Glen Dimplex Dimplex 18 OV Скачать руководство пользователя страница 6

1.0

USING THE BOILER

© Dimplex Boilers 2008

3

1.1

CONTROL PANEL

1.2

CH - CENTRAL HEATING TEMPERATURE CONTROL

Control knob shown in the OFF position.

Turn the knob clockwise to increase the temperature of the

central heating.

1.4

CH - CENTRAL HEATING TEMPERATURE CONTROL

Adjustable via the CH temperature control knob to give radiator

temperatures of between 30°C and 80°C.

During periods of no central heating requirement, the control

should be set to the STANDBY position but the permanent live

to the boiler should be left on.

1.3

TO LIGHT THE BOILER

1. Switch on the electrical supply.

2. Turn the CH temperature Control knob to the midpoint

between the minimum and maximum setting. The display

changes from ‘O’ to ‘h’.

3. Ensure Programmer and room thermostat (if fitted) are

calling for heat.

4. The display changes to ‘H’. When the boiler has lit a small

dot will also appear in the bottom right corner of the display.

5. If the burner fails to light the fan will stop. Initially this may

be due to air in the gas supply. The boiler will automatically

have five attempts at ignition.

6. After the five attempts it may be necessary to RESET the

boiler by turning the control knob to the RESET/STANDBY

position and back to ‘ON’ within TWO seconds (then repeat

step 2).

Min

Max

Central Heating

Temperature Control

7 segments 

LED display

Fig. 2

Fig. 3

Fig. 4

Min

Max

Fig. 5

Digital Display

Burner On Light

4.0

ERROR CODES

6

© Dimplex Boilers 2008

AFTER ENSURING THAT ALL ACTIONS HAVE BEEN CARRIED OUT RESET THE BOILER (REFER TO SECTION 5.4) IF ANY

Y OF 

THE BELOW FAULTS OCCUR DURING INSTALLATION PLEASE REFER TO THE ACTIONS, HOWEVER IF ANY OTHER ER

RROR 

CODE IS SHOWING PLEASE CONTACT THE INSTALLER OR TECHNICAL HELP LINE

E:: 01926 834834

ERROR CODE

DESCRIPTION

REASON

ACTION

RESET POSSIBLE

1

Overheated 

CH Water temperature 

•Check no air is in heat exchanger / CH system

appliance

greater than 105°C

•Check external pump operation

Yes

•Check PCB / X1C connector
•Check flow thermistor
•Check wires to sensors not crossed

2

Different check faulty / Sensor temperature  

• Check water pressure

Flame for 15 seconds

differential incorrect

• Check external pump / CH system blockage

Auto Restart When Fixed

• Check no air is in heat exchanger / CH system
• Check flow, and return sensors

3

No gas or Lockout flame Low gas pressure.

• Check gas supply

signal / No flame, 

Loss of flame signal during 

• Check gas service cock

Lockout after 5 ignition operation

• Check gas valve and lead

attempts

• Check detection electrode / lead

Yes

• Check PCB / X2A & X2B connectors
• Check spark generator /spark electrode
• Check mains earth lead continuity

4

Flue gas sensor / 

Flue gas temperature greater

• Check flue sensor

No flame

than 95°C

• Check flue system
• Check no air is in heat exchanger / CH system

Yes

• Check external pump
• Check PCB / PCB connectors

ERROR CODE

DESCRIPTION

REASON

ACTION

RESET POSSIBLE

5

Defective sensor or

Defective flow, return or flue  • Check wiring to sensors

thermal fuse blown

sensor or heat exchanger

• Check PCB / X6 & X8 connectors

reached maximum safe

• Check flow, return and flue sensors

working temperature

• CHECK THERMAL FUSE IS OPEN CIRCUIT.

IF SO REPLACE HEAT EXCHANGER (SEE 10.8)

6

Defective gas valve / 

5 sec flame signal after burner • Check gas valve and lead

Flame continues after

is switched off

• Check PCB

demand ends

7

Defective fan / No flame Missing or Erroneous RPM 

• Check fan

signal

• Check mains fan lead & connector
• Check low voltage fan lead & connector
• Check PCB / X3 connector

Auto Restart When Fixed

A

PCB error / No flame

Internal error

• Check PCB

b

Activate BCC / No flame New BCC

• Turn CH control knob to reset twice to activate

C

Safety system failure / Failure of internal self  

• Check PCB

No flame

checking system

• Check BCC is initialised

E

BCC error / No flame

Incorrect / missing BCC

• Reset or replace BCC

h

No flame

Faulty connector

• Check PCB / X1A connector

0

Different check faulty / Water flow rate too low

• Check water pressure

Flame for 15 seconds 

• Check external pump / CH system blockage
• Check no air is in heat exchanger / CH system
• Check wires to sensors not crossed
• Check flow, and return sensors

P

Error in power supply /  Low mains voltage

• Check mains voltage

No flame

• Check PCB connectors

No light indication

Defective power supply

• Check power supply
• Check PCB / X1B connector
• Check PCB fuse

RESET LOCK-OUT CODES

BLOCKING CODES

Содержание Dimplex 18 OV

Страница 1: ... Dimplex Boilers 2008 Dimplex 18 OV Dimplex 32 OV Open Vented Condensing Boilers User s Operating Instructions These instructions should be left with the user ...

Страница 2: ... 4 0 Error Codes 6 5 0 Additional Information 7 Natural Gas Dimplex 18 OV Gas Council Appliance No 41 149 04 Dimplex 32 OV Gas Council Appliance No 41 149 03 2 Dimplex Boilers 2008 GAS COUNCIL NUMBERS Control Panel Fig 1 Read these instructions carefully before trying to operate the appliance ...

Страница 3: ...n the CH temperature Control knob to the midpoint between the minimum and maximum setting The display changes from O to h 3 Ensure Programmer and room thermostat if fitted are calling for heat 4 The display changes to H When the boiler has lit a small dot will also appear in the bottom right corner of the display 5 If the burner fails to light the fan will stop Initially this may be due to air in ...

Страница 4: ... the CH temperature control knob ON Is the timer on and calling for heat Is the room thermostat set high enough Reset the boiler see Section 5 7 If the boiler does not reset contact your installer or service engineer Yes No No No No No Yes Yes Yes Consult gas supplier Turn the knob clockwise Ensure the timer is set for central heating on see your timerinstructions Turn the room thermostat to maxim...

Страница 5: ... mains supply must facilitate complete isolation of the appliance Either a 3A fused three pin plug and unswitched shuttered socket outlet or a 3A fused double pole switch having a 3mm contact separation in both poles serving only the boiler and its external controls may be used 3 3 ELECTRICAL SUPPLY 3 4 CLEARANCES AND VENTILATION 5mm Min 372mm 5mm Min 580mm 200mm 200mm 285mm Wall 450mm Min For Ser...

Страница 6: ...heck external pump Check PCB PCB connectors ERROR CODE DESCRIPTION REASON ACTION RESET POSSIBLE 5 Defective sensor or Defective flow return or flue Check wiring to sensors thermal fuse blown sensor or heat exchanger Check PCB X6 X8 connectors reached maximum safe Check flow return and flue sensors working temperature CHECK THERMAL FUSE IS OPEN CIRCUIT IF SO REPLACE HEAT EXCHANGER SEE 10 8 6 Defect...

Страница 7: ... must be carried out by a competent person such as British Gas or other CORGI Registered personnel 5 5 PLUMING FROM TERMINAL Like all condensing boilers this appliance will produce a plume of condensation from the flue terminal This is due to the high efficiency and hence low flue gas temperature of the boiler It is normal and not a fault indication The boiler is fitted with a condensate trap The ...

Страница 8: ...rve the right to change product specifications without prior notice Errors omissions excepted Glen Dimplex Boilers Stoney Lane Prescot Merseyside L35 2XW For all telephone enquiries call 0844 371 2222 website www glendimplexboilers com Part of the Glen Dimplex Group S A L E S A N D S E RV I CE H E L P L I N E 0 8 4 4 3 7 1 1 1 1 1 ...

Отзывы: