Appendix
46
Installation and maintenance instructions Energy
7
0020300877_01
Setting level
Values
Unit
Increment, select, explanation
Default set-
ting
Own setting
Min.
Max.
d.27 Function of relay 1 (multi-
functional module)
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Anti-legionella pump
10 = Solar valve
1
Adjustable
d.28 Function of relay 2 (multi-
functional module)
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Anti-legionella pump
10 = Solar valve
2
Adjustable
d.31 Automatic filling device
0
2
–
0 = Manual
1 = Semi-automatic
2 = Automatic
0
Adjustable
d.33 Fan speed target value
Current value
rpm
Fan speed = Display value x 100
–
Not
adjustable
d.34 Value for the fan speed
Current value
rpm
Fan speed = Display value x 100
–
Not
adjustable
d.40 Heating flow temperature
Current value
℃
–
–
Not
adjustable
d.41 Heating return temperat-
ure
Current value
℃
–
–
Not
adjustable
d.43 Heat curve
0.2
4
–
0.1
1.2
Adjustable
d.45 Value for the base point
of the heat curve
15
30
–
1
20
Adjustable
d.47 Outdoor temperature
Current value
℃
–
–
Not
adjustable
d.50 Correction of the min-
imum fan speed
0
3000
rpm
1
Fan speed = Display value x 10
600
Adjustable
d.51 Correction of the max-
imum fan speed
-2500
0
rpm
1
Fan speed = Display value x 10
-1000
Adjustable
d.58 Solar circuit reheating
0
3
–
0 = Boiler's anti-legionella function
deactivated
3 = Domestic hot water activated (tar-
get value min. 60 °C)
0
Adjustable
d.60 Number of blocks by the
temperature sensor
Current value
–
–
–
Not
adjustable
d.61 Number of unsuccessful
ignitions
Current value
–
–
–
Not
adjustable
d.62 Night set-back
0
30
–
1
0
Adjustable
d.64 Average burner ignition
time
Current value
s
–
–
Not
adjustable
d.65 Maximum burner ignition
time
Current value
s
–
–
Not
adjustable
d.66 Activation of the warm
start function for domestic hot
water
–
–
–
off = Function deactivated
on = Function activated
1
Adjustable
d.67 Remaining burner anti-
cycling time (setting under
d.02)
Current value
min
–
–
Not
adjustable