 [1] Installers should be members of an appropriate Competent Persons Scheme. [2] All installations in England and Wales must be 

notified to Local Area Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance 
Certificate will then be issued to the customer. [3] May be required for systems covered by G3 Regulations

© Heating and Hotwater Industry Council (HHIC) 

www.centralheating.co.uk 

AIR TO WATER HEAT PUMP COMMISSIONING CHECKLIST

This Commissioning Checklist is to be completed in full by the competent person who commissioned the heat pump and associated equipment as a means of 
demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.  

Failure to install and commission this equipment to the manufacturer’s instructions will invalidate the warranty but does not affect statutory rights.

Customer Name   

Address  

 

Telephone Number 

Heat Pump Make and Model 

Heat Pump Serial Number 

Commissioned by 

(print name)

 

Certified Operative Reg. No. 

[1]

Company Name & Address 

Commissioning Date

 

Telephone No.

Building Regulations Notification Number 

(if applicable)

 [2]

Commissioning Engineer’s Signature

Customer’s Signature

(To confirm demonstration of equipment and receipt of appliance instructions) 

ALL INSTALLATIONS

The heating, hot water and ventilation systems complies with the appropriate Building Regulations   

Yes

All electrical work complies with the appropriate Regulations 

 

Yes

The heat pump and associated products have been installed and commissioned in accordance with the manufacturer’s instructions 

Yes

The operation of the heat pump and system controls have been demonstrated to the customer 

 

Yes

The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer 

Yes 

CENTRAL HEATING MODE  

Heating Flow Temperature                        °C                      Heating Return Temperature                       °C

ALL SYSTEMS 

The heating system has been filled and pressure tested 

 

Yes

Expansion vessel for heating is sized, fitted & charged in accordance with manufacturer’s instructions  

Yes

The heat pump is fitted on a solid/stable surface capable of taking its weight 

 

Yes 

The system has been flushed and cleaned in accordance with BS7593 and heat pump manufacturer’s instructions 

Yes                

What system cleaner was used?

What inhibitor was used? 

                                                                               Qty                 litres

Is the system adequately frost protected? 

 

Yes

OUTDOOR UNIT 

Are all external pipeworks insulated? 

 

Yes

Is the fan free from obstacles and operational? 

  

Yes

Has suitable consideration been made for waste water discharge? 

 

Yes 

DOMESTIC HOT WATER MODE  

Measure and Record

Is the heat pump connected to a hot water cylinder?            Unvented             Vented                  Thermal Store            Not Connected

Hot water has been checked at all outlets        Yes     

Have Thermostatic Blending Valves been fitted?  

                                                    Yes         Not required

ADDITIONAL SYSTEM INFORMATON

Additional heat sources connected:       Gas Boiler            Oil Boiler              Electric Heater              Solar Thermal           Other

CONTROLS - SYSTEM AND HEAT PUMP 

Tick the appropriate boxes if applicable

1.  Time & Temperature 

Room Thermostat & 

Programmable 

Load/Weather 

Optimum Start

 

Control to Heating       

Programmer/Timer     

Roomstat     

Compensation    

Control

2.  Time & Temperature 

 

 

Cylinder Thermostat & 

Combined with Heat

 

Control to Hot Water  

 

 

Programmer/Timer        

pump main controls

3.  Heating Zone Valves (including underfloor loops) 

 

Fitted   

Not Required

4.  Hot Water Zone Valves 

 

 

Fitted   

Not Required

5.  Thermostatic Radiator Valves 

 

 

Fitted   

Not Required

6.  Heat Pump Safety Interlock 

[3]

  

 

Built 

In 

 

Provided

7.  Outdoor Sensor  

 

 

Fitted   

Not Required

8.  Automatic Bypass System 

 

 

Fitted   

Not Required

9.  Buffer Vessel Fitted 

 

 

Yes 

    No          If YES,    Volume                       Litres

Содержание Envirosorb2 12

Страница 1: ...Envirosorb2 7 12 14 Installation and Servicing...

Страница 2: ......

Страница 3: ...rantee Responsibility 9 5 1 Detailed guarantee 9 5 2 Appliance use manufacturer responsibility 9 TECHNICAL DATA 6 Envirosorb 10 INSTALLATION 7 Appliance location 12 7 1 Heat pump location 12 7 2 Clear...

Страница 4: ...it 28 14 2 Activating the heat pump 28 14 3 Activating the options 28 14 4 Heating system test 28 15 Specific adjustment 28 15 1 Adjusting the heating circuit 28 15 2 Settings for the command unit 29...

Страница 5: ...th and Safety Executive in accordance with the manufacturer s recommendations We strongly recommend regular servicing of your appliance but where the condition is not met any chargeable spare parts or...

Страница 6: ...oth manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in accordance with the m...

Страница 7: ...ter temperature B Air temperature 2 4 4 Min and Max temperature settings in cooling 12 14 16 18 20 10 8 6 4 2 0 0 10 20 30 40 50 46 A B Key A Water temperature B Air temperature 2 4 5 Principle for co...

Страница 8: ...at pump circuit 10 Water flow detector for the heat pump circuit 11 Circulator for the heat pump circuit 12 Safety valve for the heat pump circuit 13 Expansion vessel in this position for the 12 and 1...

Страница 9: ...to replace hydraulic components drain the appliance Protect all the electrical components from water while working on the appliance Use only original spare parts Use only new O rings and gaskets Afte...

Страница 10: ...ured and give no known hazard in this state The refrigerant used in this appliance is R410a the use of which is strictly controlled by F Gas regulation EN842 2006 4 Recycling i The recycling of the pa...

Страница 11: ...person in accordance with installation instructions The appliance is used for normal domestic purposes and in accordance with the manufacturer s operating and maintenance instructions The appliance is...

Страница 12: ...A 8 13 2 15 6 COP A7 6 W35 30 3 91 3 91 4 06 Refrigerant circuit Type of refrigerant Quantity of refrigerant kg 1 81 2 485 3 385 Type of compressor Rotary Type of oil Polyolester Type of regulator El...

Страница 13: ...lassification 1 1 1 Description Unit 7 12 14 Dimensions Height mm 821 1363 1363 Width mm 908 908 908 Depth mm 326 326 326 Water circuit connections 1 1 1 Nett total weight kg 71 105 130 Sound power le...

Страница 14: ...e can be accessed and inspected see chapter Clearances Observe current regulations Install the appliance outside Do not install the appliance near a heat source near flammable materials near the venti...

Страница 15: ...the drawing above in order to ensure a correct air flow and to facilitate maintenance operations Make sure that the available space is su cient for the installation of the water system piping 7 3 Com...

Страница 16: ...f the connector and connect them onto terminal 4 See the chapter Installation examples Position the support 3 on a wall Drill holes for the fixing screws in accordance with the 2 fixing holes on the w...

Страница 17: ...t before installing the new appliance and to add an anti sludge filter If a component of the system is not to be installed immediately protect the various connections so plaster and paint cannot compr...

Страница 18: ...2 3 4 5 6 7 132 27 132 9 4 Mounting 9 4 1 Unpacking the appliance Carefully remove the packaging and protections without damaging the parts of the appliance 1 1 2 3 Key 1 Transport pallet 2 Attachmen...

Страница 19: ...table handling equipment If you move the appliance with a two wheeled trolley respect the following regulations Only lift the appliance from the back Attach the appliance to the two wheeled trolley wi...

Страница 20: ...0020117819_01 05 11 Glow worm 18 10 Examples of installation 10 1 Installation with hydraulic module control by control unit A B H E F 230V 230V L5 1 6 2 4 5 3 1 4 2 3 INSTALLATION...

Страница 21: ...ature 24 46 C 40 C 123 Exterior temperature from which the heat pump stops in cooling mode 0 30 C 22 C 124 Minimum temperature of water in the installation in cooling mode 4 20 C 4 C 125 Maximum tempe...

Страница 22: ...020117819_01 05 11 Glow worm 20 10 2 Installation with hydraulic module DHW tank control by control unit A B H E F 230V 230V L5 230V 1 9 8 2 3 6 1 6 6 2 7 5 1 4 6 2 8 2 5 230V 3 4 6 1 R6 1 INSTALLATIO...

Страница 23: ...t 0 0 112 External calibrated adjustment graphs 7 12 8 117 External calibrated adjustment graphs for cooling 0 2 122 Maximum reference exterior temperature 24 46 C 40 C 123 Exterior temperature from w...

Страница 24: ...heat pump Connect a hose and a shut o valve to the flow heat pump connection in the direction of the building Install the filter on the heat pump return pipe Install it between 2 shut o valves in orde...

Страница 25: ...pump A 2 13 1 Access to main board B A A A C 2 1 Key 1 Terminal blocks for 230 V and 12 V connection 2 Front panel Remove the fastening screws A Slide the front panel 2 downwards B and pull it towards...

Страница 26: ...odel use the anti wrench connector supplied with the appliance 13 5 Wiring diagram 13 5 1 Command board 7kW 12kW 14kW 1FS 1T 1TR 1PS 1LWT 1EWT 1PCB Key 1PS Circulator 1LWT Flow temperature sensor for...

Страница 27: ...1 CN500 1 6 1 1 1 1 1 46CF 3 2 1 47CF 6 5 4 3 2 1 48CF 3 2 1 49CF 2 1 50CF 3 2 1 51CF 2 1 C W W R Y G O C A Y G R 1 2 3R 1TB 1 N 3 L N PE N L 230V 1 50Hz 2 10 J4 1 2 03 J3 1 2 08 J1 1 1TD 1TS 2R 1R 1F...

Страница 28: ...2C 2 3 3C 2 3 P 9 CN04 CN03 P20 P 7 P 8 CN600 4C 2 3 C 2 CN09 CN 0 CN CN30 6C 2 3 CN600 7C 2 3 4 CN300 8C 2 CN60 9C 2 CN604 60C 2 7 ERMO67A7 ORbCOMPRE66OR CN 00 2T 2 6 C 2 3 CN60 CN606 R C 6 N 3 4 b b...

Страница 29: ...F03 T10A 250V F01 T25A 250V CN201 P01 L F P02 CN202 P09 10CM 1 2 11CM 1 2 49C 1 2 L N 65CF 1 2 3 66CF 1 2 67CF 1 2 68CF 1 2 3 69CF 1 2 70CF 1 2 71CF 1 2 3 72CF 1 2 3 4 5 6 73CF 1 2 3 4 74CF 1 2 3 4 5...

Страница 30: ...he circuit breaker located on the electrical circuit box and connected to the heat pump to the ON position The main screen for the command unit is displayed See the chapter Example installation to ent...

Страница 31: ...control box connected for at least 10 seconds so that the change is properly saved Press simultaneously on the button and M for 3 seconds The parameter number is displayed and its value blinks Press...

Страница 32: ...d 13 Correction to the ambient temperature command unit position This parameter corrects the measurement of the ambient temperature following an error in positioning the command unit 5 C 5 C 0 C Yes 1...

Страница 33: ...ial functions on the appliance 0 No test 1 Force the circulator 2 Force output between terminals 5 and N code 147 3 Force output between terminals 4 and N code 106 4 Force output between terminals 11...

Страница 34: ...0 10 20 30 40 50 60 2 3 1 4 Key 1 Code 118 2 Code 119 3 Code 120 4 Code 121 A Heating flow temperature C B Exterior temperature C Code Function Description Setting Factory setting Modifiable paramete...

Страница 35: ...which the compressor has functioned since first activation No 136 Capacity of the heat pump This parameter displays the capacity of the heat pump No 137 Return temperature of the heat pump circuit Thi...

Страница 36: ...hot water demand contact S5 1 Always active demand for hot water is always met 2 Activated only in heating and cooling modes demand for hot water is met only in heating or cooling mode 1 2 1 Yes 154...

Страница 37: ...te n 10 or circulator pump n 11 sensor fault Code Description 10 Outside air temperature greater than the maximum in heating parameter 119 11 Air temperature higher than the maximum value for heating...

Страница 38: ...here are no traces of rust or oil around the cooling circuit s components Ensure that the appliance s components are neither worn nor broken Check that the wires are firmly attached to the electrical...

Страница 39: ...r Yes The manufacturer s literature including Benchmark Checklist and Service Record has been explained and left with the customer Yes CENTRAL HEATING MODE Heating Flow Temperature C Heating Return Te...

Страница 40: ...ature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Engineer Name Company Name Te...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...GLOW WORM Nottingham Road Belper Derbyshire DE56 1JT Because of our constant endeavour for improvement details may vary slightly from those shown in these instructions www glow worm co uk Subject to...

Отзывы: