How to Setup and Operate 
 

First connect the heater load (7.5 amps or less) and the thermocouple plug to the load and 
thermocouple receptacles on the rear of the control. Next, plug the control line cord into 
the appropriate 3-wire grounded power receptacle. 
 
Push the power switch to the “ON” position to apply power to the control. Press the 
set/reset key and turn the control knob to the desired temperature setting. Release the 
set/reset key once the desired temperature setting is set. The control will apply power to 
the load until the temperature setting is exceeded. Once the setting is exceeded, power 
will be removed from the load and a manual reset is required. The control is accurate 
/- 1% of full scale. 
 
 

Control Sensor 
 

The LimiTrol is furnished with a TC105 thermocouple. This probe is an Iron-Constantan 
thermocouple in a 6” stainless steel sheath. It is furnished with a 48” extension wire with 
stainless steel overbraid and a polarized plug. The control may be used with any Type J 
thermocouple which has a lead resistance less than 100 ohms. 
 
Proper placement of the thermocouple can eliminate many problems in the total system. 
The probe should be placed so that it can detect any temperature change with little 
thermal lag. In a process that requires fairly constant heat output, the probe should be 
close to the heater. In processes where heat demand is variable, the probe should be close 
to the work area. Some experimenting with probe location can be tried to provide 
optimum results. 
 

Maintenance 

Simple preventative maintenance steps include keeping the controller fairly clean. Protect 
it from excessive dirt, oil and corrosion. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 