquid Presence Detector Interface Relay Output ISM0057 9 D1180D INSTRUCTION MANUAL Flammable Liquid Presence Detector Interface Relay Output DIN Rail Model D1180D...

Страница 2: ...witching current 8 0 mA 0 5 mA hysteresis Input equivalent source 13 0 V 150 typical 13 V no load 25 mA short circuit limited current Output voltage free SPDT relay contact Contact material AgCdO Cont...

Страница 3: ...liability SMD components High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated wi...

Страница 4: ...Ch2 13 16 9 12 Io Isc 13 mA Ch1 Ch2 14 16 13 15 10 12 9 11 Po Po 428 mW Ch1 Ch2 13 16 9 12 Po Po 51 mW Ch1 Ch2 14 16 13 15 10 12 9 11 Ii Imax Pi Pi D1180 Associated Apparatus Parameters Ci Ci device...

Страница 5: ...International ISM0057 9 Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA MODEL D1180D 8 NC 2 NO 1 COM Out 1 7 NC 6 NO 5 COM Out 2 13 14 15 In 1 3 wire Sensor 16 3 wire Sensor 9 10 1...

Страница 6: ...ment 7 6 5 12 Intrinsically Safe Equipment 11 10 9 D1180 is an AC supply liquid presence detector interfaces housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN5002...

Страница 7: ...figuration 1 2 3 4 ON Switch positions Trip Current Level Ch2 Ch1 A configuration DIP Switch is located on component side of pcb This switch allows the configuration of input output relationship and t...

Отзывы: