INSTALLATION OVERVIEW

Fan Terminal Installation 

Instructions

Mounting The Unit

1.

Global IFS Fan Powered Terminal Units are designed to be mounted in the direction indicated by the Control

Assembly Label found on the protective shroud.

2.

Mount the unit directly on the sub-floor, beneath the raised floor. Ensure the area where the unit is to go is clear of

cables, wires, etc.

3.

Position the unit so that there is no interference with the raised floor support members.

4.

Install the unit in a location that allows free access to the unit as well as all control components.

5.

Ensure main power to the terminal and electrical coil has been disconnected prior to performing any electrical

work or inspection of the circuitry.

WARNING: 

Do not tamper with control components.

Fan Terminal Duct Connection

1. To prevent excessive air leakage, all cleat joints should be sealed with an approved duct sealer. This applies to all

accessory connections as well as the basic fan box.

2. Holes that are drilled in the duct for testing or balancing purposes are to be sealed with duct tape or duct sealer.
3. A minimum of 0.10 inches W.G. downstream static pressure is required to prevent overheating of the fan motor.

Fan Terminal Electrical Connection

1. All field wiring is to be in accordance with the National Electrical Code ANSI/NFPA No. 70 or the Canadian Electrical

Code , Part 1, CSA Standard C 22.1 and local codes and standards.

2. Refer to the product identification label on each unit for information to determine the field wire size.

CAUTION: 

Check voltage requirements prior to power supply connection.

 Refer to the electrical label located near the electrical 

control box and also refer to the schematic drawing provided on the underside of the electrical control box cover.

3. If upon energizing the electric motor(s), excessive noise is apparent, shut down the unit. Determine the cause by

checking for packing materials, etc. and re-energize after corrective action has been taken.

4. If an Electric Reheat Coil has been supplied, refer to the electrical schematic which is permanently affixed to the

topside of the electrical control cabinet cover, prior to hook-up.

CAUTION: 

Check the voltage requirements to ensure proper voltage supply is used

FAN POWERED BOX & TERMINAL UNIT 

Содержание 1462263

Страница 1: ...Page 1 of 9 Global IFS Fan Powered Box Global IFS Fan Powered Box Installation Instruction Tool Check List 2 Fan Powered Box Terminal Unit FPB TU...

Страница 2: ...l Global IFS fan powered terminal units are tagged with a control assembly label as shown on the left This label identifies the model number location tag controller type actuator type thermostat actio...

Страница 3: ...sting or balancing purposes are to be sealed with duct tape or duct sealer 3 A minimum of 0 10 inches W G downstream static pressure is required to prevent overheating of the fan motor Fan Terminal El...

Страница 4: ...turn filters if supplied are clean 3 All balancing dampers are adjusted and locked Dampers downstream of the terminal unit should be proportionally balanced 4 Thermostats are calibrated and operationa...

Страница 5: ...2 VDC Fan Off 1 5V Recommended 2 10 VDC Remote Control 0 100 Note Refer to Fan Curves performance data documents for fan curves Pressure Independent Flow PIF Motor Program Voltage Equations Box Con i...

Страница 6: ...lso has a digital screen and BAS RPM feedback 2 10 VDC which is proportional to motor RPM NOTE 24 VAC COM BAS COM ANALOG OUTPUT COM are all connected together Please observe 24 VAC polarity NOTE Local...

Страница 7: ...ce the downstream static pressure is confirmed check the supply voltage is the same as stated on the wiring diagram The supply voltage must be identical to the wiring diagram c For ECM applications th...

Страница 8: ...ING 1 4 5 voe MIN TO MAX AIRFLOW 0 1 voe FAN OFF UNE LEGEND FACTORY ELEClRICAL WIRING FIELD EL EClRICAL WIRING OPTIONAL WIRING WH AFS AUT AIR OMATI FLOW C SWITCH RESET SWIT AR CH C1 C2 24V CONTACTOR C...

Страница 9: ...dulating Controller with BACnet Manual5 mfd Transformers 019436 001 115V 24V 50 VA Transformer 019436 011 208V 240V 24V 50 VA Transformer 019439 001 277V 24V 50 VA Transformer Disconnect Switch 019903...

Отзывы: