background image

D1030 

- Switch / Proximity Detector Repeater Relay Output 

ISM0008-10 

D1030S - D1030D 

INSTRUCTION MANUAL

INSTRUCTION MANUAL

 

 

Switch/Proximity Detector 

Repeater Relay Output 

DIN-Rail Models D1030S, D1030D 

Содержание D1030D

Страница 1: ...D1030 Switch Proximity Detector Repeater Relay Output ISM0008 10 D1030S D1030D INSTRUCTION MANUAL INSTRUCTION MANUAL Switch Proximity Detector Repeater Relay Output DIN Rail Models D1030S D1030D ...

Страница 2: ...t circuit input and relays energized 1 8 W for 2 channels D1030D 1 7 W for 1 channel D1030S Isolation Test Voltage I S In Out 1 5 KV I S In Supply 1 5 KV Out Supply 1 5 KV Out Out 1 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual c...

Страница 3: ...ection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High Density two channels per unit Simplified installation using standard DIN Rail an...

Страница 4: ...put Ch 1 Relay Normally Opened NO 2 Power Supply 24 Vdc 3 Power Supply 24 Vdc 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1030S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A Co...

Страница 5: ...pparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB C IIA D IIC A B Lo La 172 mH Lo La 689 mH Lo La 1379 mH IIB C IIA D IIC A B Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to G...

Страница 6: ...L D1030S 13 14 3 4 8 NC 2 NO 1 COM Supply 24 Vdc Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free Contact Proximity Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC HAZARDOUS LOCATIONS CLASS I DIVISION 1 GROUPS A B C D CLASS II DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Cod...

Страница 7: ... or fault condition of sensor and connecting line are displayed by signaling LEDs green for power yellow for status and red for fault condition D1030D dual channel type has two independent input channels and actuates the corresponding output relay SPDT contact two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally energized relayor Normal...

Страница 8: ... requires an additional enclosure with higher degree of protection i e IP54 to IP65 or NEMA type 12 13 consistent with the effective operating environment of the specific installation Units must be protected against dirt dust extreme mechanical e g vibration impact and shock and thermal stress and casual contacts If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of d...

Страница 9: ...etection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON 1 OFF 4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC N...

Страница 10: ...led proximity sensor or contact with terminating line resistor Out B Out A 1 2 8 5 6 7 Out A 1 2 8 Out B 5 6 7 No Fault 5 6 7 5 6 7 NE NE NE ND ND NE No Fault D1030D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resisto...