INSTALLERS MENU EXPLAINATION 

Monitored Safety

On This screen you can see the Safety sensors of your doors. This serves two purposes. 

1) If the Writing is green it means that your sensors are not active. If any are in Red, this indicates that
the particular Safety sensor is receiving any activation.
2) This screen shows you if your sensors are monitored or not. If you fit a monitored sensor, that 
particular one will say “YES” next to it

Example:

SIDE SCREEN L/H – NO  = Left hand side screen sensor is not a monitored sensor but it is being 
activated, Check for Objects in the sensor field and check the sensor, is not adjust so it is seeing the door. 

Door Information

This screen shows you the PSU Voltage and the battery voltage. 
This screen also shows you the last thing to happen to the door ( Last = L> ) and if anything is currently
happening to the door ( Current = C> )

The bottom line of the screen will show you any alarms currently active on the control unit. 

Error Log

The Control Unit will Log the last 20 faults with the door – saving the time and date
There is also an option to delete the log and start again.

Set Time and Date

This screen is to set the time and date use in the Error logs. Scroll up or down to select the digit required
and press select. (Please note: this control unit uses a 24 Hour time format)

Opening speed (Group) 1 – 9

1-5 - Single door settings
6-9 – Double door settings

The Speed Group combines the high speed, Braking force, Braking Distance, Low Speed and Safety
speed into one convenient group. 

These groups have been assembled to allow a smooth operation of the sliding door. Group Number 5 Is
the fastest for a single door and Group number 1 is the slowest. Upon Start up of your Premier-slide
operator, it will weigh the doors and select an appropriate group so that the speeds and forces are as close
to the British standard as possible.

PLEASE BE AWARE THAT WE CANNOT GUARANTEE THIS AND IT IS THE CERTIFIED 
ENGINEERS JOB TO TEST AND ADJUST EACH INDIVIDUAL DOOR SO THAT IT COMPLIES
TO THE RELEVANT STANDARD. 

Auto Reverse Force – Opening

This is a force form 1- 20 that dictates the amount of force required on the door to stop it during its 
opening cycle. General use is set at 1 which is the minimum amount required to stop the door. Please
adjust up if you get Reversing failures.

Please note: if this number is set too low the door may stop at different positions in its travel as it will
see them as obstructions 

18

Содержание Premier-Slide 100

Страница 1: ...Technical Manual Premier Slide 100 CE...

Страница 2: ...witch Page 13 Customer Door Operating Modes Page 14 Using the Access panel Page 15 Door Start up Procedure Page 16 Installers Menu Layout Page 17 Installers Menu Features Explained Pages 18 19 Technic...

Страница 3: ...nd make installations maintenance as easy as possible Safety Standard Your door system has been manufactured to the latest applicable safety standard in order for you to comply you will need to have t...

Страница 4: ...ion minimal tools required Monitored battery backup with optional opening Programs Switch able Motor direction Slim line mode switch available in Surface flush fit and canopy mounting options Interloc...

Страница 5: ...m bar This should be installed inside the top door rail see Fig 1 2 If the unit is to be fitted to an existing door see Fig 2 then a suitable fixing such as a threaded insert should be used The top of...

Страница 6: ...ets have slots to allow the door distance from the frame to be adjusted as necessary Position the hanger brackets so that the centre of the bracket is approx 150mm from the edge of the door Once the d...

Страница 7: ...opening height and level Mark through one of the bottom fitting holes at each end Remove the header drill tap and fix the unit Attention should be paid to what fixings are used when fitting in the ar...

Страница 8: ...slide in if required The floor mounted guide block assembly is simply drilled into the floor and secured with countersunk screws and rawl plugs The guide should be positioned so that the side of the...

Страница 9: ...iction problems When adjusted properly you should be able to manually push each leaf with minimum effort and no friction To Adjust the doors up and down loosen the two M6 Bolts Now you can turn the M5...

Страница 10: ...the motor gearbox unit to the left hand side 5 mm from the end and the idler pulley assembly to the right hand side so that the centre of the pulley wheel on each align Install new control unit to the...

Страница 11: ...bolt For Bi parting doors there will be one longer and one smaller belt bracket Idler Wheel Adjustment The idler pulley assembly installs like the rest of the equipment into the right hand side of the...

Страница 12: ...the default values The following connections as listed below are normally open Inner sensor Outer sensor Key Input The following connections as listed below are normally closed Inner Threshold Safety...

Страница 13: ...This switch has been designed to fit flush for Installation in hollow Aluminium frame sections and Hollow walls You will need to cutout remove part of the Section wall and drill 4 x fixing holes in a...

Страница 14: ...neer s mode Pharmacy Mode When selected the door will open to the desired position and Lock When you change it back to closed the door will close and lock if switched on This Function is commonly used...

Страница 15: ...Note If you have fitted the Canopy Switch then the reset is in the Top Right Hand corner Errors The Access panel has a complex self diagnostic System There are two sets of error codes The first sets a...

Страница 16: ...s mode The door is now ready for you to make the final adjustments to suit site conditions and the BS7036 1996 If a Contact requires changing to allow the door to work I e Fire alarm N C Change to N O...

Страница 17: ...ode you need to press the down button twice then the up button twice and press select This will take you to the first screen of the Installers menu From here you can navigate up or down through the Me...

Страница 18: ...Date This screen is to set the time and date use in the Error logs Scroll up or down to select the digit required and press select Please note this control unit uses a 24 Hour time format Opening spee...

Страница 19: ...arts to close No 3 4 11 12 Key Entry Hold Open Time This is where you adjust the time in seconds which the door waits in its fully open position once it has received an activation from the Key Input c...

Страница 20: ...n t exceed the High Speed 10 Safety speed Closing 10 20 11 Braking force Closing 1 40 12 Braking distance 1 100 13 Auto reverse force 1 20 14 Holding force Closed 0 2 15 Partial opening 50 80 16 Pharm...

Страница 21: ...unsafe The Bs7036 1996 states a maximum 150Nm Please use your Newton Meter on all installations to confirm that your particular door is compliant with the BS7036 1996 Closing Speed Adjustments 1 RED...

Страница 22: ...idth Motor lock This Function allows you to turn the Motor Lock On or off when the door reaches its closed position Aux lock on off Should you wish to fit an additional Lock to the door via the Auxili...

Страница 23: ...on the age of the cells Door hold time This is an adjustable time in seconds that the door will count down from once it reached its open position before it closes Key hold time This hold open Time is...

Страница 24: ...his is to help you identify the door This will be displayed on the bottom of the screen in Grey Interlock enable When installed in a security lobby setup the door will use one of the above modes but w...

Страница 25: ...time and date This is saved when a fault is detected in fault Logs Use the up and down arrow to run from 0 to 9 plus a space when you get to the digit you need to press the select button and it will...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...and other types of door should be assessed individually You will need to Times the Door Height by the Door width to get an overall area to use the table below I E 1 1mtr wide door x 2 2m High door 2 4...

Страница 29: ...sor has gone faulty Side Screen Safety constantly active 4 minutes SIDE SCREEN SENSOR FAILURE OR The monitoring system detects that the sensor has gone faulty If the Key Input is constantly active 4 m...

Страница 30: ...30 SHORT CIRCUIT...

Страница 31: ...ears care should be taken when handling products that have been finished Sharp edges can scratch and Pierce Powder coated surface Powder coating should be cleaned down with warm water and a mild deter...

Страница 32: ...replacing components from its Factory within the 18month period from purchase The Batteries are only warranted for a 12 Month Period The warranty does not cover misuse accidental damage or negligence...

Отзывы: