background image

 

D1080 

- Flammable Liquid Presence Detector Interface Relay Output 

G.M. International ISM0055-9 

Parameters Table 

Must 

be 

Hazardous Area 

Device Parameters 

D1080 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area 

Cable Parameters 

Uo / Voc = 15.8 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the 
Hazardous Area and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, 
Po/Po) of the D1080 Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that added connecting cable and field device 
capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas group. See parameters on

 

enclosure side 

and the ones indicated in the table below: 

D1080 Terminals 

Ch1 

Ch2 

13 - 16 

9 - 12 

Uo / Voc = 15.8 V 

Ch1 

Ch2 

14 - 16, 13 - 15 

10 - 12, 9 - 11 

Io / Isc = 109 mA 

Ch1 

Ch2 

13 - 16 

9 - 12 

Io / Isc = 13 mA 

Ch1 

Ch2 

14 - 16, 13 - 15 

10 - 12, 9 - 11 

Po / Po = 428 mW 

Ch1 

Ch2 

13 - 16 

9 - 12 

Po / Po = 51 mW 

Ch1 

Ch2 

14 - 16, 13 - 15 

10 - 12, 9 - 11 

 

Ii/ Imax 

 

Pi / Pi 

 

D1080 Associated 

Apparatus Parameters 

Ci / Ci  C cable 

 

Li / Li L cable 

 

Li / Ri device and 

L cable / R cable 

 

(II-A, B) 

Co / Ca = 478 nF 

Co / Ca = 2.88 µF 
Co / Ca = 11.6 µF 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Co / Ca = 478 nF 

Co / Ca = 2.88 µF 
Co / Ca = 11.6 µF 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / La = 3 mH 

Lo / La = 12 mH 
Lo / La = 24 mH 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / La = 217.6 mH 
Lo / La = 870.7 mH 

Lo / La = 1741 mH 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / Ro = 83 µH/

 

Lo / Ro = 332 µH/

 

Lo / Ro = 664 µH/

 

(IIB-C) 
(IIA-D) 

(IIC-A, B) 

Lo / Ro = 706 µH/

 

Lo / Ro = 2820 µH/

 

Lo / Ro = 5650 µH/

 

(IIB-C) 
(IIA-D) 

 

D1080 Terminals 

Ch1 

Ch2 

13 - 16 

9 - 12 

Ch1 

Ch2 

14 - 16, 13 - 15 

10 - 12, 9 - 11 

Ch1 

Ch2 

13 - 16 

9 - 12 

Ch1 

Ch2 

14 - 16, 13 - 15 

10 - 12, 9 - 11 

Ch1 

Ch2 

13 - 16 

9 - 12 

Ch1 

Ch2 

14 - 16, 13 - 15 

10 - 12, 9 - 11 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 

Содержание D1080D

Страница 1: ...D1080 Flammable Liquid Presence Detector Interface Relay Output ISM0055 9 D1080D INSTRUCTION MANUAL Flammable Liquid Presence Detector Interface Relay Output DIN Rail Model D1080D ...

Страница 2: ...d electrical apparatus Uo Voc 15 8 V Io Isc 109 mA Po Po 428 mW at terminals 13 16 9 12 Uo Voc 15 8 V Io Isc 13 mA Po Po 51 mW at terminals 14 16 13 15 10 12 9 11 Um 250 Vrms 20 C Ta 60 C Approvals DMT 01 ATEX E 042 X conforms to EN60079 0 EN60079 11 EN60079 26 EN61241 0 EN61241 11 IECEx BVS 07 0027X conforms to IEC60079 0 IEC60079 11 IEC60079 26 IEC61241 0 IEC61241 11 Russia according to GOST 12 ...

Страница 3: ...MD components High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Input Ch 2 for 3 wire Sensor Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for 3 wire Sensor Collector Input Ch 2 for 3 wire Sensor Emitter Input Ch 2 for 3 wire Sensor Input Ch 1...

Страница 4: ... 9 12 Io Isc 13 mA Ch1 Ch2 14 16 13 15 10 12 9 11 Po Po 428 mW Ch1 Ch2 13 16 9 12 Po Po 51 mW Ch1 Ch2 14 16 13 15 10 12 9 11 Ii Imax Pi Pi D1080 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable II A B Co Ca 478 nF Co Ca 2 88 µF Co Ca 11 6 µF IIB C IIA D IIC A B Co Ca 478 nF Co Ca 2 88 µF Co Ca 11 6 µF IIB C IIA D IIC A B Lo La 3 mH Lo La 12...

Страница 5: ...tput G M International ISM0055 9 Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA MODEL D1080D 3 4 8 NC 2 NO 1 COM Supply 24 Vdc Out 1 7 NC 6 NO 5 COM Out 2 13 14 15 In 1 3 wire Sensor 16 3 wire Sensor 9 10 11 In 2 3 wire Sensor 12 3 wire Sensor ...

Страница 6: ...more than 250 Vrms or Vdc Control Equipment Safe Area 13 14 1 2 Power Supply 3 4 16 15 8 Control Equipment 7 6 5 12 Intrinsically Safe Equipment 11 10 9 Installation D1080 is a liquid presence detector interfaces housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022 D1080 unit can be mounted with any orientation over the entire ambient temperature range see s...

Страница 7: ...nfiguration 1 2 3 4 ON Switch positions Trip Current Level Ch2 Ch1 A configuration DIP Switch is located on component side of pcb This switch allows the configuration of input output relationship and the trip current levels Channel IN OUT Operation NO ND or NC NE NO NE or NC ND Dip switch Configuration Summary Table 1 SW1 OFF ON 2 SW2 OFF ON Trip Current Level 8 mA Sensor 0 to 5 mA 11 mA Sensor 3 ...

Отзывы: