GMI D1180D Скачать руководство пользователя страница 1

D1180 

- Flammable Liquid Presence Detector Interface Relay Output 

ISM0057-9 

D1180D 

INSTRUCTION MANUAL 

Flammable Liquid Presence Detector 

Interface Relay Output 

DIN-Rail Model D1180D 

Содержание D1180D

Страница 1: ...D1180 Flammable Liquid Presence Detector Interface Relay Output ISM0057 9 D1180D INSTRUCTION MANUAL Flammable Liquid Presence Detector Interface Relay Output DIN Rail Model D1180D...

Страница 2: ...witching current 8 0 mA 0 5 mA hysteresis Input equivalent source 13 0 V 150 typical 13 V no load 25 mA short circuit limited current Output voltage free SPDT relay contact Contact material AgCdO Cont...

Страница 3: ...liability SMD components High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated wi...

Страница 4: ...Ch2 13 16 9 12 Io Isc 13 mA Ch1 Ch2 14 16 13 15 10 12 9 11 Po Po 428 mW Ch1 Ch2 13 16 9 12 Po Po 51 mW Ch1 Ch2 14 16 13 15 10 12 9 11 Ii Imax Pi Pi D1180 Associated Apparatus Parameters Ci Ci device...

Страница 5: ...International ISM0057 9 Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA MODEL D1180D 8 NC 2 NO 1 COM Out 1 7 NC 6 NO 5 COM Out 2 13 14 15 In 1 3 wire Sensor 16 3 wire Sensor 9 10 1...

Страница 6: ...ment 7 6 5 12 Intrinsically Safe Equipment 11 10 9 D1180 is an AC supply liquid presence detector interfaces housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN5002...

Страница 7: ...figuration 1 2 3 4 ON Switch positions Trip Current Level Ch2 Ch1 A configuration DIP Switch is located on component side of pcb This switch allows the configuration of input output relationship and t...