background image

Logging In

To enter programming mode you need to log in.

The Main Panel must be powered up and must have initialized itself i.e. NOT be showing the
‘INITIALIZING’ message.

Press ENTER on the IR Keypad (or keyboard). You must now input your unique customer access code
(supplied with the panel). You have unlimited attempts but if code entry is not started within 10
seconds then the panel will revert back to it’s default screen. While entering the code you are allowed
up to 5 seconds between key presses.

The programming functions are arranged using a menu system.

To select a function or sub-menu use either

and ENTER or 0-9 and ENTER.

HOME takes you to "1-Review".
ESC takes you up a menu level.

Any number presses (0-9) will append a digit to what you see unless :

1) You are at the very top (1- Review) then the first press selects the first digit.
2) You are at the bottom then the press replaces the last digit.

The top level menus are:

1 Review Historic Log
2 Text Descriptions & Names
3 Zones - Disable & Assign
4 Sounders - Disable & Assign
5 Input/Output - Disable & Assign
6 Device Set-up
7 Monitor Device Counts & Test
8 General

Most functions operate in a consistent manner using the standard keys. The item that is being
changed is usually highlighted with a flashing cursor.

Function Selection

JUNO-NET

COMMISSIONING

G L O B A L

F I R E

E Q U I P M E N T