Control overview, Parameters and Theory of Operation

This unit is equipped with  a sophisticated, microprocessor based, digital electronic control.  All of the temperature  and

defrost functions are controlled by use of a subset of a broad range of the control’s capabilities. Global Refrigeration has

preconfigured this control for optimal performance using the operating parameters listed below. It is highly recommended

that these parameters (other than set point temperature) be left at their Global Refrigeration factory settings. In the event

of a control failure, Global Refrigeration recommends that the replacement control be sourced from us, as our factory

replacement part will be preconfigured for the specific model required. In a service emergency, a Danfoss replacement

control of the same type and model can be used, but it must be installed as the original and programmed with the values

in the table below. All Danfoss parameters not shown are left at the Danfoss default values.

CAUTION: It is essential that control replacement is only done by trained service professionals; non- standard

program parameters may result in serious machine failures and may void the unit or compressor warranty.

Theory of operation: Danfoss controls for Global freezers are equipped with two temperature sensors; a cavity sensor

connected to the S4 input and a defrost sensor connected to the S5 input. It is configured for a time interval initiated /

temperature terminated defrost cycle.

The  evaporator  fan(s)  are  configured  for  continuous  operation  with  the  exception  that  they  will  de-energize  via  the

controller’s fan relay during defrost or by the door switch(s) if a door is opened. As temperature rises in the cabinet up to

the  set  point  temperature plus  the  differential,  the  compressor  control  relay  will  energize,  powering  the  compressor

contactor  and  the compressor  will  run.  As  the  temperature  falls  to  the  set  point,  the  control  will  de-energize  the

compressor relay. After 8 hours of operation (or other interval specified in param. d03) the unit will initiate a defrost cycle .

Upon initiation of the of the defrost cycle, the compressor and evaporator fans will de-energize. The control will close the

defrost heater relay and the defrost heater will start heating the bottom of the evaporator coil. As frost melts away, the

temperature of the evaporator outlet tube, (where the defrost temperature sensor is located) will warm. When the defrost

sensor  rises  above  it’s  set  point  temperature  of  35°F  (param.  d02)  the  defrost  heaters  will  de-energize  and  the

compressor  will  be  energized.  If  the  defrost  sensor  fails  to reach  it’s  stop  temperature  the  control  will  invoke  a  timed

termination after 35minutes of defrost time (param. d04). Note that the evaporator fans will not resume operation at the

same  time  as  the  compressor.  The  evaporator  fans  will  remain  off  for  15 minutes  (param.  d07)  or  until  the  defrost

sensor’s temperature declines to 10°F (d08); whichever comes first.

Parameter description.

Danfoss

ULG30BS

T30LSP

T30HSP

T30MSP

Units

Note: parameters not shown are left

Parameter

ULG50BC

T50LSP

T50HSQL

T50MSP

at their Danfoss factory default

Number

ULG80BC

T80LSP

T50HSQHP

T80MSP

T30LGP

settings

T50LGP

T80LGP

Differential

r01

7

7

7

7

°

F

Maximum Set Point setting

r02

+20

0

0

+50

°

F

Minimum Set Point setting

r03

- 20

- 30

- 40

+ 35

°

F

Temperature Units (°C/°F)

r05

F

F

F

F

Control Operating mode*

r12

1

1

1

1

0 = STOP, 1 = RUN, ‐1 = Manual
Defrost method

d01

1

1

1

0

0=None, 1= Electric, 2=Gas, 3 = BRINE
Defrost stop temperature

d02

38

38

38

38

°

F

Interval Between Defrost Cycles

d03

12

12

12

12

Hours

Maximum Length of Defrost Cycle

d04

35

35

35

35

Minutes

Delay for Fan Restart after Defrost

d07

15

15

15

15

Minutes

Fan (Re)start temperature

d08

10

10

10

10

°

F

Fan run during defrost  1 = yes, 0= NO

d09

0

0

0

0

Defrost sensor   0 = time, 1 = S5, 2=S4

d10

1

1

1

0

*

- This parameter must be set to 1 for control to function

Содержание T30HSP

Страница 1: ...ss door Merchandisers T30MGP T50MGP T80MGP Low Temperature Storage Cabinets T30LSP T50LSP T80LSP Ice Cream Hardening Cabinets T30HSP T50HSQL T50HSQHP T50HSP IMPORTANT THE REFERENCE INFORMATION FOR THE...

Страница 2: ...STANCE For Customer Service or Technical Assistance please call our manufacturing facility toll free number 1 888 650 9799 or 1 864 260 6600 Our Customer Service Representative and Engineers are willi...

Страница 3: ...nches between the back of the cabinet and wall for proper air circulation through the condensing unit Installing the Cabinet Models with Top Mounted Compressors Whenever possible leave the crate skid...

Страница 4: ...e removable without the use of a tool At the time of initial installation all shelf bracket screws should be loosened with a tool and re tightened hand tight Floor sealing of cabinets without legs or...

Страница 5: ...be removed as follows 1 Open the door 180 and support the outer edge Remove the screws in the upper hinge at the cabinet leaving the hinge attached to the door Lift and remove from lower hinge pin CAU...

Страница 6: ...The heating element used to vaporize the water in the pan can get quite hot After unplugging the unit allow 10 minutes for it to cool prior to removing the pan The pan is located on the bottom of the...

Страница 7: ...r a failure to close the door fully To initiate a defrost manually press and hold the lower button for 4 seconds Note For all units with top mounted compressors the thermostat is located directly on t...

Страница 8: ...tactor and the compressor will run As the temperature falls to the set point the control will de energize the compressor relay After 8 hours of operation or other interval specified in param d03 the u...

Страница 9: ...efrigeration system capacity low due to Professional service required provide service defective component or refrigerant charge agent with unit s model serial no at time of service request Compressor...

Страница 10: ...n irregular surface Level or support unit silicon seal base to floor Unit Noisy Service level problems Refrigerant flood Request professional service back fan blade contact incidental component contac...

Отзывы: