Page: 1 of
9
Global IFS
Fan Powered Box
Installation Instruction
Tool Check List
#2
Fan Powered Box & Terminal Unit (FPB & TU)
Страница 1: ...Page 1 of 9 Global IFS Fan Powered Box Global IFS Fan Powered Box Installation Instruction Tool Check List 2 Fan Powered Box Terminal Unit FPB TU...
Страница 2: ...l Global IFS fan powered terminal units are tagged with a control assembly label as shown on the left This label identifies the model number location tag controller type actuator type thermostat actio...
Страница 3: ...sting or balancing purposes are to be sealed with duct tape or duct sealer 3 A minimum of 0 10 inches W G downstream static pressure is required to prevent overheating of the fan motor Fan Terminal El...
Страница 4: ...turn filters if supplied are clean 3 All balancing dampers are adjusted and locked Dampers downstream of the terminal unit should be proportionally balanced 4 Thermostats are calibrated and operationa...
Страница 5: ...2 VDC Fan Off 1 5V Recommended 2 10 VDC Remote Control 0 100 Note Refer to Fan Curves performance data documents for fan curves Pressure Independent Flow PIF Motor Program Voltage Equations Box Con i...
Страница 6: ...lso has a digital screen and BAS RPM feedback 2 10 VDC which is proportional to motor RPM NOTE 24 VAC COM BAS COM ANALOG OUTPUT COM are all connected together Please observe 24 VAC polarity NOTE Local...
Страница 7: ...ce the downstream static pressure is confirmed check the supply voltage is the same as stated on the wiring diagram The supply voltage must be identical to the wiring diagram c For ECM applications th...
Страница 8: ...ING 1 4 5 voe MIN TO MAX AIRFLOW 0 1 voe FAN OFF UNE LEGEND FACTORY ELEClRICAL WIRING FIELD EL EClRICAL WIRING OPTIONAL WIRING WH AFS AUT AIR OMATI FLOW C SWITCH RESET SWIT AR CH C1 C2 24V CONTACTOR C...
Страница 9: ...dulating Controller with BACnet Manual5 mfd Transformers 019436 001 115V 24V 50 VA Transformer 019436 011 208V 240V 24V 50 VA Transformer 019439 001 277V 24V 50 VA Transformer Disconnect Switch 019903...