It is recommended that the batteries are fitted at the end of commissioning the system otherwise
it can be difficult to remove the power quickly if there is a problem.
The batteries are connected to the GFE-BCM module board. This battery connection not only
supplies the module with power if the primary supply should fail, it also provides a charging output
to maintain the batteries in a fully charged state.
Before connecting the batteries check the voltage across the battery connection terminals. It
should be 28.0V +/- 0.5V.
Note -
arcing and fire risk. Never short circuit the battery terminals. Always connect the blue
wire between the batteries last.