MAINTENANCE

JUNO-NET

Programming mode is accessed via the front panel 7 key keypad or the miniature infra-red keypad (IR
Keypad) or by connecting a PC (PS2) keyboard to the Main Panel. It is also possible to upload and
download settings to a PC but to do this you must first enter the panel programming mode.

If using the front panel's keypad, the

keys will have the same function as the equivalent keys on

the IT Remote Control Keypad (or PS/2 keyboard). The OK key is equivalent to ENTER and the ESC key
will perform the same functions as the ESC key on the remote IR keypad

—˜–

INFRA-RED KEYPAD

0

A

4

E

8

I

1

B

5

F

9

J

2

C

6

G

K

3

D

7

H

L

M

N

/

[

]

.

,

'

"

+

-

:

*

&

O

P

Q

R

S

T

U

V

W

X

Y

HOME

SHIFT

ENTER

B-SP

Z

SPACE

ESC

EXIT

HOME

: Return to first loop, zone, device etc.

ENTER

: Accept current selection

B-SP

: Backspace

ESC

.: Reject. (ESCape from current selection)

EXIT

: Press both keys simultaneously to stop programming

SHIFT

: Toggle this keypad to switch from alpha-numeric

to numeric

2.9 GETTING INTO PROGRAMMING MODE

23

JUNO-NET EN-54

MAINTENANCE MANUAL

21-08-2005

REVISION 1.0

OPERATION &

ss

ss

FRONT PANEL KEYPAD

ESC

OK

Used to confirm entry of any data or selection. Same
function as the ENTER key on IR remote control.

Used to increase selection or number. Equivalent function
as UP arrow key on IR remote control.

Used to decrease selection or number. Equivalent
function as UP arrow key on IR remote control.

Escape key. Used to exit a particular function. Equivalent
function as ESC arrow key on IR remote control.

Used to increase loop number. Equivalent function as +
arrow key on IR remote control.

Used to decrease loop number. Equivalent function as -
arrow key on IR remote control.

Note:

It is not possible to introduce text for labels using

the front panel keypad.

OK

ESC

+

-

Содержание JUNO-NET EN-54

Страница 1: ...OPERATION MAINTENANCE MANUAL JUNO NET Fire Alarm Control Panel EN 54 JUNO NET EN 54 MAINTENANCE MANUAL 21 08 2005 REVISION 1 0 OPERATION ss ss...

Страница 2: ...2 8 Use of programming functions for maintenance 2 9 Getting into Programming Mode 2 10 Logbook 2 10 Event data sheet OPERATION 1 3 Reset the system 1 4 Sound and silence the alarms 1 5 Read the Fire...

Страница 3: ...icates that at least one disablement exists If the LED is GREEN it means that the panel is in ACTIVE mode If the LED is flashing GREEN then the panel is in INSTALLATION mode If the LED is AMBER it ind...

Страница 4: ...ated Press to Enable or disable all sounders on the system Both Conventional or Addressable When LED is lit all sounders are disabled Enabled if LED is off Pressing this switch disables or enables all...

Страница 5: ...TUS FIRE will remain lit RED Press the INTERNAL BUZZER SILENCE to silence the Internal Buzzer It will also turn off the INTERNAL BUZZER SILENCE button LED button LED At the fire control panel the STAT...

Страница 6: ...ILENCE RESOUND All sounders turn on The illuminates RED Press the The sounders turn off The extinguishes button LED button LED ALARMS SILENCE RESOUND ALARMS SILENCE RESOUND ALARMS SILENCE RESOUND 1 4...

Страница 7: ...xt queued message Do this until all messages have been reviewed The LED stops flashing RED but remains lit once all messages have been displayed After 20 seconds the first fire event will be re displa...

Страница 8: ...08 2005 REVISION 1 0 OPERATION ss ss FIRE FAULT PRE ALARM TEST DISABLED SYSTEM ON ALARM FAULT SUPPLY FAULT SYSTEM FAULT TRANS FAULT PAPER FEED LAMP TEST SYSTEM RESET INTERNAL BUZZER SILENCE DISABLED...

Страница 9: ...1997 AC 1999 EN54 Press and hold the LAMP TEST All LEDs shown in this diagram should be illuminated All pixels on the LCD display should turn black All external Zone LEDs if fitted should be illuminat...

Страница 10: ...TH 2 1997 AC 1999 EN54 4 1997 AC 1999 EN54 OPERATION JUNO NET 1 8 PERFORM A FIRE DRILL Authorized User Level Access To start the fire drill press the The following will occur All sounders turn on The...

Страница 11: ...uired in order for the LCD display to show the described above format Press the QUEUE REVIEW TEST first then the CONTROLS LAMP TEST momentarily The FAULTS SYSTEM FAULT button button LED will light mom...

Страница 12: ...Repeater LCD displays for 15 seconds Testing More Than One Device Disablements Sensor sensitivity Other Detectors and callpoints can only be tested one at a time The LED must be extinguished on the c...

Страница 13: ...NT Re pressing the SELECTED DETECTORS button again will re enable the detectors LED LED LED button Using the programming functions see the Installation Commissioning Manual individual detectors can be...

Страница 14: ...n to re enable the relays and I O modules button LED LED The QUEUE REVIEW DISABLED illuminates AMBER LED OPERATION JUNO NET 1 10 DISABLEMENTS continued 1 10 2 AUXILIARY RELAYS 1 10 3 SOUNDERS ENABLE D...

Страница 15: ...e procedure described below 1 Enter either a valid User or Programming Code 2 Select Function 3 1 Zones Disable Assign using the arrow keys or the arrow keys on the either the Infrared remote control...

Страница 16: ...g bracket again and re insert the mounting pin with the new roll The pointing towards the main circuit board Thread the paper into the printer Close the fascia and replace the screws Press the PAPER F...

Страница 17: ...SIM CARD The SIM CARD is mounted on the back of the main board Release the by pulling in the direction of the arrows With the retaining clips held in the released position push the SIM CARD forward a...

Страница 18: ...STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTALLING PRINTED CIRCUIT BOARDS ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTA...

Страница 19: ...WITH THE MANUFACTURER S RECOMMENDATION ALWAYS USE SEALED LEAD ACID BATTERIES 18 JUNO NET EN 54 MAINTENANCE MANUAL 21 08 2005 REVISION 1 0 OPERATION ss ss 2 7 REPLACING THE ELECTRICAL MAINS FUSE On th...

Страница 20: ...ter is free before starting a new print job If you wish to stop a printout enter the function again and you will be given the option of canceling the printout This function cannot be accessed remotely...

Страница 21: ...ted to the Analogue Loops Note that in Installation Mode all information is live i e the count of devices will change as the panel learns and device types will be updated if they change In Active Mode...

Страница 22: ...Zones you wish to put into test mode Exit programming mode but DO NOT press SYSTEM RESET as this clears all test modes In test mode when a detector is activated the LED on the detector will be illumi...

Страница 23: ...tor LED can be lit at any one time Select the device and SWITCHED ON and press ENTER The device will typically take a few seconds to respond Selecting NORMAL for that device or selecting SWITCHED ON f...

Страница 24: ...on B SP Backspace ESC Reject ESCape from current selection EXIT Press both keys simultaneously to stop programming SHIFT Toggle this keypad to switch from alpha numeric to numeric 2 9 GETTING INTO PRO...

Страница 25: ...RINTER CONNECTOR PRINTER FUSE PS2 PC KEYBOARD ADAPTOR STANDOFFS 4 FOR LOOPCARD SIM CARD CONNECTOR QUAD UART 50 WAY BOX HEADER FOR J NET CON 16 WAY BOX HEADER FOR LOOP CONNECTOR LOOPCARD HEADER JUNO NE...

Страница 26: ...0 9 are used to input numbers and are used to select items B SP and are often used to change fields move the cursor are often used to select the loop ENTER is used to select items and to store change...

Страница 27: ...or sub menu use either and ENTER or 0 9 and ENTER HOME takes you to 1 Review ESC takes you up a menu level Any number presses 0 9 will append a digit to what you see unless 1 You are at the very top...

Страница 28: ...mple pages of the logbook are provided here and can be photocopied to produce a logbook that conforms to EN54 14 The sample below is for the reference data e g the name of the responsible person whils...

Страница 29: ...MAINTENANCE JUNO NET 2 10 EVENT DATA SHEET DATE TIME EVENT INITIALS ACTION REQUIRED DATE COMPLETED 28 JUNO NET EN 54 MAINTENANCE MANUAL 21 08 2005 REVISION 1 0 OPERATION ss ss...

Отзывы: