3

4

All tanks must have the same pre-charge for the system to function properly. Tanks should be installed on a header to ensure all 

tanks receive equal and balanced pressure. Adjust each tank pre-charge as detailed in the adjusting tank pre-charge section. 

The system pressure switch or control should be centrally located (see Figure 2.1 & 2.2) in order for the tanks to function 

properly.

If the pump short cycles, check the air valve mounted on the tank. If water bleeds from the valve, the membrane has burst. 

Please 

call an authorized service provider to replace the membrane with factory replacement parts and instructions (see 

gwsusa.com/support).

PressureWave SF™ pressure tanks have a replaceable membrane and require pre-charge checks by an authorized service 

professional every six (6) months. 

Failure to check and adjust pre-charge every six months voids the warranty.

 

PressureWave SF™

It is recommended that the system is checked annually by a qualified professional.  The pressure tank and its connections 

to the system should be visually inspected regularly for any signs of water leakage or corrosion on the exterior of the tank or 

connection.  If any is seen, replace tank immediately.   Although our PressureWave™ diaphragm tank design is maintenance-

free, damaged and/or poorly working accessories and tank fittings can adversely affect the tank's performance, as can 

extreme temperature variations and age. Therefore, the tank pre-charge should also be checked periodically.

PressureWave™ 

CONNECTING TANK TO SYSTEM

IF REPLACING A TANK 

Remove and discard the protective cap from the pressure 

tank’s stainless steel water connection.  Connect the 

tank cross / tee fitting (3- or 5- way connector for inline 

or horizontal pressure tanks) into the pressure tank with 

adequate pipe sealant (Teflon™ Tape or pipe dope) on the 

male threads. Be cautious to not over-tighten, cross, or 

strip threads when connecting fittings.

Once the fitting is securely tightened, be sure that the 

threaded holes for your pressure switch and pressure 

gauge on the tank connection fitting are in the upward 

position. (See vertical tank examples Figures 1.1, 1.2, and 

1.3, horizontal tank example Figure 1.4 and inline tank 

example Figure 1.5).

With adequate pipe sealant, connect all of the fittings, 

valves, pressure switch, pressure gauge and water system 

pipe / connection unions to the connection fitting.

EASY AS 1-2-3 INSTALLATION

1

2

3

GWS USA, Bradenton, FL, USA  • [email protected]  • (833) 261-5461  •  www.gwsusa.com  •  2020 Rev. 02.25

PRESSURE TANK INSTALLATION

MULTIPLE TANK INSTALLATION

MAINTENANCE

GLOBAL WATER SOLUTIONS USA LIMITED PRODUCT WARRANTY

Disconnect or shut off all electric 

power to t he water suppl y/pump 

system. Shut off the water supply to the system and 

remove all water pressure from the system. Failure to 

follow these instructions may result in serious injury, 

death and/or property damage and will void product 

warranty.

A suitable pressure relief valve, 

set at a maximum of 100 psi, must 

be installed in the system near the 

pressure tank (see Fig.1.1)

All piping and electrical components should 

be in accordance with prevailing local codes 

and standards.

Inspect the installation for water leaks 

paying close attention to the connection 

between the pressure tank and the system piping. 

Always release all water and air from tank before disassembling the parts exposed to pressure 

such as flanges, air valve, pressure gauge, and the like.

The pressure tank should be installed in the incoming 

water supply line from the pump system and before any 

point of user (POU) fixtures. (see Fig. 1.1)

STARTING THE SYSTEM

Before turning on the water supply to the system, open a 

water faucet to allow air from the system piping to be purged. 

Turn on the power to the water supply and the pump should 

turn on, filling the system piping. When the water is flowing 

freely from the faucet without air, close the faucet. The pump 

will continue to run filling the pressure tank.

IMPORTANT         

Carefully read the installation, operating and maintenance instructions manual to avoid serious personal injury and/or property 

damage and to ensure safe use and proper care of this product.

WARRANTY

Warranty is extended to the original purchaser of the new product and is not assignable or transferable. Global Water Solutions 

USA (GWS USA) warrants that will be free from defect in material or workmanship under normal usage conditions beginning on 

the date of manufacture for a period of five (5) years. Any warranty claim must be made within five (5) years (unless another time 

period is set forth in the manual), measured from the date of manufacture.
To receive service under this warranty, the consumer must deliver the alleged defective product, freight prepaid, to an 

authorized GWS USA distributor or dealer within thirty (30) days after the expiration of the warranty period.  GWS USA will either 

refund the purchase price paid, or, at its option, repair or replace defective product freight prepaid to the distributor or dealer. 

GWS USA will not accept any claims for, nor will GWS USA be responsible for, any other cost, including labor.

To confirm pre-charge, shut off power to the pump, isolate and drain the tank. Check pre-charge using a pressure gauge. If 

needed, top up air to appropriate pre-charge level using an air pump or compressor. Open isolation gate valve allowing the pump 

to fill the tank with water.

With all power turned off to the pump system, drain the old 

tank, close all water flow to the tank and disconnect it from 

the system. Check all fittings, valves, switches and gauges for 

proper working condition and replace as appropriate.

Fig. 2.1

 

Fig. 2.2

Fig. 1.5 Booster Pump w/ Inline Tank

TYPICAL INSTALLATIONS

Tank

Pressure Switch

Pressure Gauge

To System

Fig. 1.2  With Submersible Pump

Drain

Valve

From

Pump

Submersible Pump

Shut Off / Check Valve

Water Flow

Pressure

Relief

Valve

If you have a jet pump, to prevent damage to the well

system, close or plug the opening during tank

installation where the installation where the vacuum and 

air volume controls connect to the pump and/or piping.

Fig. 1.3  With Convertible Jet Pump

Tank

Pump

Pressure Switch

Pressure Gauge

Drain

Pressure

Relief

Valve

Drain

Valve

Shut Off / Check Valve

Water Flow

Pump

Pressure Gauge

Tank

Pressure

Switch

Fig. 1.4 Booster Pump w/ Horizontal Tank

Pressure Relief Valve

Pressure

Switch

To Water Usage / 

System

Pump

From 

Water Source

Tank

Drain Valve

PRODUCTS COVERED

PRESSURE WAVE™ Series – LX, LH, and LV Tanks
PRESSURE WAVE SF™ Series – LV Tanks

Содержание PressureWave Series

Страница 1: ...on and Operation Manual Manual de Instalación y Operación PressureWave and PressureWaveSF PressureWaveTM y PressureWave SFTM GWS USA Bradenton FL USA support gwsusa com 833 261 5461 www gwsusa com 2020 Rev 02 25 ...

Страница 2: ... mounted on a level surface and must be adequately supported around the entire base using the mounting holes or brackets provided Inline tanks should be connected directly to the pump or the supply line using a 3 or 5 way fitting ACCESSORIES NEEDED Pressure Gauge Pressure Switch Check Valve Drain Valve Teflon Tape Tank Connector Fitting Pressure Relief Valve PressureWaveTM and PressureWave SFTM Se...

Страница 3: ... Inspect the installation for water leaks paying close attention to the connection between the pressure tank and the system piping Always release all water and air from tank before disassembling the parts exposed to pressure such as flanges air valve pressure gauge and the like The pressure tank should be installed in the incoming water supply line from the pump system and before any point of user...

Страница 4: ...señado para almacenar y entregar agua potable a presión en un sistema de agua doméstico Cuenta con un diseño de membrana o diafragma que mantiene el agua del sistema en una cámara segura y libre de contaminantes para el suministro de agua a presión entre los ciclos de la bomba Sin un tanque de almacenamiento presurizado la bomba de un sistema de agua doméstico se encenderá cada vez que haya una de...

Страница 5: ...stema abra un grifo de agua para permitir que se purgue el aire de la tubería del sistema Encienda la energía de alimentación del suministro de agua la bomba debería encenderse llenando la tubería del sistema Cuando el agua fluya libremente sin aire del grifo cierre el grifo La bomba continuará funcionando y llenando el tanque de presión Desconecte o apague toda la energía eléctrica al sistema de ...

Страница 6: ... o implícitas incluida cualquier garantía de comerciabilidad o idoneidad para un propósito particular La única y exclusiva solución del comprador por el incumplimiento de GWS USA de sus obligaciones en virtud del presente incluido el incumplimiento de cualquier garantía expresa o implícita o de otra manera a menos que se indique en el presente documento o en un instrumento escrito que forme parte ...

Страница 7: ......

Отзывы: