D5290S-079 

- 5 A SIL 3 Relay Output Module (115 Vac coil voltage) 

G.M. International ISM0153-2 

 

 

 

Technical Data 

Characteristics 

Input: 

115 Vac nom (95 to 130 Vac). 

Current consumption @ 115 Vac:

 25 mA with relay energized, typical. 

Power dissipation:

 2.5 W with 115 Vac input voltage, relay energized, typical. 

Isolation (Test Voltage): 

Input / All Outputs: 2.5 KV; Out S_1 & Out P_1 / Out S_3 & Out P_2, Out S_2, Out S_4: 500 V; 

                                      Out S_3 & Out P_2 / Out S_2, Out S_4: 500 V; Out S_2 / Out S_4: 500 V. 

Output:

 2 voltage free SPDT (= NO c parallel of 2 NC contacts) relay contacts identified with outputs: Out S_1 & Out P_1 and Out S_3 & Out P_2; 

 

2 voltage free SPST (NO) relay contacts identified with: Out S_2 and Out S_4. 

Terminals 13-14 (Out S_1), 15-16 (Out S_2), 21-22 (Out S_4) and 23-24 (Out S_3) are: open when relay is de-energized, closed in energized relay condition. 
Terminals 17-18 (Out P_1) and 19-20 (Out P_2) are: closed when relay is de-energized, open in energized relay condition. 

Contact material: 

Ag Alloy (Cd free). 

Contact rating: 

5 A 250 Vac 1250 VA, 5 A 250 Vdc 175 W (resistive load). 

DC Load breaking capacity: 

Mechanical / Electrical life: 

10 * 10

6

 / 5 * 10

4

 operation, typical. 

Bounce time NO / NC contact: 

4 / 10 ms, typical. 

Frequency response: 

10 Hz maximum.

 

Compatibility: 

CE mark compliant, conforms to 94/9/EC Atex Directive and to  
2004/108/CE EMC Directive.

 

Environmental conditions: 

Operating:

 temperature limits - 40 to + 60 °C, relative humidity 95 %, up to 55 °C. 

Storage:

 temperature limits - 45 to + 80 °C. 

Approvals:

 

TÜV Certificate No. C-IS-224248-01, SIL 2 / SIL 3 conforms to IEC61508:2010. 

Mounting:

 

T35 DIN-Rail according to EN50022. 

Weight:

 about 145 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 Safe Area / Non Hazardous Location. 

Protection class:

 IP 20. 

Dimensions: 

Width 22.5 mm, Depth 123 mm, Height 120 mm. 

General Description: 

The D5290S-079 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508 for high risk industries. 
It provides isolation between input channel and output contacts. 
The input channel requires 115 Vac voltage signal to drive the relay coils. 
 
See the following pages for Functional Safety applications with related SIL value. 
 
Mounting on standard DIN-Rail in Safe Area. 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

3

Resistive

Load

4 5

250

Содержание D5290S-079

Страница 1: ... 3 Relay Output Module 115 Vac coil voltage G M International ISM0153 2 5 A SIL 3 Relay Output Module for NE or ND Loads with NE Relay condition DIN Rail Model D5290S 079 D5290S 079 INSTRUCTION MANUAL INSTRUCTION MANUAL ...

Страница 2: ... Mechanical Electrical life 10 106 5 104 operation typical Bounce time NO NC contact 4 10 ms typical Frequency response 10 Hz maximum Compatibility CE mark compliant conforms to 94 9 EC Atex Directive and to 2004 108 CE EMC Directive Environmental conditions Operating temperature limits 40 to 60 C relative humidity 95 up to 55 C Storage temperature limits 45 to 80 C Approvals TÜV Certificate No C ...

Страница 3: ...n 3 5 A SIL 3 SIL 2 contacts for NE or ND loads with NE Relay condition Input Output isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system TÜV Certification Simplified installation using standard DIN Rail and plug in terminal blocks Model D5290S 079 DIN Rail accessories Cover and fix MCHP196 Normally Open NO contact Out S_1 Terminal block connections SAFE A...

Страница 4: ...ding to the relay breaking capacity diagram Relay contacts shown in de energized position Terminals 13 14 15 16 21 22 and 23 24 are open Terminals 17 18 and 19 20 are closed See the following pages for Functional Safety applications with related SIL value MODEL D5290S 079 1 2 3 4 22 21 19 20 23 24 Out S_1 NO contact 13 14 Out P_1 NC contact 17 18 16 15 Out S_2 NO contact Out S_4 NO contact Out P_2...

Страница 5: ...e output load being de energized fail Safe this failure causes the system to go to the defined fail safe state without a process demand fail Dangerous failure mode that does not respond to a demand from the process i e being unable to go to the defined fail safe state so that the output load remains energized In addition there are other definitions of failure behaviours which are not safety relate...

Страница 6: ...operating in Low Demand mode as a Type A module having Hardware Fault Tolerance HFT 0 In the 2nd Functional Safety application the normal state operation of relay module is energized with NE Normally Energized loads In case of alarm or request from process the relay module is de energized safe state de energizing loads The failure behaviour of relay module is described by the following definitions...

Страница 7: ...ailure behavior D5290S 079 is considered to be operating in Low Demand mode as a Type A module having Hardware Fault Tolerance HFT 0 In the 3rd Functional Safety application the normal state operation of relay module is energized with NE Normally Energized loads In case of alarm or request from process the relay module is de energized safe state de energizing loads The failure behaviour of relay m...

Страница 8: ...g Hardware Fault Tolerance HFT 0 In the 4th Functional Safety application the normal state operation of relay module is energized with ND Normally De energized loads In case of alarm or request from process the relay module is de energized safe state energizing loads The failure behaviour of all relay modules here considered is described by the following definitions fail Safe State it is defined a...

Страница 9: ...gize main power source turn off power supply voltage and disconnect plug in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential Start up Before powering the inputs of unit check that all wires are properly connected Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts Enabling input the RELAY ...

Отзывы: