Air-to-water heat pump 6 kW

English

14 Product information as per Regulation (EU) No 813/2013, Annex 

II, Table 2

Information requirements for heat pump space heaters and heat pump combination heaters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

Symbol

Value

Unit

Item

Symbol

Value

Unit

Tj = - 7°C

P

dh

4,6

kW

Tj = - 7°C

COP

d

2,03

-

Tj = + 2°C

P

dh

3,4

kW

Tj = + 2°C

COP

d

3,00

-

Tj = + 7°C

P

dh

4,2

kW

Tj = + 7°C

COP

d

4,02

-

Tj = + 12°C

P

dh

4,8

kW

Tj = + 12°C

COP

d

5,06

-

Tj = bivalent temperature

P

dh

5,0

kW

Tj = bivalent temperature

COP

d

1,76

-

Tj = operation limit temperature

P

dh

5,0

kW

Tj = operation limit temperature 

COP

d

1,76

-

For air-to-water heat pumps

For air-to-water heat pumps:

Tj = -15°C (if TOL < -20°C)

P

dh

-

kW

Tj = -15°C (if TOL < -20°C)

COP

d

-

-

Bivalent temperature

T

biv

-10

°C

For air-to-water heat pumps: 
Operation limit temperature

TOL

-10

°C

Cycling interval capacity for heating

P

cych

-

kW

Cycling interval efficiency

COP

cyc

-

-

Degradation co-efficient (**)

C

dh

0,99

-

Heating water operating limit 
temperature

WTOL

60

°C

Power consumption in modes other than active mode

 

Supplementary heater

 

 

 

Off mode

P

OFF

0,021

kW

Rated heat output (*)

P

sup

0

kW

Thermostat-off mode

P

TO

0,021

kW

Type of energy input

 

eletrical

 

Standby mode

P

SB

0,021

kW

 

 

 

 

Crankcase heater mode

P

CK

0,000

kW

 

 

 

 

Other items

 

 

 

 

 

Capacity control

variable

 

-

3000

m³ /h

Sound power level, indoors/ outdoors

L

WA

45/60

dB

-

--

m³ /h

Emissions of nitrogen oxides

NO

x

-

mg/kWh

 

 

 

 

 

 

 

 

 

Declared load profile

L

 

Water heating energy efficiency

η

wh

87

%

Daily electricity consumption

Q

elec

5,66

kWh

Daily fuel consumption

Q

fuel

-

kWh

Contact details

(**) If C

dh

 is not determined by measurement nthen the default degradation is C

dh

 = 0,9

(--) not applicable

For air-to-water heat pumps: Rated 
air flow rate, outdoors

For water-/brine-to-water heat 
pumps: Rated brine or water flow 
rate, outdoor heat exchanger

Declared capacity for heating foer part load at indoor temperature 20°C and 
outdoor temperature T

j

Declared coefficient of performance or primary energy ratio for part load at 
indoor temperature 20 °C and outdoor temperature T

j

For heat pump combination heater:

Glen Dimplex Deutschland GmbH, Am Goldenen Feld 18, 95326 Kulmbach

(*) For heat pump space heaters and heat pump combination heaters, the rated output P

rated

 is equal to the design load for heating P

designh

, and the rated 

heat output of a supplementary capacity for heating sup(

Tj

).

118

%

Heat pump combination heater

yes

Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low- temperature heat pumps, parameters 
shall be declared for low-temperature application.

Rated heat output (*)

Prated

5

kW

Seasonal space heating energy 
efficiency

η

s

Parameters shall be declared for average climate conditions:

Brine-to-water heat pump

no

Low-temperature heat pump

no

Equipped with a supplementary heater

yes

Model

06CHOIAOW2

Air-to-water heat pump

yes

Water-to-water heat pump

no

Содержание 06CHOIAOC6

Страница 1: ...er no DOK4x HOIAO WxDEN EN FD 9912 System M Compact Plus 6kW Installation and Operating Instruction Air to Water Heat Pump in Integral Design Glen Dimplex Thermal Solutions Dimplex 06CHOIAOC6 06IHOIAO...

Страница 2: ......

Страница 3: ...e 11 6 2 Condensate drain 11 6 3 Connection on heating side 11 6 4 Domestic hot water connection 12 6 5 Temperature sensor connection 13 6 6 Electrical connection 14 6 7 Refrigerant pipe connections 1...

Страница 4: ...2 DOK4x HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 6 kW 17 Declaration of conformity 33...

Страница 5: ...to This unit can be used by children aged 8 and over and by per sons with limited physical sensory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been...

Страница 6: ...the air i e ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increas ing its pres...

Страница 7: ...lve for generating domestic hot water 9 Switch box with heating controller 10 Overflow valve to guarantee the minimum heating water flow rate to be set by the installer 11 Universal hardware interface...

Страница 8: ...6 DOK4x HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 6 kW 3 2 Outdoor unit 1 Evaporator 2 Fan 3 Expansion valve 4 Switch box 5 Connection for refrigerant line 1 2 3 4 5...

Страница 9: ...be tilted back by up to 45 and lifted by the handles on the back at the top Tilting over 45 is not permitted without removing the refrigeration circuit beforehand To remove the refrigeration circuit r...

Страница 10: ...onnection 2 Disconnect the plug connections on the refrigeration cir cuit switch box 3 Loosen the mounting screws 4 Pull the refrigeration circuit out at the side and transport it to the intended loca...

Страница 11: ...The responsibility for the heat pump in stallation lies with the specialist system construction company During the installation local requirements such as building reg ulations static load of the bui...

Страница 12: ...on location at any time of the year The minimum volume of the room where the heat pump is in stalled must be no less than the following value depending on the refrigerant quantity in the device If the...

Страница 13: ...and shut off option must be im plemented upstream and downstream of the indoor unit Once the heat pump has been connected to the heating sys tem it must be filled purged and pressure tested When doin...

Страница 14: ...e ready for op eration The system must be drained if the heat pump is taken out of service or in the event of a power failure The heating cir cuit should be operated with a suitable frost protection i...

Страница 15: ...at all weather conditions are taken into consideration and the meas ured value is not falsified Mount on the external wall on the north or north west side where possible Do not install in a sheltered...

Страница 16: ...OK4x HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 6 kW 6 6 Electrical connection 6 6 1 Circuit diagram Symbol legend see cap 6 6 2 on page 15 Equipment marking see cap 6 6 3 on page...

Страница 17: ...ydraulics WPM A210 Master unit A220 Expansion module WPM A300 Electrical distribution system A350 Router A400 Hydraulic installation general A420 Domestic hot water B3 domestic hot water thermostat E1...

Страница 18: ...old cur rent because otherwise important protection functions could be lost during a utility block Utility block The utility blocking contactor K22 with main contact and auxiliary contact NO contact 1...

Страница 19: ...75 g 225 g HINWEIS NOTE If the indoor unit is mounted 2 5 m or more metres higher or lower than the outdoor unit a cooling technology specialist must perform a separate check to ensure that the device...

Страница 20: ...the system Step 1 Preparation Ensure that every pipe liquid and intake side between the in door and outdoor unit is connected correctly Ensure that both maintenance valves on the liquid and intake of...

Страница 21: ...ss varies with differ ent lengths of the pipework and the pump output The follow ing table shows the time required for pumping empty Step 4 Filling Once the leakage tightness test and evacuation have...

Страница 22: ...ing procedure to set the over flow valve correctly Close all heating circuits that may also be closed during opera tion depending on how the heat pump is being used so that the most unfavourable opera...

Страница 23: ...by a heating technician Based on current information we recommend using a 5 phosphoric acid solution for cleaning purposes However if cleaning needs to be performed more frequently a 5 formic acid sol...

Страница 24: ...rom the power supply HINWEIS NOTE Personal protective equipment protective goggles safety shoes and gloves where necessary must be used when work ing on the device Components with plastic parts must b...

Страница 25: ...nce of 1 m indoors4 dB A 38 38 3 7 Air flow Normal operation reduced operation3 m h 3000 2600 3000 2600 4 Dimensions weight and filling quantity 4 1 Device dimensions5 indoors without connections H x...

Страница 26: ...system other parameters in particular the defrosting capacity the bivalence point and regulation should also be taken into consideration These figures are only achieved with clean heat exchangers Info...

Страница 27: ...intake 0 3 m 1 0 m 0 5 m 0 5 m Minimum clearances Direction of air flow 358 40 460 40 17 5 4x Fixing holes base frame for M12 438 540 Hatched area footprint 600 871 500 165 40 40 53 36 676 472 99 160...

Страница 28: ...2 www gdts one English Air to water heat pump 6 kW 12 2 Dimension drawing indoor unit 2 1 2 6 2 8 2 7 2 3 2 4 2 5 2 2 544 600 600 2100 0 40 142 212 282 352 422 573 652 880 63 572 37 ca 0 68 118 195 25...

Страница 29: ...ugh refrigerant line 1 6 Optional feedthrough electric wires 1 7 External dimensions wood design variant 1 8 Included pipe set for optional rear connection of the re frigerant lines 2 Indoor unit 2 1...

Страница 30: ...25 20 15 10 5 0 5 10 15 20 25 30 35 40 max min 0 1 2 3 4 25 20 15 10 5 0 5 10 15 20 25 30 35 40 max min 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air intake temperatu...

Страница 31: ...ions of nitrogen oxides NOx mg kWh Declared load profile L Water heating energy efficiency wh 87 Daily electricity consumption Qelec 5 66 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is...

Страница 32: ...eclared load profile L Water heating energy efficiency wh 87 Daily electricity consumption Qelec 5 66 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen...

Страница 33: ...overed by the warranty If it was not possible to remedy the defect the manufacturer shall either deliver a replacement free of charge or issue a reimburse ment for the reduced value In cases in which...

Страница 34: ...en cryption methods III Use of service providers Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sal...

Страница 35: ...www gdts one DOK4x HOIAO WxDEN FD 9912 33 Air to water heat pump 6 kW English 17 Declaration of conformity You can find and download the current CE conformity declaration at https gdts one m...

Страница 36: ...9 dimplex gdts one www gdts one Gesch ftsstelle sterreich Glen Dimplex Austria GmbH Hauptstra e 71 A 5302 Henndorf am Wallersee T 43 6214 20330 F 43 6214 203304 info dimplex at www dimplex at Office F...

Отзывы: