UG-7/STD-H
SMOKE DETECTOR
HOUSING HIGH LID
MANUAL 220829
MADE IN PORTUGAL - EU
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL |
Tel
: +351 289 896 560
Technical Suppor
t: [email protected] |
www.globalfire-equipment.com
TECHNICAL SPECIFICATIONS
MATERIAL / COLOUR
ABS Plastic/Aluminium / Grey
WEIGHT: HOUSING
880 g
PROTECTION / AIR SAMPLING TUBE
IP54 / Aluminium
DIMENSIONS: HOUSING
279mm x 165mm x (103mm + venturi pipe length)
DIMENSIONS: VENTURI PIPE
0,6m, 1,5m or 2,8m - 1.6m extension tube available
ORDER CODE
UG-7/STD-H
SMOKE DETECTOR HOUSING HIGH LID
MOUNTING AND POSITIONING
The Uniguard should be installed according to the
drawing below. The Uniguard can be installed on any side
of the duct. N.B. Rectangular ducts: In order to gain
maximum air sampling coverage, install the Uniguard on
the shortest side of a rectangular duct. We recommend
that the Uniguard is mounted at an equal distance from
heating, cooling, or humidity devices, and similar to the
siting for flow monitors.
A distance of 3 times the duct diameter should be left
before a damper, filter or change of the duct direction,
and 5 times the diameter after these devices.
Example of installation at sources of interference
Hydraulic diameter