Global Fire Equipment // 

globalfire.pt 

pm_io3ioplusmainsio_01_010003_en_200103

 

 

 
 

IO-ISO 
3 I/O PLUS 
MAINS I/O 

 

PROGRAMMING MANUAL

 

 

 

INTRODUCTION 

 

This manual explains in detail how to use and program the following modules: 
 

 

 

 

IO-ISO 

3 I/O PLUS 

all variants 

MAINS I/O 

 
PROGRAMMING MODE 

 

In order to set the module in programming mode first POWER OFF your module then set DIL Switches 1 to 7 to OFF and 
Switch 8 to the ON position, as indicated on the image below. Finally POWER ON your module. 
 

 

Switches 1-7 - 

Used to select programming parameter and assigned value.

 

Switch 8 - 

Programming Mode. 

 
When in programming mode the 2 LEDs will flash alternatively. The unit will remain in programming mode while SW 8 is in 
the ON position. When Switch 8 goes from ON to the OFF position the settings indicated on Switches 1 through 7 will be 
recorded on the non-volatile memory of the module. If a new parameter has been accepted, the Green LED for 

IO-ISO

 or 

Yellow LED for 

MAINS I/O

 or 

3 I/O PLUS

 modules, will flash 4 times. When programming is not accepted the Red indicator 

will remain on for an extra 3 seconds. 

 
Programmable Options 
 

In order to program the different  functions available use Switches 1 through 7 as shown below: 

 

 
A

 - 

The first 3 Switches select the function to be programmed.

 

B

 - 

Switches 4 through 7 select the value for the function to be programmed. 

 

Содержание IO-ISO

Страница 1: ...Mode When in programming mode the 2 LEDs will flash alternatively The unit will remain in programming mode while SW 8 is in the ON position When Switch 8 goes from ON to the OFF position the settings...

Страница 2: ...ed to obtain the desired output configuration In order to program the different functions available use Switches 1 through 7 as shown below FUNCTION VALUE DIL SWITCH SW1 SW2 SW3 DIL SWITCH SW4 SW5 SW6...

Страница 3: ...ule s Output is now programmed with a delay of 30s which is the default Output Timer value OUTPUT TIMER FUNCTION Now that the module s output is programmed to have a 30s delay let s assume that desire...

Страница 4: ...trigger FAULT 3 OPEN CIRCUIT TO ALARM Open Circuit OC Activation This mode is constantly monitoring the 22k EOL in case of OC it will trigger ALARM in case of SC it will trigger FAULT 4 4K7 OPEN TO A...

Страница 5: ...ON MODE ON ON OFF 4K7 CLOSE TO ALARM Default OFF OFF OFF OFF SHORT CIRCUIT TO ALARM ON OFF OFF OFF OPEN CIRCUIT TO ALARM OFF ON OFF OFF 4K7 OPEN TO ALARM ON ON OFF OFF INPUT DELAYED ACTIVATION FUNCTIO...

Страница 6: ...nd DIL Switch 8 to the ON position STEP 3 Power up the module The two LEDs flashing alternatively will indicate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to INPUT DELAY...

Страница 7: ...cate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to ONE ADDRESS MODE SW1 ON SW2 OFF SW3 ON STEP 5 Set the DIL Switches 4 to 7 to ON SW4 ON SW5 OFF SW6 OFF SW7 OFF STEP 6...

Отзывы: