0470
II 2G Ex db eb mb IIC T4 Gb
II 2D Ex tb IIIC T70°C Db
PRESAFE 15ATEX 7083X
IECEx PRE 15.0055X
Description:
Surface mounted
Ex luminaire emergency light HF-E or without emergency HF light for Zone 1
Temperature limits (ta):
HF: -30°C to 50°C (to 45°C for 58W)
HF-E: -20°C to 50°C
Line voltage:
For 18/36W: 110–254VAC 50/60Hz and 220–250VDC
For 58W: 220–254V AC 220–250V DC
Supplied current (mains mode): For 18W: 0.07–0.34A
For 36W: 0.13–0.59A
For 58W: 0.22–0.55A
Power factor:
0.95–0.98W
Light tube type:
T8 18W, 36W or 58W Bi-pin tubes with brass pins
For more information, please see www.glamox.com
L1
C1
60
85
128
165
C
L
50
115
150
111
L1 + 134
C1 + 134
124
165
Types
L1
C1
L
C = M8 Hood nuts distance
18W
724
704
681
400
430
500
36W
1334
1314
1291
500
700
950
58W
1634
1614
1591
700
-
1100
X:
Special conditions for safe use:
Potential electrostatic charging hazard – For cleaning use moist cloth only! No solvent.
WARNING:
Do not open when an explosive atmosphere is present!
Live parts behind cover – Do not contact!
Glamox MAX T8, 18W, 36W and 58 W
5
4
Installation and operation
MAX terminal Glamox 112 20556
Torque value for screws: 1.8Nm
Type and size of wires that can be used:
Solid wire: From 1.0mm² to 6.0mm²
Stranded wire with or without ferrule: From 0.75mm² to 6.0mm²
There can only be connected one wire on each side of the screw on
each side of each terminal. (totally max 4 wires at each terminal).
Earthing the luminaire
The luminaire must be earthed in the terminal block.
It can also be earthed external, to the contact on the luminaire house.
Shielded cable must be earthed as described in the drawing.
12mm
N
Earthing
Earthing of
shielded cable
L3 L2 L1 L4
M20
M25
Polyamid
5.0 Nm
8-13mm
7.5 Nm
12-18 mm
Torque
Cabel diameter
Brass
7.5 Nm
4-12mm
10.0 Nm
12-18mm
Torque
Cabel diameter